L3 Campus Stackable Managed Switch
"
Speċifikazzjonijiet
- Mudell: Omada Campus Stackable L3 Managed Switch
- Front Panel: Mode Selection Button, Management Port, LED,
Console Port USB2.0 Port (Type-C/RJ45), 1G RJ45 Port, 10G SFP+ Slot
LED - Indikazzjoni LED:
- PWR1*: Green On (switch powered by PWR1), Off (PWR2
disconnected or not working properly) - PWR2: Green On (switch powered by PWR1 and PWR2 connected),
Yellow On** (PWR2 powered), Off (PWR1 disconnected or not working
sew) - LED SYS FAN: Green On (all fans work properly), Yellow On (not
all fans work properly) - MGMT: On (device linked to port), Flashing (transmitting or
receiving data), Off (no device linked to port) - MST: On (device linked to port), Flashing (transmitting or
receiving data), Off (no device linked to port)
- PWR1*: Green On (switch powered by PWR1), Off (PWR2
Istruzzjonijiet għall-Użu tal-Prodott
Kapitolu 2: Installazzjoni
Qabel ma tibda l-proċess ta 'installazzjoni, kun żgur li għandek kollox
the necessary tools and follow safety precautions.
- Kontenut tal-Pakkett: Check all items mentioned in
il-pakkett. - Prekawzjonijiet tas-Sigurtà: Follow the guidelines to
tiżgura installazzjoni sigura. - Għodod ta 'installazzjoni: Gather all tools required
għall-installazzjoni. - Installazzjoni tal-Prodott: Segwi l-pass pass
instructions provided in the manual for successful
installazzjoni.
Kapitolu 3: Konnessjoni
After installation, connect the switch to the network using
appropriate cables and ports as per your network setup.
Kapitolu 4: Konfigurazzjoni
Configure the switch based on your requirements. You can choose
between Standalone Mode or Controller Mode as per your network
bżonnijiet.
FAQ
Q: What should I do if the LED indications show an error?
A: If the LED indications suggest improper functioning, check
the power sources and connections. Refer to the troubleshooting
sezzjoni fil-manwal għal aktar għajnuna.
"`
Soluzzjoni għan-Netwerking tan-Negozju
Gwida għall-Installazzjoni
Omada Ċampus Stackable L3 Managed Switch
Dwar din il-Gwida għall-Installazzjoni
Din il-Gwida għall-Installazzjoni tiddeskrivi l-karatteristiċi tal-ħardwer, il-metodi ta 'installazzjoni u l-punti li għandhom jiġu attenduti matul l-installazzjoni. Din il-Gwida għall-Installazzjoni hija strutturata kif ġej: Kapitolu 1 Introduzzjoni Dan il-kapitolu jiddeskrivi l-komponenti esterni tas-swiċċ. Kapitolu 2 Installazzjoni Dan il-kapitlu juri kif tinstalla l-iswiċċ. Kapitolu 3 Konnessjoni Dan il-kapitlu juri kif tagħmel il-konnessjoni fiżika tas-swiċċ. Kapitolu 4 Konfigurazzjoni Dan il-kapitolu juri kif tikkonfigura l-iswiċċ. Appendiċi A Issolvi l-problemi Appendiċi B Speċifikazzjonijiet
Udjenza
Din il-Gwida għall-Installazzjoni hija għal:
Inġinier tan-Netwerk
Amministratur tan-Netwerk
Konvenzjonijiet
· Xi mudelli li jidhru f’din il-gwida jistgħu ma jkunux disponibbli f’pajjiżek jew fir-reġjun tiegħek. Għal informazzjoni dwar il-bejgħ lokali, żur https://www.omadanetworks.com/.
· Iċ-ċifri fil-Kapitolu 2, il-Kapitolu 3, u l-Kapitolu 4 huma għal skopijiet ta’ dimostrazzjoni biss. Is-swiċċ tiegħek jista' jkun differenti fid-dehra minn dak muri.
· Il-kalkoli tal-baġit PoE huma bbażati fuq ttestjar tal-laboratorju. Il-baġit attwali tal-enerġija PoE mhuwiex garantit u se jvarja bħala riżultat tal-limitazzjonijiet tal-klijent u fatturi ambjentali.
· Din il-gwida tuża l-formati speċifiċi biex tenfasizza messaġġi speċjali. It-tabella li ġejja telenka l-ikoni tal-avviż li jintużaw matul din il-gwida.
Fakkar li toqgħod attent. Attenzjoni tindika potenzjal li jista 'jirriżulta fi ħsara lill-apparat.
Fakkar li tieħu nota. In-nota fiha l-informazzjoni utli għal użu aħjar tal-prodott.
Dokument Relatat
Il-Gwida għall-Utent u l-Gwida ta 'Referenza CLI tal-prodott huma pprovduti fuq iċ-Ċentru tat-Tniżżil. Biex tikseb l-aħħar informazzjoni dwar il-prodott, żur l-uffiċjal websit: https://support.omadanetworks.com/document/.
Kontenut
Kapitolu 1 Introduzzjoni ———————- 01
1.1 Prodott Fuqview ………………………………………………..01 1.2 Id-dehra…………………………………………………………………………..01
Kapitolu 2 Installazzjoni ———————- 12
2.1 Il-Kontenut tal-Pakkett ……………………………………………….12 2.2 Prekawzjonijiet ta’ Sigurtà …………………………………………………12 2.3 Għodod ta’ Installazzjoni……………………………………………………..14 2.4 Installazzjoni tal-Prodott ………………………………………………..14
Kapitolu 3 Konnessjoni ———————- 22
3.1 Ethernet Port …………………………………………………………..22 3.2 10G SFP+/25G SFP28/100G QSFP28 Slot ………..22 3.3 Console Port ……………………………………………………………22 3.4 Verify Installation…………………………………………………….23 3.5 Power On ………………………………………………………………….24 3.6 Initialization………………………………………………………………24 3.7 Stack Topology ……………………………………………………….24
Kapitolu 4 Konfigurazzjoni ——————– 27
4.1 Konfigurazzjoni Overview…………………………………………27 4.2 Modalità Standalone……………………………………………………27 4.3 Modalità Kontrollur……………………………………………………28
Appendiċi A Issolvi l-problemi —————- 32
Appendiċi B Speċifikazzjonijiet —————— 33
Omada Ċampus Stackable L3 Managed Switch
Kapitolu 1 Introduzzjoni
1.1 Prodott Fuqview
Iddisinjat għal intrapriżi u kumpanijiampus, Omada Campus Stackable L3 Managed Switch provides wire-speed performance and abundant L2 and L3 management features. It provides a variety of service features and multiple powerful functions with high security. The EIA-standardized framework and smart configuration capacity can provide flexible solutions for a variable scale of networks. Static Routing, RIP, OSPF, BGP, IS-IS, PIM-SM/DM/SSM, and ECMP come with abundant Layer 3 routing protocols that support a scalable network. Physically stacking for builtin redundancy and performance. Redundant power supplies and fans make it an ideal choice for reliable networking architecture. VRRP allows a group of switches to dynamically back up each other. ERPS supports rapid protection and recovery in a ring topology. MACsec, secure boot, ACL, 802.1x and Dynamic ARP Inspection provide robust security strategies. QoS and IGMP snooping/filtering optimize voice and video application. Link aggregation (LACP) increases aggregated bandwidth, optimizing the transport of business critical data. SNMP, RMON, WEB, Netconf and CLI Log-in bring abundant management policies. These switches integrate multiple functions with excellent performance, and is friendly to manage, which can fully meet the need of the users demanding higher networking performance. S6500-24GP4XF/S6500-48GP6XF/S6500-24MPP4Y/S6500-48MPP6Y is also a Power Sourcing Equipment (PSE*). The RJ45 ports that support Power over Ethernet (PoE*) function can automatically detect and supply power to those powered devices (PDs*) complying with IEEE 802.3af, IEEE 802.3at, and IEEE 802.3bt (only for S6500-24MPP4Y/S6500-48MPP6Y). *PSE: a device (switch or hub for instance) that provides power through an Ethernet cable. *PoE: This technology describes a system to transmit electrical power, along with data, to remote devices over standard twisted-pair cable in an Ethernet. *PD: a device powered by a PSE and thus consumes energy. Exampil-les jinkludu l-enerġija ta' kameras tan-netwerk, punti ta' aċċess għal LAN mingħajr fili, telefowns IP, ċentri tan-netwerk, kompjuters inkorporati eċċ.
1.2 Dehra
Front Panel (The figure is for demonstration only. It may differ from your actual product. )
The front panel of S6500-24G4XF is shown as the following figure.
Buttuna tal-Għażla tal-Modalità
Ġestjoni tal-Port
LED
Console Port USB2.0 Port (Type-C/RJ45)
1G RJ45 Port
10G SFP+ Slot LED
The front panel of S6500-48G6XF is shown as the following figure.
Buttuna tal-Għażla tal-Modalità
Ġestjoni tal-Port
LED
Console Port USB2.0 Port (Type-C/RJ45)
1G RJ45 Port
10G SFP+ Slot LED
Introduzzjoni 01
Omada Ċampus Stackable L3 Managed Switch
Indikazzjoni LED
PWR1*
PWR2
Aħdar Mixgħul
Mitfi
Aħdar Mixgħul
Isfar Mixgħul**
Mitfi
Aħdar Mixgħul
Mitfi
Mitfi
Indikazzjoni
Is-swiċċ huwa mħaddem minn PWR1. PWR2 huwa skonnettjat jew jaħdem ħażin.
Is-swiċċ huwa mħaddem minn PWR1. PWR1 u PWR2 huma konnessi.*
Is-swiċċ huwa mħaddem minn PWR2. PWR1 huwa skonnettjat jew jaħdem ħażin.
Is-swiċċ huwa mitfi jew kemm PWR1 kif ukoll PWR2 jaħdmu ħażin.
LED SYS FAN
MGMT
MST
Port 1-24 of S6500-24G4XF/ Port 1-48 of S6500-48G6XF
(When the SPEED LED is on)
Port 1-24 of S6500-24G4XF/ Port 1-48 of S6500-48G6XF
(Meta l-LED STK ikun mixgħul)
Port 25-28 of S6500-24G4XF/ Port 49-54 of S6500-48G6XF ***
Indikazzjoni
Li jteptep: Is-swiċċ jaħdem sew. Mixgħul jew Mitfi: Is-swiċċ jaħdem ħażin.
Aħdar Mixgħul: Il-fannijiet kollha jaħdmu sew. Isfar Mixgħul: Mhux il-fannijiet kollha jaħdmu sew.
Mixgħul: Apparat huwa konness mal-port. Jteptep: Qed jittrażmetti jew jirċievi dejta. Mitfi: L-ebda apparat mhu konness mal-port.
Mixgħul: L-apparat jiffunzjona bħala s-swiċċ ewlieni fit-topoloġija tal-istack jew jaħdem individwalment. Mitfi: L-apparat jiffunzjona bħala s-swiċċ tal-membru fit-topoloġija tal-istack.
Aħdar Mixgħul: Taħdem b'1000 Mbps, iżda l-ebda attività. Green Flashing: Tħaddim b'1000 Mbps u tittrasmetti jew tirċievi data. Isfar Mixgħul: Taħdem b'10Mbps/100 Mbps, iżda l-ebda attività. Itteptep isfar: Tħaddim b'10Mbps/100 Mbps u tittrasmetti jew tirċievi data. Mitfi: L-ebda apparat mhu marbut mal-port korrispondenti.
Mixgħul: In-numru tal-port jindika l-ID tal-unità fit-topoloġija tal-munzell.
Aħdar Mixgħul: Taħdem b'10 Gbps, iżda l-ebda attività. Green Flashing: Tħaddim b'10 Gbps u tittrasmetti jew tirċievi data. Isfar Mixgħul: Taħdem b'1 Gbps, iżda l-ebda attività. Itteptep isfar: Tħaddim b'1 Gbps u tittrasmetti jew tirċievi data. Mitfi: L-ebda apparat mhu marbut mal-port korrispondenti.
*PWR1 is the primary power supply and it takes priority over PWR2. When the device is powered by PWR1, PWR2 will be working in the backup mode.
**Meta kemm PWR1 kif ukoll PWR2 jaħdmu sew u l-iswiċċ jitħaddem minn PWR1, tieħu 10-20 sekonda biex l-LED PWR2 (isfar) jintefa wara li PWR2 jiġi splaggjat.
***All 10 Gbps SFP+ slots can be used as uplink ports or stacking ports. When used as stacking ports, the slots need to run at the highest speed.
02 Introduzzjoni
Omada Ċampus Stackable L3 Managed Switch The front panel of S6500-24GP4XF is shown as the following figure.
Buttuna tal-Għażla tal-Modalità
Ġestjoni tal-Port
LED Console Port USB2.0 Port (Type-C/RJ45)
1G RJ45 Port
10G SFP+ Slot LED
Il-pannell ta 'quddiem ta' S6500-48GP6XF jidher bħala l-figura li ġejja.
Buttuna tal-Għażla tal-Modalità
Ġestjoni tal-Port
LED Console Port USB2.0 Port (Type-C/RJ45)
1G RJ45 Port
10G SFP+ Slot LED
The front panel of S6500-24M4Y is shown as the following figure.
Buttuna tal-Għażla tal-Modalità
Ġestjoni tal-Port
LED Console Port USB2.0 Port (Type-C/RJ45)
2.5G RJ45 Port
25G SFP28 Slot LED
The front panel of S6500-24MPP4Y is shown as the following figure.
Buttuna tal-Għażla tal-Modalità
Ġestjoni tal-Port
LED Console Port USB2.0 Port (Type-C/RJ45)
2.5G RJ45 Port
25G SFP28 Slot LED
Introduzzjoni 03
Omada Ċampus Stackable L3 Managed Switch The front panel of S6500-48M6Y is shown as the following figure.
Buttuna tal-Għażla tal-Modalità
Ġestjoni tal-Port
LED Console Port USB2.0 Port (Type-C/RJ45)
2.5G RJ45 Port
The front panel of S6500-48MPP6Y is shown as the following figure.
25G SFP28 Slot LED
Buttuna tal-Għażla tal-Modalità
Ġestjoni tal-Port
LED Console Port USB2.0 Port (Type-C/RJ45)
2.5G RJ45 Port
25G SFP28 Slot LED
LED Indication LED
PWR1* PWR2
SYS FAN PoE MAX
(For S6500-24GP4XF, S6500-48GP6XF, S6500-24MPP4Y, S6500-48MPP6Y)
MGMT
MST
Indikazzjoni
Green On: The power supply works properly. Green Flashing: The power supply module is not plugged in properly or not compatible with the switch. Yellow On: The power supply works properly but the switch is powered by the other power supply.** Yellow Flashing: The power supply module is plugged in properly but there’s is no AC power input; abnormal power supply. Off: No power supply module is inserted.
Li jteptep: Is-swiċċ jaħdem sew. Mixgħul jew Mitfi: Is-swiċċ jaħdem ħażin.
Aħdar Mixgħul: Il-fannijiet kollha jaħdmu sew. Isfar Mixgħul: Mhux il-fannijiet kollha jaħdmu sew.
Mixgħul: Il-qawwa PoE li fadal hija ta' 7 W. Jitteptep: Il-qawwa PoE li fadal iżżomm 7 W wara li dan l-LED ikun mixgħul għal 2 minuti. Mitfi: Il-bqija tal-qawwa PoE hija > 7 W.
Mixgħul: Apparat huwa konness mal-port. Jteptep: Qed jittrażmetti jew jirċievi dejta. Mitfi: L-ebda apparat mhu konness mal-port.
Mixgħul: L-apparat jiffunzjona bħala s-swiċċ ewlieni fit-topoloġija tal-istack jew jaħdem individwalment. Mitfi: L-apparat jiffunzjona bħala s-swiċċ tal-membru fit-topoloġija tal-istack.
04 Introduzzjoni
Omada Ċampus Stackable L3 Managed Switch
LED
Indikazzjoni
Port 1-24 of S6500-24GP4XF/
Port 1-48 of S6500-48GP6XF
(When the SPEED LED is on)
Aħdar Mixgħul: Taħdem b'1000 Mbps, iżda l-ebda attività. Green Flashing: Tħaddim b'1000 Mbps u tittrasmetti jew tirċievi data. Isfar Mixgħul: Taħdem b'10Mbps/100 Mbps, iżda l-ebda attività. Itteptep isfar: Tħaddim b'10Mbps/100 Mbps u tittrasmetti jew tirċievi data. Mitfi: L-ebda apparat mhu marbut mal-port korrispondenti.
Port 1-24 of S6500-24M4Y & S6500-24MPP4Y/
Port 1-48 of S6500-48M6Y & S6500-48MPP6Y
(When the SPEED LED is on)
Green On: Running at 2.5 Gbps, but no activity. Green Flashing: Running at 2.5 Gbps and transmitting or receiving data. Yellow On: Running at 10 Mbps/100 Mbps/1000 Mbps, but no activity. Yellow Flashing: Running at 10 Mbps/100 Mbps/1000 Mbps and transmitting or receiving data. Off: No device is linked to the corresponding port.
Port 1-24 of S6500-24GP4XF, S6500-24M4Y &
S6500-24MPP4Y/
Port 1-48 of S6500-48GP6XF, S6500-48M6Y &
S6500-48MPP6Y
(Meta l-LED STK ikun mixgħul)
Mixgħul: In-numru tal-port jindika l-ID tal-unità fit-topoloġija tal-munzell.
Port 1-24 of S6500-24GP4XF & S6500-24MPP4Y/
Port 1-48 of S6500-48GP6XF & S6500-48MPP6Y
(Meta l-LED PoE ikun mixgħul)
Green On: The port is supplying power normally. Green Flashing: The supply power exceeds the correponding port’s maximum power. Yellow On: Overload or short circuit is detected. Off: Not providing PoE power on the port
Port 25-28 of S6500-24GP4XF/ Port 49-54 of S6500-48GP6XF ***
Aħdar Mixgħul: Taħdem b'10 Gbps, iżda l-ebda attività. Green Flashing: Tħaddim b'10 Gbps u tittrasmetti jew tirċievi data. Isfar Mixgħul: Taħdem b'1 Gbps, iżda l-ebda attività. Itteptep isfar: Tħaddim b'1 Gbps u tittrasmetti jew tirċievi data. Mitfi: L-ebda apparat mhu marbut mal-port korrispondenti.
Port 25-28 of S6500-24M4Y & S6500-24MPP4Y/
Port 49-54 of S6500-48M6Y & S6500-48MPP6Y***
Aħdar Mixgħul: Jaħdem b'25 Gbps, iżda mingħajr attività. Aħdar Jteptep: Jaħdem b'25 Gbps u qed jittrażmetti jew jirċievi dejta. Isfar Mixgħul: Jaħdem b'1 Gbps/10 Gbps, iżda mingħajr attività. Isfar Jteptep: Jaħdem b'1 Gbps/10 Gbps u qed jittrażmetti jew jirċievi dejta. Mitfi: L-ebda apparat mhu konness mal-port korrispondenti.
*By default, S6500-24GP4XF is shipped with a PSM500-AC power supply module, S6500-24M4Y/S650048M6Y is shipped with a PSM550-AC power supply module, and S6500-48GP6XF/S6500-24MPP4Y/ S6500-48MPP6Y is shipped with a PSM900-AC power supply module. One more power supply module needs to be purchased separately.
**By default, both PWR1 and PWR2 will work simultaneously in the load sharing mode. They can also work simultaneously in the redundant power supply mode: for S6500-24GP4XF/S6500-48GP6XF/S650024MPP4Y/S6500-48MPP6Y, you can specify the primary power supply and the backup power supply according to your needs; for S6500-24M4Y/S6500-48M6Y, you can only set PWR1 as the primary power supply and PWR2 as the backup power supply. Generally, the primary power supply takes priority over the backup power supply.
***All 10 Gbps SFP+ slots and 25 Gbps SFP28 slots can be used as uplink ports or stacking ports. When used as stacking ports, the slots need to run at the highest speed.
Introduzzjoni 05
Omada Ċampus Stackable L3 Managed Switch The front panel of S7500-26XF6Y is shown as the following figure.
Ġestjoni tal-Port
LED
Console Port USB3.0 Port
(RJ45/Tip Ċ)
Għażla tal-Modalità
Buttuna
10G SFP+ Slot (Port 1-26)
The front panel of S7500-48XF4C is shown as the following figure.
LED 25G SFP28 Slot (Port 27-32)
Buttuna tal-Għażla tal-Modalità
Ġestjoni tal-Port
LED Console Port USB3.0 Port (Type-C/RJ45)
10G SFP+ Slot (Port 1-48)
The front panel of S7500-24Y4C is shown as the following figure.
100G QSFP28 Slot LED (Port 49-52)
Ġestjoni tal-Port
LED
Port USB3.0
Port tal-Console
(RJ45/Tip Ċ)
Buttuna tal-Għażla tal-Modalità
Slott ta' 25G SFP28
LED
(Port 1-24)
The front panel of S7500-48Y8C is shown as the following figure.
Slott ta' 100G QSFP28 (Port 25-28)
LED Mode Selection Button
25G SFP28 Slot (Port 1-48)
06 Introduzzjoni
Slott ta' 100G QSFP28 (Port 49-56)
Omada Ċampus Stackable L3 Managed Switch The front panel of S7500-32C is shown as the following figure.
Buttuna tal-Għażla tal-Modalità
Port ta 'Ġestjoni LED
Port USB3.0
Console Port (Type-C/RJ45)
Slott ta' 100G QSFP28
LED
Note: S7500-24Y4C and S7500-48Y8C are designed for installation in Network Telecommunications Facilities (NTFs) where ambient temperature and humidity are controlled.
LED Indication LED
PWR1* PWR2
SYS FAN
MGMT
MST
Port 1-26 of S7500-26XF6Y/ Port 1-48 of S7500-48XF4C
(Meta l-LED SPD ikun mixgħul)
Port 1-24 of S7500-24Y4C/ Port 1-48 of S7500-48Y8C
(When the SPD/SPEED LED is on)
Indikazzjoni
Green On: The power supply works properly. Green Flashing: The power supply module is not plugged in properly or not compatible with the switch. Yellow On: The power supply works properly but the switch is powered by the other power supply.** Yellow Flashing: The power supply module is plugged in properly but there’s is no AC power input; abnormal power supply. Off: No power supply module is inserted.
Li jteptep: Is-swiċċ jaħdem sew. Mixgħul jew Mitfi: Is-swiċċ jaħdem ħażin.
Aħdar: Il-fannijiet kollha jaħdmu sew. Isfar: Mhux il-fannijiet kollha jaħdmu sew.
Mixgħul: Apparat huwa konness mal-port. Jteptep: Qed jittrażmetti jew jirċievi dejta. Mitfi: L-ebda apparat mhu konness mal-port.
Nota:
For S7500-48Y8C, this LED lights green at 1 Gbps and orange at sub-1 Gbps.
Mixgħul: L-apparat jiffunzjona bħala s-swiċċ ewlieni fit-topoloġija tal-istack jew jaħdem individwalment. Mitfi: L-apparat jiffunzjona bħala s-swiċċ tal-membru fit-topoloġija tal-istack.
Aħdar Mixgħul: Taħdem b'10 Gbps, iżda l-ebda attività. Green Flashing: Tħaddim b'10 Gbps u tittrasmetti jew tirċievi data. Isfar Mixgħul: Taħdem b'1 Gbps, iżda l-ebda attività. Itteptep isfar: Tħaddim b'1 Gbps u tittrasmetti jew tirċievi data. Mitfi: L-ebda apparat mhu marbut mal-port korrispondenti.
Aħdar Mixgħul: Jaħdem b'25 Gbps, iżda mingħajr attività. Aħdar Jteptep: Jaħdem b'25 Gbps u qed jittrażmetti jew jirċievi dejta. Isfar Mixgħul: Jaħdem b'1 Gbps/10 Gbps, iżda mingħajr attività. Isfar Jteptep: Jaħdem b'1 Gbps/10 Gbps u qed jittrażmetti jew jirċievi dejta. Mitfi: L-ebda apparat mhu konness mal-port korrispondenti.
Introduzzjoni 07
Omada Ċampus Stackable L3 Managed Switch
LED
Indikazzjoni
Port 27-32 of S7500-26XF6Y ***
(Meta l-LED SPD ikun mixgħul)
Aħdar Mixgħul: Jaħdem b'25 Gbps, iżda mingħajr attività. Aħdar Jteptep: Jaħdem b'25 Gbps u qed jittrażmetti jew jirċievi dejta. Isfar Mixgħul: Jaħdem b'1 Gbps/10 Gbps, iżda mingħajr attività. Isfar Jteptep: Jaħdem b'1 Gbps/10 Gbps u qed jittrażmetti jew jirċievi dejta. Mitfi: L-ebda apparat mhu konness mal-port korrispondenti.
Port 49-52 of S7500-48XF4C/
Port 25-28 of S7500-24Y4C/ Port 49-56 of S7500-48Y8C/ Port 1-32 of S7500-32C***
(When the SPD/SPEED LED is on)
Aħdar Mixgħul: Taħdem b'100 Gbps, iżda l-ebda attività. Green Flashing: Tħaddim b'100 Gbps u tittrasmetti jew tirċievi data. Isfar Mixgħul: Taħdem b'40 Gbps, iżda l-ebda attività. Itteptep isfar: Tħaddim b'40 Gbps u tittrasmetti jew tirċievi data. Mitfi: L-ebda apparat mhu marbut mal-port korrispondenti.
Nota:
For S7500-48XF4C/S7500-48Y8C/S7500-32C, the indication above applies only when the 100 Gbps QSFP28 slots work with common cables. When the slots work with 1-to-4 breakout cables, a single slot is split into four 25 Gbps interfaces. In such scenario, the LED will light green only when all four interfaces are working at 25 Gbps (maximum speed), otherwise it will light yellow. When no device is connected to any of the four interfaces, the LED will be off. (The 100 Gbps QSFP28 slots will support 1-to-4 breakout cables in a future software release.)
Port 1-32 of S7500-26XF6Y/
Port 1-48 of S7500-48XF4C/ Port 1-28 of S7500-24Y4C/ Port 1-56 of S7500-48Y8C
(Meta l-LED STK ikun mixgħul)
Mixgħul: In-numru tal-port jindika l-ID tal-unità fit-topoloġija tal-munzell.
*By default, S7500-26XF6Y/S7500-48XF4C/S7500-24Y4C/S7500-48Y8C/S7500-32C is shipped with a PSM550-AC power supply module installed respectively. One more power supply module needs to be purchased separately. **By default, both PWR1 and PWR2 will work simultaneously in the load sharing mode. They can also work simultaneously in the redundant power supply mode with PWR1 as the primary power supply and PWR2 as the backup power supply. Generally, the primary power supply takes priority over the backup power supply. ***All 25 Gbps SFP28 slots of S7500-26XF6Y and 100 Gbps QSFP28 slots of S7500-48XF4C/S7500-24Y4C/ S7500-48Y8C/S7500-32C can be used as uplink ports or stacking ports. When used as stacking ports, the slots need to run at the highest speed.
Port Introduction (The Management Port, Console Ports, and USB Ports of S7500-48Y8C are located on the rear panel.)
Port tal-Ġestjoni Iddisinjat biex jikkonnettja l-apparat għall-ġestjoni permezz ta' web, CLI or SNMP. Do not connect this port to any outdoor device, as this may induce surge and lightning damage. Console Port Designed to connect with a computer for monitoring and configuring the switch. When the switch has an RJ45 console port and a Type-C console port, console input is active on only one console port at a time. By default, the Type-C connector takes priority over the RJ45 connector, or you can change the priority through the web. Do not connect this port to any outdoor device, as this may induce surge and lightning damage. USB Port Designed to install the USB flash disk for data storage. 1000M RJ45 Port Designed to connect to the device with a bandwidth of 10Mbps, 100 Mbps or 1000 Mbps. For PoE switches, the port can also provide power for PDs.
08 Introduzzjoni
Omada Ċampus Stackable L3 Managed Switch
2.5G RJ45 Port Designed to connect to the device with a bandwidth of 10 Mbps, 100 Mbps, 1000 Mbps or 2.5 Gbps. For PoE switches, the port can also provide power for PDs. 10G SFP+ Slot Designed to install the 10 Gbps/1 Gbps optical module. 25G SFP28 Slot Designed to install the 25 Gbps/10 Gbps/1 Gbps optical module. 100G QSFP28 Slot Designed to install the 100 Gbps/40 Gbps optical module. Port Feature
Mudell
1000M
2.5G 10G SFP+ 25G SFP28 100G QSFP28 Management Console USB
RJ45 Port RJ45 Port Slot
Slott
Slott
Port
Port Port
S6500-24G4XF
24
/
4
/
/
S6500-48G6XF
48
/
6
/
/
S6500-24GP4XF
24
/
4
/
/
S6500-48GP6XF
48
/
6
/
/
S6500-24M4Y
/
24
/
4
/
S6500-24MPP4Y
/
24
/
4
/
S6500-48M6Y
/
48
/
6
/
S6500-48MPP6Y
/
48
/
6
/
S7500-26XF6Y
/
/
26
6
/
S7500-48XF4C
/
/
48
/
4
S7500-24Y4C
/
/
/
24
4
S7500-48Y8C
/
/
/
48
8
S7500-32C
/
/
/
/
32
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
1
2
2
Rear Panel (The figure is for demonstration only. It may differ from your actual product. )
The rear panel of S6500-24G4XF/S6500-48G6XF is shown as the following figure. The figure is for demonstration purposes only. Your switch may differ in appearance from the depicted.
Kensington Security Slot Grounding Terminal Power Socket
Locking Strap Slot
Nota: PWR1 hija l-provvista tal-enerġija primarja u tieħu prijorità fuq PWR2.
Introduzzjoni 09
Omada Ċampus Stackable L3 Managed Switch
The rear panel of S6500-24GP4XF/S6500-48GP6XF/S6500-24MPP4Y/S6500-48MPP6Y is shown as the following figure. The figure is for demonstration purposes only. Your switch may differ in appearance from the depicted.
Slot tas-Sigurtà ta' Kensington
LED
Terminal tal-Art
Modulu tal-Provvista tal-Enerġija
LED
Locking Strap Slot
Note: By default, S6500-24GP4XF is shipped with a PSM500-AC power supply module, and S650048GP6XF/S6500-24MPP4Y/S6500-48MPP6Y is shipped with a PSM900-AC power supply module. One more power supply module needs to be purchased separately. Both PWR 1 and PWR2 can work simultaneously, or you can specify the primary power supply and the backup power supply according to your needs. Generally, the primary power supply takes priority over the backup power supply.
The rear panel of S6500-24M4Y/S6500-48M6Y/S7500-26XF6Y/S7500-48XF4C/S7500-24Y4C is shown as the following figure. The figure is for demonstration purposes only. Your switch may differ in appearance from the depicted.
Terminal tal-Art
LED
Power Supply Module Locking Strap Slot
LED
Slot tas-Sigurtà ta' Kensington
Note: By default, the device is shipped with a PSM550-AC power supply module installed. One more power supply module needs to be purchased separately. When the switch has two power supply modules installed, both PWR1 and PWR2 will work simultaneously in the load sharing mode by default. They can also work simultaneously in the redundant power supply mode: for S6500-24M4Y/S6500-48M6Y, you can only set PWR1 as the primary power supply and PWR2 as the backup power supply; for S7500-26XF6Y/S7500-48XF4C/S7500-24Y4C, you can specify the primary power supply and the backup power supply according to your needs; Generally, the primary power supply takes priority over the backup power supply.
Il-pannell ta' wara tal-S7500-48Y8C jidher fil-figura li ġejja. Il-figura hija għal skopijiet ta' dimostrazzjoni biss. Is-swiċċ tiegħek jista' jkun differenti fid-dehra minn dak muri.
Terminal tal-Art
LED
LED
Ċinga tal-qfil
Slott
Modulu tal-Provvista tal-Enerġija
10 Introduzzjoni
ManagemeC(nTtoyPnposeor-tCle/RPJoU4rt5S)B3P.o0wPeorrSt upplyLoMcokdiSnulgoletStraLpED
Omada Ċampus Stackable L3 Managed Switch
Note: By default, the device is shipped with a PSM550-AC power supply module installed. One more power supply module needs to be purchased separately. When the switch has two power supply modules installed, both PWR1 and PWR2 will work simultaneously in the load sharing mode by default. They can also work simultaneously in the redundant power supply mode with PWR1 as the primary power supply and PWR2 as the backup power supply. Generally, the primary power supply takes priority over the backup power supply.
The rear panel of S7500-32C is shown as the following figure. The figure is for demonstration purposes only. Your switch may differ in appearance from the depicted.
LED LED
Locking Strap Slot
Modulu tal-Provvista tal-Enerġija Slott tas-Sigurtà Kensington
Terminal tal-Art
LED
Locking Strap Slot
Modulu tal-Provvista tal-Enerġija
Note: By default, the device is shipped with a PSM550-AC power supply module installed. One more power supply module needs to be purchased separately. When the switch has two power supply modules installed, both PWR1 and PWR2 will work simultaneously in the load sharing mode by default. They can also work simultaneously in the redundant power supply mode with PWR1 as the primary power supply and PWR2 as the backup power supply. Generally, the primary power supply takes priority over the backup power supply.
Power Supply Module The pluggable power supply module PSM500-AC/PSM900-AC/PSM550-AC is an AC-input power supply module. It can convert the input voltage to 53.5 V (12 V for PSM550-AC) with the maximum output power of 500 W/900 W/550 W respectively. Kensington Security Slot Secure the lock (not provided) into the security slot to prevent the device from being stolen.
Grounding Terminal The switch already comes with lightning protection mechanism. You can also ground the switch through the PE (Protecting Earth) cable of AC cord or with Ground Cable. For detailed lightning protection measures, refer to the Lightning Protection Guide from: https://support.omadanetworks.com/r/1004/. Locking Strap Slot Remove the instruction label and insert the AC power cable locking strap into the slot to secure the power cable.
Introduzzjoni 11
Omada Ċampus Stackable L3 Managed Switch
Kapitolu 2 Installazzjoni
2.1 Kontenut tal-Pakkett
Kun żgur li l-pakkett ikun fih l-oġġetti li ġejjin. Jekk jogħġbok ikkuntattja lid-distributur tiegħek, jekk xi wieħed mill-oġġetti elenkati huwa bil-ħsara jew nieqes. Iċ-ċifri huma għal dimostrazzjoni biss. L-oġġetti attwali jistgħu jvarjaw fid-dehra u l-kwantità minn dawk murija.
Aqleb
Kejbil tal-Enerġija u Kejbil tal-Konsola
Gwida għall-Installazzjoni
Soluzzjoni għan-Netwerking tan-Negozju
Gwida għall-Installazzjoni
Omada Ċampus Stackable L3 Managed Switch
Brazzi tal-Immuntar, Viti u Saqajn tal-Gomma
2.2 Prekawzjonijiet tas-Sigurtà
Biex tevita kwalunkwe ħsara lill-apparat u korriment tal-ġisem ikkawżat minn użu mhux xieraq, għandek tosserva r-regoli li ġejjin.
Prekawzjonijiet ta' Sigurtà Żomm l-elettriku mitfi waqt l-installazzjoni. Ilbes ċinga tal-polz li tipprevjeni l-ESD, u kun żgur li ċ-ċinga tal-polz tkun f'kuntatt tajjeb mal-ġilda u li tkun
ertjat sew. Uża biss il-korda tal-enerġija pprovduta mas-swiċċ. Kun żgur li l-vultaġġ tal-provvistatage jaqbel mal-ispeċifikazzjonijiet indikati fuq il-pannell ta 'wara tal-
swiċċ. Kun żgur li s-swiċċ huwa installat f'ambjent ventilat tajjeb u t-toqba tal-ventilazzjoni tiegħu mhix
imblukkata. Tiftaħx jew tneħħi l-għatu tas-swiċċ. Qabel ma tnaddaf l-apparat, aqta 'l-provvista tal-enerġija. Tnaddafx bid-drapp waterish, u qatt
use any other liquid cleaning method. Place the device with its bottom surface facing downwards. Only instructed person or skilled person can be allowed to install, replace, or service this device.
Rekwiżiti tas-Sit
Temperatura/Umdità
12 Installazzjoni
Omada Ċampus Stackable L3 Managed Switch Keep the equipment room at an appropriate level of temperature and humidity. Too much or too little humidity may lead to bad insulation, leakage of electricity, mechanical property changes, and corrosion. High temperatures may accelerate aging of the insulation materials, significantly shortening the service life of the device. To find out the best temperature and humidity conditions for the device, check the Appendix B Specifications. Clearness
It-trab akkumulat fuq is-swiċċ jista 'jiġi assorbit mill-elettriku statiku u jirriżulta f'kuntatt ħażin tal-punti ta' kuntatt tal-metall. Ittieħdu xi miżuri għall-apparat biex jipprevjeni l-elettriku statiku, iżda l-elettriku statiku qawwi wisq jista 'jikkawża ħsara fatali lill-elementi elettroniċi fuq il-bord taċ-ċirkwit intern. Biex tevita l-effett tal-elettriku statiku fuq it-tħaddim tas-swiċċ, agħti ħafna importanza lill-oġġetti li ġejjin: It-trab tal-apparat regolarment, u żomm l-arja ta 'ġewwa nadifa. Żomm l-apparat ertjat sew u kun żgur li l-elettriku statiku ġie trasferit. Interferenza Elettromanjetika
L-elementi elettroniċi inklużi l-kapaċità u l-inductance fuq l-apparat jistgħu jiġu affettwati minn interferenzi esterni, bħal emissjoni kondotta permezz ta 'akkoppjar ta' kapaċità, akkoppjar ta 'inductance, u akkoppjar ta' impedenza. Biex tnaqqas l-interferenzi, kun żgur li tieħu l-miżuri li ġejjin: Uża l-provvista tal-enerġija li tista 'effettivament tiffiltra l-interferenza mill-grilja tal-enerġija. Żomm l-apparat 'il bogħod minn apparati ta' frekwenza għolja u kurrent qawwi bħat-trażmissjoni tar-radju
stazzjon. Uża lqugħ elettromanjetiku meta meħtieġ. Protezzjoni mis-sajjetti
Installazzjoni 13
Omada Ċampus Stackable L3 Managed Switch
Vol estremament għolitagIl-kurrenti jistgħu jiġu prodotti istantanjament meta sseħħ is-sajjetti u l-arja fil-mogħdija ta 'skarika elettrika tista' tissaħħan istantanjament sa 20,000 °C. Peress li dan il-kurrent instantanju huwa b'saħħtu biżżejjed biex jagħmel ħsara lill-apparat elettroniku, għandhom jittieħdu miżuri ta 'protezzjoni mis-sajjetti aktar effettivi. Kun żgur li r-rack u l-apparat ikunu ertjati sew. Kun żgur li s-sokit tal-enerġija għandu kuntatt tajjeb mal-art. Żomm sistema ta 'kejbils raġonevoli u evita sajjetti indotti. Uża s-sinjal SPD (Surge Protective Device) meta wajers barra.
Nota: Għal miżuri dettaljati ta' protezzjoni mis-sajjetti, irreferi għall-Gwida għall-Protezzjoni mis-Sajjetti minn: https://support.omadanetworks.com/r/1004/. Sit tal-Installazzjoni
When installing the device on a rack or a flat workbench, attach much importance to the following items: Install the device with its bottom surface facing down only. This equipment is not suitable for use in locations where children are likely to be present. The rack or workbench is flat, stable, and sturdy enough to support the weight of 9.5 kg at least. The rack or workbench has a good ventilation system. The equipment room is well ventilated. The rack is well grounded. Keep the device less than 1.5 meters away from the power socket.
2.3 Għodod ta 'Installazzjoni
Phillips tornavit Kejbils tal-polz preventiv ESD
Nota: Dawn l-għodod mhumiex inklużi mal-prodott tagħna. Jekk meħtieġ, tista 'tixtrihom separatament.
2.4 Installazzjoni tal-Prodott
Is-swiċċ huwa ddisinjat b'karatteristika ta 'dissipazzjoni tas-sħana minn quddiem għal wara. Meta taħdem, l-arja tiċċirkola kif muri hawn taħt. Għal dissipazzjoni aħjar tas-sħana, jekk jogħġbok installa l-apparat f'ambjent ventilat tajjeb u ħalli 5 sa 10 ċm vojt madwar l-apparat.
14 Installazzjoni
Figura 2-1
Ċirkolazzjoni ta' l-Arja
Omada Ċampus Stackable L3 Managed Switch
Installazzjoni tad-Desktop
Biex tinstalla l-apparat fuq id-desktop, segwi l-passi:
1. Issettja l-apparat fuq wiċċ ċatt li huwa b'saħħtu biżżejjed biex isostni l-piż kollu tal-apparat bil-fittings kollha.
2. Neħħi l-karti li jwaħħlu li jeħlu mis-saqajn tal-lastku.
3. Waħħal is-saqajn tal-gomma mal-qiegħ tal-apparat biex tevita li jiżloq meta titqiegħed fuq id-desktop.
Figura 2-2
Installazzjoni tad-Desktop
Saqajn Qiegħ tal-Notch tal-Apparat
Installazzjoni ta 'rack
Il-pakkett jinkludi 6 pari ta 'parentesi differenti ta' immuntar ta 'rack, l-istampi tagħhom huma murija hawn taħt u jistgħu jkunu differenti mill-prodotti attwali.
Figura 2-3
Brazzi tal-Immuntar
Grupp tat-Toqob tal-Viti 2
Bracket D Bracket C Bracket B Bracket A
Grupp tat-Toqob tal-Viti 1
Grupp tat-Toqob tal-Viti 3
Parentesi F
Screw Hole Group 4-2 (for device with 420mm depth)
Grupp tat-Toqob tal-Viti 5
Toqba tal-Invita
Grupp 4-1
Screw Hole Group 4-3
(for device with 380mm depth)
(for device with
460mm depth)
Bracket E
Installazzjoni 15
Omada Ċampus Stackable L3 Managed Switch
Before installing the device in an EIA standard-sized, 19-inch rack, please check the efficiency of the grounding system and the stability of the rack, then wear an ESD-preventive wrist strap, and make sure that it has good skin contact and is well grounded. Bracket B, C & E have two adjustable ears, please measure the distance between the front-post rack and the rear-post rack, and determine a suitable mounting method from below:
Metodu
Dimostrazzjoni
Front: Bracket A Rear: Bracket D (Screw Hole Group 1) + Bracket B (Ear towards back)
Distanza tar-Rack
(For device with a depth of 380mm)
Distanza tar-Rack
(For device with a depth of 420mm)
Distanza tar-Rack
(For device with a depth of 460mm)
498-640mm 538-680mm 578-720mm
Front: Bracket A Rear: Bracket D (Screw Hole Group 1) + Bracket C (Ear towards back)
477-498mm 517-538mm 557-578mm
Front: Bracket A Rear: Bracket D (Screw Hole Group 2) + Bracket C (Ear towards back)
429-477mm 469-517mm 509-557mm
Front: Bracket A Rear: Bracket D (Screw Hole Group 2) + Bracket C (Ear towards front)
410-429mm 450-469mm 490-509mm
Front: Bracket A Rear: Bracket D (Screw Hole Group 3) + Bracket C (Ear towards back)
357-410mm 397-450mm 437-490mm
Front: Bracket A Rear: Bracket D (Screw Hole Group 2) + Bracket B (Ear towards back)
282-410mm 322-450mm 362-490mm
16 Installazzjoni
Omada Ċampus Stackable L3 Managed Switch
Front: Bracket A Rear: Bracket F (Screw Hole Group 4) + Bracket E (Ear towards back)
555-936mm 555-936mm 555-936mm
Front: Bracket A Rear: Bracket F (Screw Hole Group 5) + Bracket E (Ear towards back)
743-1121mm 743-1121mm 743-1121mm
Biex tinstalla l-apparat, segwi l-istruzzjonijiet deskritti hawn taħt:
1. Attach the M6 nuts to the racks.
Figura 2-4
L-Iżgurar tal-Ġewż M6
×8
2. Attach the mounting brackets (B, C or E) to the rear-post racks and secure them with the provided M6 screws, as illustrated in the following figure.
Figura 2-5
Installazzjoni ta' Brackets fuq Racks
or
3. Attach the brackets A & D/F to the switch with the provided M3 screws.
Installazzjoni 17
Omada Ċampus Stackable L3 Managed Switch
Figura 2-6
Installazzjoni ta' Brackets fuq is-Swiċċ
4. After the brackets are attached to the device, hold the switch with attached brackets up until it aligns with the brackets on the racks, and gently push the switch backwards until it is in place, then secure the device on the racks with M6 screws and fix brackets B/C or E to brackets D or F with M4 screws on both sides.
Figura 2-7
Installazzjoni ta' Swiċċijiet fuq Racks
Caution: Leave 5 to 10 cm gaps around the devices for air circulation. Avoid placing heavy things on the device. Mount devices in the order demonstrated above and ensure a certain clearance between devices for
the purpose of heat dissipation.
18 Installazzjoni
Omada Ċampus Stackable L3 Managed Switch
Installazzjoni tal-Modulu tal-Provvista tal-Enerġija
S6500-24GP4XF is shipped with a PSM500-AC power supply module installed, S6500-48GP6XF/ S6500-24MPP4Y/S6500-48MPP6Y is shipped with a PSM900-AC power supply module installed, and S6500-24M4Y/S6500-48M6Y/S7500-26XF6Y/S7500-48XF4C/S7500-24Y4C/S7500-48Y8C/S750032C is shipped with a PSM550-AC power supply module installed. It looks like below, and the image may differ from your actual product.
Figura 2-8
Id-Dehra tal-Modulu tal-Provvista tal-Enerġija
Konnettur tal-Kurdun tal-Enerġija AC
FAN
Clips Retainer
Manku tal-Estrazzjoni
LED
Locking Strap Slot Release Handle
Jekk għandek bżonn iżżid modulu ieħor tal-provvista tal-enerġija, jekk jogħġbok segwi l-passi:
1. Ilbes ċinga tal-polz li tipprevjeni l-ESD, u kun żgur li jkollha kuntatt tajjeb mal-ġilda u li tkun ertjata sew.
2. Agħfas il-manku tal-estrazzjoni tal-modulu b'id waħda, u żomm il-qiegħ tal-modulu bl-id l-oħra. Imbotta l-modulu bil-mod 'il ġewwa tul il-binarju gwida tas-slott.
3. Itlaq il-manku tal-estrazzjoni biex twaħħal il-modulu tal-provvista tal-enerġija f'postu.
Figura 2-9
Installazzjoni tal-Modulu tal-Provvista tal-Enerġija
Rilaxx Manku
Caution: Do not plug the power cord until the power supply module installation is completed. When installing a power supply module, make sure it is set correctly in the operation of installation. Do not use too much force in the installation. If resistance is encountered or positions of the power
supply module appear larger during installation, you must first remove the module and then reinstall the module. If the Retainer Clips cannot spring up naturally and the power module is blocked, it may be due to the power supply module is not installed properly. Please check carefully.
The power supply module is designed with a locking strap slot. If you need to secure the power cable with the included locking strap, please follow the steps:
1. Ilbes ċinga tal-polz li tipprevjeni l-ESD, u kun żgur li jkollha kuntatt tajjeb mal-ġilda u li tkun ertjata sew.
Installazzjoni 19
Omada Ċampus Stackable L3 Managed Switch
2. Remove the instruction label on the AC power cable locking strap slot. 3. Attach the clamp to the AC power cable and insert the locking strap into the slot. 4. Adjust tightness and distance of the locking strap using clips to ensure the cable is securely fastened.
Figure 2-10 Installing the Locking Strap
Jekk għandek bżonn tneħħi l-modulu tal-provvista tal-enerġija, jekk jogħġbok segwi l-passi:
1. Ilbes ċinga tal-polz li tipprevjeni l-ESD, u kun żgur li jkollha kuntatt tajjeb mal-ġilda u li tkun ertjata sew.
2. Depress the retainer clip to release the locking strap, and then remove the power cord from the external power supply system and the power module.
3. Press the extraction handle of the module with one hand, and pull the extraction handle using your other hand, until the module completely comes out of the chassis.
Caution: Unplug the power cord first, then remove the power supply module. When removing a power supply module, make sure that the power supply module is set correctly in the
operation of installation. In order to better protect the power supply module during removal, it is recommended that you
package it in an antistatic bag.
Installazzjoni tal-Modulu tal-Fann
S6500-24GP4XF/S6500-48GP6XF/S6500-24M4Y/S6500-24MPP4Y/S6500-48M6Y/S650048MPP6Y/S7500-26XF6Y/S7500-48XF4C/S7500-24Y4C/S7500-48Y8C/S7500-32C is shipped with hot-swappable fan modules installed. They look like below, and the images may differ from your actual product.
Figura 2-11 Id-Dehra tal-Modulu tal-Fan
LED
20 Installazzjoni
Extraction Handle Retainer Clips Release Handle
Omada Ċampus Stackable L3 Managed Switch For normal operation of the switch, please ensure that models with 5 fan modules maintain at least 4 operational modules, while models with 4 fan modules maintain at least 3 operational modules. If one fan module is damaged, please replace it as follows: 1. Wear an ESD-preventive wrist strap, and make sure that it has good skin contact and is well
ertjat. 2. Agħfas il-manku tal-estrazzjoni tal-modulu b'id waħda, u iġbed il-manku tal-estrazzjoni sakemm
Il-modulu joħroġ kompletament mix-chassis.
Figura 2-12 It-Tneħħija ta' Modulu Fan Danneġġjat
3. Press the extraction handle of a new fan module with one hand, and hold the bottom of the module using your other hand. Gently push the module in along the slot guide rail.
4. Release the extraction handle to fix the power supply module in place. Caution: S6500-24GP4XF/S6500-48GP6XF/S6500-24M4Y/S6500-24MPP4Y/S6500-48M6Y/S6500-48MPP6Y/ S7500-26XF6Y uses hot-swappable fan modules with a maximum speed of 9,000 RPM. S7500-48XF4C/ S7500-24Y4C/S7500-48Y8C/S7500-32C uses hot-swappable fan modules with a maximum speed of 18,000 RPM. Please do not interchange or mix fan modules between models. Sharp edges on the fan module may cause injury, so please operate with caution. Make sure the damaged fan module is in place before you are going to replace it. DO NOT unplug the damaged fan module until the replacement operation. Do not use too much force in the replacement. If resistance is encountered or positions of the fan module appear larger during installation, you must first remove the module and then reinstall the module. If the Retainer Clips cannot spring up naturally and the power module is blocked, it may be due to the fan module is not installed properly. Please check carefully.
Installazzjoni 21
Omada Ċampus Stackable L3 Managed Switch
Kapitolu 3 Konnessjoni
3.1 Port Ethernet
Qabbad port Ethernet tas-swiċċ mal-kompjuter permezz ta 'kejbil RJ45 kif turi l-figura li ġejja.
Figura 3-1
Konnessjoni tal-Port RJ45
Port RJ45
Kejbil RJ45
3.2 10G SFP+/25G SFP28/100G QSFP28 Slot
The following figure demonstrates the connection of 10G SFP+/25G SFP28/100G QSFP28 slot to an optical module
Figura 3-2
Inserting the Fiber Module
Slot Fiber Module
3.3 Port tal-Console
CLI (Command Line Interface) jippermettilek timmaniġġja s-swiċċ, u b'hekk tista' tgħabbi s-CLI wara li tqabbad il-PCs jew it-Terminals mal-port tal-console fuq is-swiċċ permezz ta' kejbil (kejbil tal-console RJ45 huwa pprovdut, filwaqt li l-kejbil tat-Tip C mhux provdut)
Qabbad il-port tal-console RJ45 tal-apparat mal-kompjuter tiegħek permezz tal-kejbil tal-console kif turi l-figura li ġejja.
22 Konnessjoni
Figura 3-3
Konnessjoni tal-Console (RJ45) Port
Omada Ċampus Stackable L3 Managed Switch
Qabbad il-port tal-console tat-Tip-Ċ tal-apparat mal-kompjuter tiegħek permezz tal-kejbil tat-Tip-Ċ (mhux ipprovdut) kif turi l-figura li ġejja.
Figura 3-4
Konnessjoni tal-Console (USB) Port
Note: RJ45 console port and Type-C console port cannot be used concurrently. Type-C Console port takes
priority over the RJ45 console port. The Type-C console port is hot-pluggable while the RJ45 console port is not. Keep the device power
off when plugging the console cable into the RJ45 console port. Do not connect the console port with other ports by RJ45 cable.
3.4 Ivverifika l-Installazzjoni
Wara li tlesti l-installazzjoni, ivverifika l-oġġetti li ġejjin: Għandu jkun hemm 5 sa 10 ċm ta 'spazju madwar l-apparat għall-ventilazzjoni u kun żgur li l-fluss tal-arja
hija adegwata. Il-voltage tal-provvista tal-enerġija tissodisfa r-rekwiżit tal-input voltage tal-apparat. Is-sokit tal-enerġija, l-apparat u l-ixtilliera huma msejsa tajjeb. L-apparat huwa konness b'mod korrett ma' apparati oħra tan-netwerk.
Konnessjoni 23
Omada Ċampus Stackable L3 Managed Switch
3.5 Mixgħul
Ipplaggja l-konnettur femminili tal-korda tal-enerġija pprovduta fis-sokit tal-enerġija tal-apparat u plagg il-konnettur pożittiv fi żbokk tal-enerġija kif turi l-figura li ġejja. Kun żgur li l-voltage tal-provvista tal-enerġija tissodisfa r-rekwiżit tal-input voltage (100-240 V~ 50/60 Hz).
Figura 3-5
Konnessjoni mal-Provvista tal-Enerġija
Note: The figure is to illustrate the application and principle. The provided plug and module in your region
may differ from the figures above. Generally PWR1 takes priority over PWR2.
3.6 Inizjalizzazzjoni
Wara li l-apparat ikun mixgħul, jibda t-Test Awtonomiku li Jixgħel. Serje ta 'testijiet jaħdmu awtomatikament biex jiżguraw li l-apparat jiffunzjona sewwa. Matul dan iż-żmien, l-indikaturi LED tiegħu se jirrispondu fl-ordni li ġejja:
1. L-indikatur LED PWR jixgħel il-ħin kollu. L-LED SYS u l-indikaturi LED tal-portijiet kollha jżommu off.
2. Wara madwar minuta, l-LED SYS u l-indikaturi LED tal-portijiet kollha se jteptpu momentarjament u mbagħad jitfi.
3. Diversi sekondi wara, l-indikatur LED SYS se jteptep, li jirrappreżenta inizjalizzazzjoni b'suċċess.
3.7 Topoloġija tal-Munzell
With stackable design, the switches can be stacked into one stack topology for higher reliability, larger bandwidth, and simpler networking. To build the stack topology, you need to prepare 2-12 switches and enough 10G SFP+/25G SFP28/100G QSFP28 modules/cables. For more details, see the table below:
Aqleb
Mudell(i) kompatibbli
Kwantità
S6500-24G4XF S6500-24G4XF, S6500-48G6XF, S6500-24GP4XF, S6500-48GP6XF S6500-48G6XF S6500-24G4XF, S6500-48G6XF, S6500-24GP4XF, S6500-48GP6XF S6500-24GP4XF S6500-24G4XF, S6500-48G6XF, S6500-24GP4XF, S6500-48GP6XF S6500-48GP6XF S6500-24G4XF, S6500-48G6XF, S6500-24GP4XF, S6500-48GP6XF S6500-24M4Y S6500-24M4Y, S6500-24MPP4Y, S6500-48M6Y, S6500-48MPP6Y S6500-24MPP4Y S6500-24M4Y, S6500-24MPP4Y, S6500-48M6Y, S6500-48MPP6Y
2-12 (max 12 in standalone mode, max 4 in controller mode) 2-12 (max 12 in standalone mode, max 4 in controller mode) 2-12 (max 12 in standalone mode, max 4 in controller mode) 2-12 (max 12 in standalone mode, max 4 in controller mode) 2-12 (max 12 in standalone mode, max 4 in controller mode) 2-12 (max 12 in standalone mode, max 4 in controller mode)
24 Konnessjoni
Omada Ċampus Stackable L3 Managed Switch
S6500-48M6Y S6500-24M4Y, S6500-24MPP4Y, S6500-48M6Y, S6500-48MPP6Y
S6500-48MPP6Y S6500-24M4Y, S6500-24MPP4Y, S6500-48M6Y, S6500-48MPP6Y
S7500-26XF6Y S7500-26XF6Y
S7500-48XF4C S7500-48XF4C
S7500-24Y4C S7500-24Y4C
S7500-48Y8C S7500-48Y8C
S7500-32C
S7500-32C
2-12 (max 12 in standalone mode, max 4 in controller mode) 2-12 (max 12 in standalone mode, max 4 in controller mode) 2-12 (max 12 in standalone mode, max 4 in controller mode) 2-12 (max 12 in standalone mode, max 4 in controller mode) 2-12 (max 12 in standalone mode, max 4 in controller mode) 2-12 (max 12 in standalone mode, max 4 in controller mode) 2-12 (max 12 in standalone mode, max 4 in controller mode)
Hemm tliet strutturi tat-topoloġija tal-munzell għal xenarji differenti, jekk jogħġbok ibni t-topoloġija xierqa skont il-bżonnijiet tiegħek:
1. Topoloġija tal-katina: Topoloġija tal-katina hija relattivament sempliċi u ma teħtieġx konnessjoni tal-kejbil bejn l-ewwel u l-aħħar unità. Huwa adattat għall-istivar fuq distanzi twal, iżda l-affidabbiltà tiegħu hija relattivament baxxa.
Figura 3-6
Topoloġija tal-Katina
Stacking Port Grupp 2
Stacking Port Grupp 1
...
2. Topoloġija taċ-ċirku: Topoloġija taċ-ċirku għandha affidabbiltà ogħla meta mqabbla mat-topoloġija tal-katina. Meta waħda mill-ktajjen fit-topoloġija taċ-ċirku tkun skonnettjata, it-topoloġija taċ-ċirku ssir topoloġija tal-katina, iżda s-sistema kollha tal-munzell xorta tista 'taħdem b'mod normali. It-topoloġija taċ-ċirku teħtieġ konnessjoni tal-kejbil bejn l-ewwel u l-aħħar unità, għalhekk mhix adattata għal stivar fuq distanzi twal.
Figura 3-7
Topoloġija Ċirku
Stacking Port Grupp 2
Stacking Port Grupp 1
...
Konnessjoni 25
Omada Ċampus Stackable L3 Managed Switch
3. Topoloġija Star: Topoloġija Star tgħaqqad is-swiċċijiet ma 'swiċċ prinċipali ċentrali, għalhekk, tista' żżid b'mod sinifikanti r-rata ta 'trażmissjoni tad-dejta bejn swiċċijiet tal-membri filwaqt li tipprovdi ġestjoni unifikata.
Figura 3-8
Topoloġija tal-Istilla
Stacking Port Grupp 2
Stacking Port Grupp 3
Stacking Port Grupp 1
...
Note: The stacking port is not allowed to connect to non-stacking port, as it may affect the operation of the
device. Stacking ports with the same group ID are not allowed to connect to stacking ports with different
group IDs, neither to different devices. A stacking port group is a logical port dedicated to stacking and needs to be bound to a stacking port.
A stacking port group can be bound to one or more stacking ports to improve bandwidth and reliability.
26 Konnessjoni
Omada Ċampus Stackable L3 Managed Switch
Kapitolu 4 Konfigurazzjoni
4.1 Konfigurazzjoni Overview
Is-swiċċ jappoġġja żewġ għażliet ta 'konfigurazzjoni:
Modalità Standalone: Ikkonfigura u mmaniġġja l-iswiċċ waħdu. Modalità tal-Kontrollur: Ikkonfigura u mmaniġġja t-tagħmir tan-netwerk b'mod ċentrali. Huwa rakkomandat fil-
netwerk fuq skala kbira, li jikkonsisti minn apparati tal-massa bħal punti ta 'aċċess, swiċċijiet, u gateways.
Nota: Meta l-iswiċċ jinbidel minn Modalità Standalone għal Modalità Kontrollur, il-konfigurazzjonijiet tal-iswiċċ jintilfu. Għad-dettalji, irreferi għad-dokumenti relatati fuq iċ-ċentru tat-tniżżil tal-uffiċjal tagħna websit: https://support.omadanetworks.com/product/.
4.2 Modalità Standalone
Fil-Modalità Standalone, uża kompjuter biex tikkonfigura u timmaniġġja l-iswiċċ billi tuża GUI (Graphical User Interface) jew CLI (interface tal-linja tal-kmand).
Figura 4-1
Topoloġija għall-Modalità Standalone
Aqleb
PC
Bl-użu tal-GUI
1. Biex taċċessa l-paġna ta 'ġestjoni tas-swiċċ, kun żgur li l-iswiċċ u l-kompjuter huma fl-istess subnet. Iftaħ browser u ittajpja l-indirizz IP tas-swiċċ fil-qasam tal-indirizz, imbagħad agħfas il-buttuna Enter.
Jekk is-swiċċ jikseb l-indirizz IP mis-server DHCP (tipikament gateway), sib l-indirizz IP tas-swiċċ fuq is-server DHCP.
Jekk le, uża l-indirizz IP default 192.168.0.1 biex tniedi l-paġna ta 'ġestjoni tas-swiċċ.
2. L-ewwel darba li tidħol, issettja l-isem tal-utent u l-password biex tipproteġi aħjar in-netwerk u l-apparati tiegħek. Wara dan, is-sistema awtomatikament tidderieġik lura lejn l-interfaċċja tal-login biex tawtentika bil-kredenzjali li għadek kif ħloqt.
3. Wara login b'suċċess, tidher il-paġna ewlenija. Tista 'tikklikkja l-menus fuq in-naħa ta' fuq u fuq in-naħa tax-xellug biex tikkonfigura l-funzjonijiet korrispondenti.
Għall-konfigurazzjonijiet dettaljati, irreferi għall-Gwida għall-Utent u l-Gwida CLI. Il-gwidi jinsabu fuq iċ-ċentru tat-tniżżil tal-uffiċjal tagħna websit: https://support.omadanetworks.com/product/.
L-użu tas-CLI Stabbilixxi konnessjoni Telnet jew SSH biex taċċessa l-iswiċċ permezz ta' CLI.
Konfigurazzjoni 27
Omada Ċampus Stackable L3 Managed Switch
Uża l-port tal-console biex taċċessa l-iswiċċ. Meta tuża l-port tal-console, ibda l-programm ta 'emulazzjoni tat-terminal (bħal Hyper Terminal) fuq il-PC u kkonfigura l-programm ta' emulazzjoni tat-terminal kif ġej:
Rata Baud 38400 bps
Bits tad-Data 8
Parità Xejn
Stop Bits 1
Kontroll tal-Fluss Xejn
Għall-konfigurazzjonijiet dettaljati, irreferi għall-Gwida għall-Utent u l-Gwida CLI. Il-gwidi jinsabu fuq iċ-ċentru tat-tniżżil tal-uffiċjal tagħna websit: https://support.omadanetworks.com/product/.
Note: You may need to change the password the first time you log in, which will better protect your network and devices.
4.3 Modalità tal-Kontrollur
Controller Mode applies to the large scale network with mass devices. All devices can be centrally configured and monitored via Omada Pro Hardware Controller (C5300), Omada Pro Software Controller, or Omada Pro Cloud-Based Controller.
Note: Before the following configurations, make sure the switch can access the internet. When using Omada Pro Hardware/Software/Cloud-based Controller, make sure the switch and the controller are in the same subnet. Typically, the switch obtains IP address from the DHCP server. You can check the switch’s IP address on the DHCP server.
Via Omada Pro Hardware Controller (C5300)
Omada Pro Hardware Controller (C5300) is a good alternative if you have no spare PC to keep running Omada Pro Software Controller in the network. It needs to be purchased additionally. Follow the steps below to configure the Omada Pro Hardware Controller (C5300).
Figura 4-2
Manage the network via Omada Pro Hardware Controller (C5300)
Swiċċ tal-Gateway
Omada Pro Hardware Controller (C5300) EAP
28 Konfigurazzjoni
EAP
EAP
Klijenti
Omada Ċampus Stackable L3 Managed Switch
Note: Before you start, be sure to power up and connect your devices according to the topology figure. A DHCP server (typically a gateway with DHCP function enabled) is required to assign IP addresses to
the EAPs and clients in your local network. Omada Pro Controller must have network access to some Omada campus devices (the gateway,
switch, or APs) in order to find, adopt, and manage them.
1. Sib l-indirizz IP tal-gateway. Iftaħ il-linja tal-kmand fuq il-PC tiegħek u daħħal ipconfig. Fil-lista tar-riżultati, sib id-Default Gateway, li huwa wkoll l-indirizz IP tal-gateway.
2. Tnedija a web il-browser u daħħal l-indirizz IP tal-gateway. Idħol fil-gateway web paġna. Imbagħad mur Netwerk > LAN > Lista tal-Klijenti DHCP biex issib l-indirizz IP tal-kontrollur tiegħek skont l-indirizz MAC tiegħu.
3. Daħħal l-indirizz IP tal-kontrollur tiegħek fil-bar tal-indirizz biex tiftaħ tiegħu web paġna.
4. Fuq il-Kontrollur Omada Pro web paġna, segwi l-wizard biex tlesti s-setup malajr.
5. Wara s-setup ta 'malajr, tidher il-paġna tal-login. Daħħal l-isem tal-utent u l-password li ħloqt u kklikkja Idħol. Imbagħad tista' tkompli tikkonfigura l-kontrollur.
6. Jekk trid timmaniġġja l-apparati mill-bogħod, segwi l-passi li jmiss:
a. Kun żgur li Cloud Access huwa attivat fuq il-kontrollur tiegħek. B'mod awtomatiku, Cloud Access huwa attivat. Kun żgur li l-Cloud LED qed iteptep bil-mod.
b. Tnedija a web browser u daħħal https://omada.tplinkcloud.com fil-bar tal-indirizz. Daħħal l-ID TP-Link u l-password tiegħek biex tidħol. Ikklikkja + Żid Kontrollur u agħżel Kontrollur tal-Hardware biex iżżid il-kontrollur tiegħek. Imbagħad tista 'tikkonfigura aktar il-kontrollur.
For more details, refer to the Installation Guide of C5300.
Permezz tal-Kontrollur tas-Software Omada Pro
Download the Omada Pro Software Controller on a PC with Windows OS or Linux OS. Then run the file and follow the wizard to install the Omada Pro Software Controller. Follow the steps below to configure the Controller.
Figura 4-3
Immaniġġja n-netwerk permezz tal-Kontrollur tas-Software Omada Pro
Bieb
Aqleb
Kontrollur
Kontrollur tas-Softwer Omada Pro AP
AP
AP
jaħdem fuq il-PC Ospitanti
Klijenti
Konfigurazzjoni 29
Omada Ċampus Stackable L3 Managed Switch
1. Launch the Omada Pro Software Controller on your PC. After the initiation process, the controller automatically opens its web paġna. Jekk le, ikklikkja Tnedija Browser biex Immaniġġja n-Netwerk.
2. Fuq il-Kontrollur Omada Pro web paġna, segwi l-wizard biex tlesti s-setup malajr.
3. Wara s-setup ta 'malajr, tidher il-paġna tal-login. Daħħal l-isem tal-utent u l-password li ħloqt u kklikkja Idħol. Imbagħad tista' tkompli tikkonfigura l-kontrollur.
4. Jekk trid timmaniġġja l-apparati mill-bogħod, segwi l-passi li jmiss:
a. Make sure that Cloud Access is enabled on your controller and your controller has been bound with your TP-Link ID. On the Omada Pro Controller’s web paġna, mur Settings > Cloud Access biex tippermetti Cloud Access u torbot l-ID TP-Link tiegħek. Jekk waqqaftha fis-setup ta' malajr, aqbeż dan il-pass.
b. Tnedija a web browser u daħħal https://omada.tplinkcloud.com fil-bar tal-indirizz. Daħħal l-ID TP-Link u l-password tiegħek biex tidħol. Se tidher lista ta' kontrolluri li ġew marbuta bl-ID TP-Link tiegħek. Imbagħad tista 'tikklikkja Tnedija biex tikkonfigura aktar il-kontrollur.
Note: To manage your devices, Omada Pro Software Controller needs to keep running on your computer.
Via Omada Pro Kontrollur Ibbażat fuq Cloud
Omada Pro Cloud-Based Controller huwa alternattiva tajba mingħajr il-ħtieġa li tinstalla l-kontrollur tas-softwer fuq PC.
Il-liċenzji jridu jinxtraw ukoll.
Figura 4-4
Immaniġġja n-netwerk permezz ta 'Omada Pro Cloud-Based Controller
Sħab Omada
Bieb
Aqleb
AP
AP
AP
AP
Klijenti
1. Contact the sales staff to grant the Omada Pro Cloud-Based Controller permission. 2. Launch a web il-browser u daħħal https://omada.tplinkcloud.com fil-bar tal-indirizzi. Idħol b'
your TP-Link ID.
30 Konfigurazzjoni
Omada Ċampus Stackable L3 Managed Switch 3. Click + Add Controller and choose Cloud-Based Controller to add an Omada Pro Controller. Then
Tista' tniedi l-kontrollur biex tadotta u timmaniġġja apparati. * App Omada Bl-app Omada, tista' wkoll timmaniġġja l-kontrollur tiegħek f'sit lokali jew sit remot permezz tat-tagħmir mobbli tiegħek. Għal konfigurazzjonijiet dettaljati, irreferi għall-Gwida għall-Utent tal-kontrollur. Il-gwida tista' tinstab fiċ-ċentru tat-tniżżil tas-sit uffiċjali tagħna websit: https://support.omadanetworks.com/product/.
Konfigurazzjoni 31
Omada Ċampus Stackable L3 Managed Switch
Appendiċi A Issolvi l-Problemi
Q1. X'nista 'nagħmel jekk insejt il-username u l-password tas-swiċċ?
1. Qabbad il-port tal-console tal-PC mal-port tal-console tas-swiċċ u tiftaħ programm ta 'emulazzjoni tat-terminal.
2. Itfi u erġa ibda l-iswiċċ. Wettaq l-azzjoni indikata mill-programm ta 'emulazzjoni tat-terminal biex tilħaq il-menu bootUtil. L-azzjoni tvarja minn prodott għal prodott. Azzjonijiet possibbli huma elenkati hawn taħt: · Agħfas kwalunkwe ċavetta biex twaqqaf l-autoboot. · Agħfas CTRL-B biex tilħaq il-menu bootUtil.
3. Jintwera l-menù bootUtil. Daħħal in-numru 6 biex tagħżel l-għażla “Password recovery” u daħħal Y biex tħassar l-utenti u l-passwords kollha. Imbagħad tista’ tirrisettja l-username u l-password.
M2. Għaliex l-LED tal-PWR jaħdem b'mod anormali? L-LED tal-PWR/Power għandu jkun mixgħul meta s-sistema tal-enerġija taħdem normalment. Jekk l-LED tal-PWR/Power jaħdem b'mod anormali, ħu l-passi li ġejjin:
1. Kun żgur li l-kejbil tal-enerġija huwa konness sew, u li l-kuntatt tal-enerġija huwa normali. 2. Kun żgur li l-volumtage tal-provvista tal-enerġija tissodisfa r-rekwiżit tal-input voltage tal-
swiċċ.
Q3. X'għandi nagħmel jekk ma nistax jaċċessa l- web paġna tal-ġestjoni? Ipprova dan li ġej:
1. Iċċekkja kull LED tal-port fuq is-swiċċ u kun żgur li l-kejbil Ethernet huwa konness kif suppost. 2. Ipprova port ieħor fuq is-swiċċ u kun żgur li l-kejbil Ethernet huwa adattat u jaħdem b'mod normali. 3. Itfi s-swiċċ u, wara ftit, erġa 'xgħel. 4. Kun żgur li l-indirizz IP tal-PC tiegħek huwa ssettjat fis-subnet tas-swiċċ. 5. Jekk xorta ma tistax taċċessa l-paġna tal-konfigurazzjoni, reset l-iswiċċ għall-defaults tal-fabbrika tiegħu. Imbagħad
l-indirizz IP tal-PC tiegħek għandu jkun issettjat bħala 192.168.0.x (“x” huwa kwalunkwe numru minn 2 sa 254) u l-maskra tas-subnet bħala 255.255.255.0.
M4. Għaliex il-programm tal-emulazzjoni tat-terminal mhux qed jintwera b'mod korrett? Ipprova dan li ġej:
1. Kun żgur li l-provvista tal-enerġija hija normali u l-kejbil tal-console huwa konness sew. 2. Iċċekkja jekk il-kejbil tal-console huwiex it-tip it-tajjeb. 3. Kun żgur li l-parametri tal-programm ta 'emulazzjoni tat-terminal huma korretti: kkonfigurat Bits kull sekonda
bħala 38400, Data bits bħala 8, Parità bħala Xejn, Stop bits bħala 1, u kontroll tal-fluss bħala Xejn.
32 Appendiċi A Issolvi l-Problemi
Omada Ċampus Stackable L3 Managed Switch
Appendiċi B Speċifikazzjonijiet
Specifications for S6500 Series Switches
Oġġett
Kontenut
IEEE 802.3, IEEE 802.3i, IEEE 802.3u, IEEE 802.3ab, IEEE 802.3z, IEEE 802.3ae, IEEE 802.3x
Standards
IEEE 802.3af/at (For S6500-24GP4XF, S6500-48GP6XF) IEEE 802.3af/at/bt (For S6500-24MPP4Y, S6500-48MPP6Y)
IEEE 802.3bz, IEEE 802.3by, IEEE 802.3cc (For S6500-24M4Y, S6500-24MPP4Y, S6500-48M6Y, S6500-48MPP6Y)
10BASE-T: 2-pair UTP/STP of Cat. 3,4,5 (maximum 100 m) 100BASE-TX: 2-pair UTP/STP of Cat. 5 or above (maximum 100 m) 1000BASE-T: 4-pair UTP/STP of Cat. 5e or above (maximum 100 m) 2.5GBASE-T: 4-pair UTP/STP of Cat. 5e or above (maximum 100 m) Transmission Medium 1000BASE-SX/LX/LX10/BX10: MMF, SMF 10GBASE-SR/LR: MMF, SMF 10G SFP+ Direct Attach Cable (SM5220-1M, SM5220-3M) 25GBASE-SR/LR: MMF, SMF (SM6110-SR, SM6110-LR) 25G SFP28 Direct Attach Cable (SM6220-1M)
S6500-24G4XF/S6500-24M4Y: PWR1, PWR2, SYS, FAN, MGMT, MST, SPEED, STK, Port 1-24, Port 25-28 S6500-24GP4XF/S6500-24MPP4Y: PWR1, PWR2, SYS, FAN, PoE Max, MGMT, MST, SPEED, STK, PoE, Port 1-24, Port 25-28 LED S6500-48G6XF/S6500-48M6Y: PWR1, PWR2, SYS, FAN, MGMT, MST, SPEED, STK, Port 1-48, Port 49-54 S6500-48GP6XF/S6500-48MPP6Y: PWR1, PWR2, SYS, FAN, PoE Max, MGMT, MST, SPEED, STK, PoE, Port 1-48, Port 49-54
Appendiċi B Speċifikazzjonijiet 33
Omada Ċampus Stackable L3 Managed Switch
Baġit PoE
For S6500-24GP4XF: 402W (with 1*PSM500-AC, by default) 720W (with 1*PSM900-AC) 720W (with 2*PSM500-AC) 720W (with 1*PSM500-AC and 1*PSM900-AC) 720W (with 2*PSM900-AC) For S6500-48GP6XF: 764W (with 1*PSM900-AC, by default) 384W (with 1*PSM500-AC) 812W (with 2*PSM500-AC) 1176W (with 1*PSM500-AC and 1*PSM900-AC) 1440W (with 2*PSM900-AC) For S6500-24MPP4Y: 751W (with 1*PSM900-AC, by default) 378W (with 1*PSM500-AC) 802W (with 2*PSM500-AC) 1168W (with 1*PSM500-AC and 1*PSM900-AC) 1534W (with 2*PSM900-AC) For S6500-48MPP6Y: 701W (with 1*PSM900-AC, by default) 328W (with 1*PSM500-AC) 752W (with 2*PSM500-AC) 1118W (with 1*PSM500-AC and 1*PSM900-AC) 1484W (with 2*PSM900-AC)
Temperatura u Altitudni Operattiva
For S6500-24G4XF/S6500-48G6XF/S6500-24M4Y/S6500-48M6Y: -5 °C to 50 °C (23 °F to 122 °F) @ 300 meters -5 °C to 45 °C (23 °F to 113 °F) @ 2,000 meters -5 °C to 40 °C (23 °F to 104 °F) @ 3,000 meters For S6500-24GP4XF/S6500-48GP6XF/S6500-24MPP4Y/S6500-48MPP6Y: -5 °C to 45 °C (23 °F to 113 °F) @ 2,000 meters -5 °C to 40 °C (23 °F to 104 °F) @ 3,000 meters
Temperatura tal-Ħażna -40 °C sa 70 °C (-40 °F sa 158 °F)
Umdità Operattiva 10% sa 90% RH Mhux kondensazzjoni
Umdità tal-Ħażna
5% sa 90% RH Mhux ta 'kondensazzjoni
34 Appendiċi B Speċifikazzjonijiet
Omada Ċampus Stackable L3 Managed Switch
Specifications for S7500 Series Switches
Oġġett
Kontenut
Standards
IEEE 802.3, IEEE 802.3x IEEE 802.3z, IEEE 802.3ae (For S7500-26XF6Y, S7500-48XF4C, S7500-24Y4C, S7500-48Y8C IEEE 802.3by, IEEE 802.3cc (For S7500-26XF6Y, S7500-24Y4C, S7500-48Y8C) IEEE 802.3 ba, IEEE 802.3bm (For S7500-48XF4C , S7500-24Y4C, S7500-48Y8C, S7500-32C)
1000BASE-SX/LX/LX10/BX10: MMF, SMF 10GBASE-SR/LR: MMF, SMF 10G SFP+ Direct Attach Cable (SM5220-1M, SM5220-3M) 25GBASE-SR/LR: MMF, SMF (SM6110-SR, SM6110-LR) 25G SFP28 Direct Attach Cable (SM6220-1M) 40GBASE-SR4/LR4: MMF, SMF (For S7500-48XF4C, S7500-24Y4C, Transmission Medium S7500-48Y8C, S7500-32C) 40G QSFP+ Direct Attach Cable (For S7500-48XF4C, S7500-24Y4C, S7500-48Y8C, S7500-32C) 100GBASE-SR4/LR4: MMF, SMF (SM9110-SR4 for S7500-48XF4C, S7500-24Y4C, S7500-48Y8C, S7500-32C) 100G QSFP28 Direct Attach Cable (SM9220-1M for S7500-48XF4C, S7500-24Y4C, S7500-48Y8C, S7500-32C)
LED
Temperatura u Altitudni Operattiva
S7500-26XF6Y: PWR1, PWR2, SYS, FAN, MGMT, MST, SPD, STK, SFP+, SFP28 S7500-48XF4C: PWR1, PWR2, SYS, FAN, MGMT, MST, SPEED, STK, SFP+, QSFP28 S7500-24Y4C: PWR1, PWR2, SYS, FAN, MGMT, MST, SPD, STK, SFP28, QSFP28 S7500-48Y8C: PWR1, PWR2, SYS, FAN, MGMT, MST, SPEED, STK, SFP28, QSFP28 S7500-32C: PWR1, PWR2, SYS, MGMT, FAN, MST, SPEED, STK, QSFP28 -5 °C to 45 °C (23 °F to 113 °F) @ 300 meters -5 °C to 40 °C (23 °F to 104 °F) @ 2,000 meters -5 °C to 35 °C (23 °F to 95 °F) @ 3,000 meters
Temperatura tal-Ħażna -40 °C sa 70 °C (-40 °F sa 158 °F)
Umdità Operattiva 10% sa 90% RH Mhux kondensazzjoni
Umdità tal-Ħażna
5% sa 90% RH Mhux ta 'kondensazzjoni
For S7500-26XF6Y, S7500-48XF4C, and S7500-24Y4C, the maximum operating temperature supported can reach 50 °C (122 °F) @ 300 meters, 45 °C (113 °F) @ 2,000 meters, and 40 °C (104 °F) @ 3,000 meters.
L-altitudni appoġġjata hija mil-livell tal-baħar sa 5000 m. Ta' min jinnota li meta l-altitudni tkun 'il fuq minn 2000 m, għal kull żieda ta' 220 metru fl-altitudni, it-temperatura massima operattiva tinżel b'1°C (1.8°F).
Appendiċi B Speċifikazzjonijiet 35
Omada Ċampus Stackable L3 Managed Switch
Speċifikazzjonijiet għall-Moduli tal-Provvista tal-Enerġija
PSM500-AC
(For S6500-24GP4XF/ S6500-48GP6XF/ S6500-24MPP4Y/ S6500-48MPP6Y)
PSM900-AC
(For S6500-24GP4XF/ S6500-48GP6XF/ S6500-24MPP4Y/ S6500-48MPP6Y)
PSM550-AC
(For S6500-24M4Y/ S6500-48M6Y/ S7500-26XF6Y/ S7500-48XF4C/ S7500-24Y4C/ S7500-48Y8C/ S7500-32C)
Input tal-Enerġija
100 V240 V~ 50/60 Hz 8A
100-120V (included)~ 50/60Hz 12A (for locations using low voltage, see specifications for specific countries/ regions)
120 (not included)240V~ 50/60Hz 10A (for other locations)
100 V240 V~ 50/60 Hz 7A
Ħruġ Voltage
Primary: 53.5 VDC Standby: 12 VDC
Primary: 53.5 VDC Standby: 12 VDC
Primary: 12 VDC Standby: 12 VDC
Kurrent tal-Ħruġ
9.35 A (Massimu)
16.5 A (Massimu)
45 A (Massimu)
Qawwa tal-Ħruġ
500 W (Massimu)
900 W (Massimu)
550 W (Massimu)
Altitudni Operattiva
For PSM500-AC/PSM900-AC: Sea level to 3000 m For PSM550-AC: Sea level to 5000 m
36 Appendiċi B Speċifikazzjonijiet
Twissija tal-Marka CE
Dan huwa prodott tal-klassi A. F'ambjent domestiku, dan il-prodott jista 'jikkawża interferenza tar-radju, f'liema każ l-utent jista' jkun meħtieġ li jieħu miżuri adegwati.
Dikjarazzjoni ta' Konformità tal-UE
TP-Link b'dan tiddikjara li s-swiċċ huwa konformi mar-rekwiżiti essenzjali u dispożizzjonijiet rilevanti oħra tad-direttivi 2014/30/UE, 2014/35/UE, 2011/65/UE u (UE) 2015/863. Id-Dikjarazzjoni ta' Konformità tal-UE oriġinali tista' tinstab fuq https://www.tp-link.com/en/support/ce/
Dikjarazzjoni ta' Konformità tar-Renju Unit
TP-Link b'dan tiddikjara li s-swiċċ huwa konformi mar-rekwiżiti essenzjali u dispożizzjonijiet rilevanti oħra tar-Regolamenti dwar il-Kompatibilità Elettromanjetika tal-2016 u r-Regolamenti dwar it-Tagħmir Elettriku (Sigurtà) tal-2016. Id-Dikjarazzjoni ta' Konformità oriġinali tar-Renju Unit tista' tinstab fuq https://www.tp-link.com/support/ukca/
, .
ATTENZJONI:
Arblu doppju, fużjoni newtrali. Skonnettja l-mejn qabel isservi.
Informazzjoni dwar is-Sigurtà
· Żomm l-apparat 'il bogħod mill-ilma, nar, umdità jew ambjenti sħan. · Tippruvax tiżżarma, isewwi, jew timmodifika l-apparat. Jekk għandek bżonn servizz, jekk jogħġbok ikkuntattjana. · Poġġi l-apparat bil-wiċċ tal-qiegħ tiegħu 'l isfel. · Il-plagg fuq il-korda tal-provvista tal-enerġija jintuża bħala l-apparat ta 'skonnettjar, is-socket-outlet għandu jkun
faċilment aċċessibbli. · Ipplaggja l-prodott fis-sokits tal-ħajt b'konnessjoni tal-ert permezz tal-korda tal-provvista tal-enerġija
or plug. · The socket-outlet shall be installed near the equipment and shall be easily accessible. · The PoE ports shall not be used to charge lithium batteries or devices supplied by lithium
batteriji.
· Operating temperature: For S6500-24G4XF/S6500-48G6XF/S6500-24M4Y/S6500-48M6Y/S7500-26XF6Y/ S7500-48XF4C/S7500-24Y4C: -5 °C to 50 °C (23 °F to 122 °F) @ 300 meters -5 °C to 45 °C (23 °F to 113 °F) @ 2,000 meters -5 °C to 40 °C (23 °F to 104 °F) @ 3,000 meters For S6500-24GP4XF/S6500-48GP6XF/S6500-24MPP4Y/S6500-48MPP6Y: -5 °C to 45 °C (23 °F to 113 °F) @ 2,000 meters -5 °C to 40 °C (23 °F to 104 °F) @ 3,000 meters S7500-48Y8C/S7500-32C: -5 °C to 45 °C (23 °F to 113 °F) @ 300 meters -5 °C to 40 °C (23 °F to 104 °F) @ 2,000 meters -5 °C to 35 °C (23 °F to 95 °F) @ 3,000 meters
· : S6500-24G4XF/S6500-48G6XF/S6500-24M4Y/S6500-48M6Y/S7500-26XF6Y/S7500-48XF4C/ S7500-24Y4C -5°C 50°C23°F 122°F@ 300 -5°C 45°C23°F 113°F@ 2,000 -5°C 40°C23°F 104°F@ 3,000 S6500-24GP4XF/S6500-48GP6XF/S6500-24MPP4Y/S6500-48MPP6Y -5°C 45°C23°F 113°F@ 2,000 -5°C 40°C23°F 104°F@ 3,000 S7500-48Y8C/S7500-32C -5°C 45°C23°F 113°F@ 300 -5°C 40°C23°F 104°F@ 2,000 -5°C 35°C23°F 95°F@ 3,000
This equipment is not suitable for use in locations
where children are likely to be present.
Jekk jogħġbok aqra u segwi l-informazzjoni ta 'hawn fuq dwar is-sigurtà meta tħaddem l-apparat. Ma nistgħux niggarantixxu li ma jseħħu l-ebda inċident jew ħsara minħabba użu mhux xieraq tal-apparat. Jekk jogħġbok uża dan il-prodott b'attenzjoni u topera għar-riskju tiegħek.
Għal appoġġ tekniku, gwidi għall-utent u informazzjoni oħra, jekk jogħġbok żur https://support.omadanetworks.com/, jew sempliċement skennja l-kodiċi QR.
© 2026 TP-Link 7100002759 REV2.0.1