ERV WALL CONTROLLER
ODD-ERV-TIMER
Manwal ta' Istruzzjoni
ERV-TIMER Kontrollur tal-Ħajt ERV
TWISSIJA
TWISSIJA -L-INSTALLAZZJONI GĦANDHA JIĠI MSEĦĦA MINN ELETTRIKU KWALIFIKAT.
Electrical wiring must be done by qualified personnel in accordance with all applicable codes and standards. Before connecting wires, unplug the unit or switch power off at service panel and lock service disconnecting means to prevent power from being switched on accidentally. Always wear safety glasses and gloves while performing these insteuctions.
ATTENZJONI
In-nuqqas ta' konformità ma' dan li ġej jista' jikkawża tħaddim erratiku tal-kontroll u/jew l-unità:
- Never install more than three timer devices per ventilation unit. When used in conjunction with screen controller, do not install more than two timer devices
- Żomm kontroll baxx voltage wiring at least 1 foot (305 mm) away from motors, lighting balast, light dimming circuit and power distribution panel. Do not route control wiring alongside house power wiring Ensure the wires are securely connected
- Uża wajer cooper normali jew vol baxxtage wire to connect the unit with the controller, 30M length maximun or use a shielded wire,10M ideal
INSTALLAZZJONI
- Aqla 'l-unità tal-ventilazzjoni.
- Cut a 27/8″ X 13/4 ” hole in a wall, at a convenient location for the control. Route a cable (type 22/4) for the control from the unit to this hole. Seefigure at right.
- Poġġi temporanjament il-kontroll fuq it-toqba u mmarka ż-żewġ pożizzjonijiet tat-toqba tal-kamin tal-immuntar.
- Remove the control, drillboth screwholes (3/16″ o) in wall and insert the wall anchors (included).
- Strixxa t-tarf tal-kejbil biex taċċessa l-4 wajers (madwar 3″). Strixxa t-tarf ta 'kull wajer (madwar 1/4″). Qabbad il-wajers mat-terminals irrispettivament mill-kulur tal-wajer. Innota liema kulur tal-wajer ġie magħżul għal kull terminal.
- Immonta l-kontroll mal-ħajt.
- Wettaq il-konnessjoni elettrika mal-konnettur terminali tal-unità. Għal aktar dettalji, irreferi għall-manwal tal-installazzjoni tal-unità tal-ventilazzjoni.
NOTA: Biex tevita wajers ħażin, irreferi għan-noti meħuda fil-pass 5 biex tqabbel il-kulur tal-wajer mat-terminal it-tajjeb. - Ipplaggja l-unità tal-ventilazzjoni u ttestja l-kontroll tal-ħajt.

KIF GĦANDEK TUŻA
Il-buttuna prinċipali taħdem wara din is-sekwenza:
MODALITÀ:
- Kontroll
Push once for 20-minute, twice for 40-minute, or three times for 60-minute activation. Indicator lights up and the controlled unit goes to high speed.
Push once more to stop activation. Unit returns to its previous setting.
Tip ta' indikazzjoni:
LED 1 = 20 min timer huwa attiv
LED 2 = 40 min timer huwa attiv
LED 3 = 60 min timer huwa attiv
- Data Teknika
Ħruġ Voltage = 24V AC 10% or 24V DC 10%
Current Out = 100mA, max
Power Supply = 24V AC :10% or 24V DC±10%
Communication = protocol: Normally opened contact
User Interface = Push Button

www.ortechindustries.ca
1.888.543.6473
13376 Comber Way, Surrey, BC V3W 5V9
205 Triq Summerlea, Bramptunnellata, Ontario
info@ortechindustries.com
604.543.6473
R1![]()