1. Prodott Aktarview
The GEYA GRD9L-R Automatic Reclosing Device is an electromagnetic leakage circuit breaker (RCCB) designed to enhance electrical system reliability and reduce manual intervention. It automatically recloses the circuit when a leakage fault causes the RCD to trip unexpectedly, minimizing downtime and maintenance costs.
This device is suitable for various applications, including electrical network terminal lines, meter boxes, new energy circuit management, solar PV control boxes, smart electricity systems, smart homes, and charging stations for new energy vehicles.
Karatteristiċi ewlenin:
- Automatic reclosing function after RCD trip, eliminating the need for manual reset.
- Integrated 3 reclosing attempts. An auxiliary contact can send an alarm if continuous tripping occurs within 15 minutes.
- Manual/Automatic selector switch for operational flexibility.
- Features double mechanical/electronic locking for enhanced safety.
- Compatible with auxiliary contacts, alarm contacts, shunt releases, and undervoltage releases.
- Reclosing attempt counter resets if no trip occurs or after a manual reset within 15 minutes of successful reclosure.

Figura 1: Quddiem view of the GEYA GRD9L-R Automatic Reclosing Device.
2. Informazzjoni dwar is-Sigurtà
TWISSIJA: Installation and maintenance of this device must be performed by a qualified electrician in accordance with all local and national electrical codes and regulations. Failure to do so may result in electric shock, fire, or other serious injury.
- Always disconnect power before installing, servicing, or removing the device.
- Aċċerta ruħek li s-sistema elettrika hija ertjata sew.
- Tħaddimx l-apparat jekk jidher li hu bil-ħsara.
- Verify correct wiring connections to prevent malfunction or damage.
- L-apparat huwa ddisinjat għal volum speċifikutage u l-klassifikazzjonijiet tal-kurrent. Teċċedix dawn il-limiti.
3. Product Components and Diagrams
3.1 Deskrizzjoni tal-Funzjoni

Figure 2: Diagram illustrating the automatic reclosing logic and function description. The device attempts to reclose the circuit up to three times with specific time intervals. If the interval between two successful closings exceeds 15 minutes, the program clears the accumulated closing times.
3.2 Functions Diagram (Auto Mode Logic)

Figure 3: Detailed flow chart of the automatic reclosing sequence. After a trip, the device attempts to reclose. If successful, it waits. If it trips again, it attempts a second reclose after 10 seconds. A third attempt follows after 60 seconds if the second fails. If all three attempts fail within 15 minutes, the device locks out and sends an auxiliary alarm. The power delay (Tr) is 2 seconds. Note: Customization of closing times and delay times requires contacting the manufacturer.
3.3 Funzjoni ta 'qfil

Figure 4: Illustration of the locking mechanism. When the locking function is activated (e.g., by inserting a padlock with a diameter less than 3.5 mm), the RCCB cannot be closed, ensuring safety during circuit checks or maintenance. This prevents accidental reclosure.
4. Setup u Installazzjoni
The GEYA GRD9L-R device is designed for DIN rail mounting and can be integrated with other electrical components such as an RCCB and auxiliary modules.
4.1 Component Integration

Figura 5: Eżample of how the GRD9L-R device can be installed alongside an Auxiliary module and an RCCB on a standard DIN rail. Ensure proper alignment and secure fastening of all components.
4.2 Dijagramma tal-Wiring

Figura 6: Eżample application wiring diagram. This diagram shows the connection of the GRD9L-R device with an alarm lamp, an RCCB, and multiple load circuits. Red lines indicate live connections, blue lines indicate neutral connections. The auxiliary contacts (A1, A2, COM, NO) are used for external signaling, such as an alarm lamp. Always consult a qualified electrician for correct wiring specific to your installation.
4.3 Passi ta' Installazzjoni (Linji Gwida Ġenerali):
- Skonnettjar tal-Enerġija: Kun żgur li l-provvista ewlenija tal-enerġija għaċ-ċirkwit tkun skonnettjata kompletament qabel tibda l-installazzjoni.
- Immuntar: Mount the GRD9L-R device, the associated RCCB, and any auxiliary modules onto a standard DIN rail within an appropriate electrical enclosure.
- Wiring: Connect the input and output terminals of the GRD9L-R and RCCB according to the wiring diagram (Figure 6) and local electrical codes. Pay close attention to live (L) and neutral (N) connections.
- Konnessjonijiet Awżiljarji: If using, connect auxiliary contacts (A1, A2, COM, NO) for remote signaling or control, such as an alarm lamp.
- Verifika: Double-check all wiring connections for tightness and correctness.
- Restawr tal-Enerġija: Ladarba l-installazzjoni tkun tlestiet u vverifikata, erġa' daħħal l-enerġija fiċ-ċirkwit.
5. Istruzzjonijiet Operattivi
5.1 Manual/Automatic Selector
The device features a selector switch labeled "AUTO" and "MANU" (Manual). This switch allows you to choose the operating mode:
- Modalità AUTO: In this mode, the device will automatically attempt to reclose the associated RCCB after a trip, following the reclosing logic described in Figure 3. This is the default and recommended mode for continuous operation.
- MANU Mode: In this mode, the automatic reclosing function is disabled. If the RCCB trips, it must be manually reset. This mode is useful for maintenance or specific operational requirements where automatic reclosure is not desired.
5.2 Reclosing Logic (Auto Mode)
When in AUTO mode, the device follows a specific sequence of reclosing attempts:
- 1st Trip: If the RCD trips, the device waits for 10 seconds, then attempts to reclose.
- 2nd Trip: If the RCD trips again within 15 minutes of the first reclosure, the device waits for 60 seconds, then attempts a second reclosure.
- 3rd Trip: If the RCD trips a third time within 15 minutes of the second reclosure, the device waits for 300 seconds (5 minutes), then attempts a third reclosure.
- Lockout: If the RCD trips a fourth time within 15 minutes, or if any of the three reclosing attempts fail, the device enters a lockout state. It will not attempt further reclosures automatically and will activate the auxiliary alarm contact (if connected). Manual intervention is required to reset the device.
- Resetting Closing Times: If no trip occurs for 15 minutes after a successful reclosure, or if the device is manually reset, the reclosing attempt counter is cleared.
5.3 Buttuna tat-test
The associated RCCB typically has a test button. Pressing this button simulates a leakage fault and should cause the RCCB to trip. This is used to verify the proper functioning of the RCCB and, in AUTO mode, the reclosing device.
6. Manutenzjoni
The GEYA GRD9L-R Automatic Reclosing Device is designed for minimal maintenance. However, regular checks are recommended to ensure optimal performance and safety.
- Spezzjoni Viżwali: Periodically inspect the device for any signs of physical damage, discoloration, or loose connections.
- Test tal-Funzjonalità: Regularly test the associated RCCB using its test button. Observe if the GRD9L-R device initiates its reclosing sequence in AUTO mode.
- Tindif: Ensure the device is kept clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
- Spezzjoni Professjonali: It is recommended to have the electrical system, including this device, inspected by a qualified electrician at least once a year.
7 Issolvi l-problemi
If the GEYA GRD9L-R device is not functioning as expected, consider the following:
| Problema | Kawża Possibbli | Soluzzjoni |
|---|---|---|
| Device does not reclose automatically. |
|
|
| Alarm contact is continuously active. |
|
|
| RCCB trips immediately after reclosure. |
|
|
If the problem persists after attempting these solutions, contact a qualified electrician or GEYA customer support.
8. Speċifikazzjonijiet
| Karatteristika | Dettall |
|---|---|
| Numru tal-Mudell | GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA |
| Brand | GEYA |
| Voltage | 220 Volts AC |
| Kurrent Rated | 63 A (as per model number) |
| Numru ta 'Pollakki | 2 |
| Tip ta 'Circuit Breaker | RCD (Apparat Kurrent Residwu) |
| Tip ta 'Immuntar | Wall Mount, Flush Mount (DIN Rail compatible) |
| Dimensjonijiet tal-Pakkett | 12 x 11.6 x 9.1 ċm |
| Piż tal-oġġett | 350 gramma |
| Manifattur | ZHEJIANG GEYA ELECTRICAL CO.,LTD |
9. Garanzija u Appoġġ
Specific warranty information for the GEYA GRD9L-R Automatic Reclosing Device is not available in the provided product details. Please refer to the product packaging or contact GEYA customer support for detailed warranty terms and conditions.
For technical support, inquiries, or assistance with installation and troubleshooting, please contact GEYA directly through their official channels or the retailer from whom the product was purchased.