1. Introduzzjoni
This manual provides detailed instructions for the proper installation, operation, and maintenance of the APC SL-2000-P Conventional Duct Smoke Detector. This device is designed to detect the presence of smoke within HVAC (Heating, Ventilation, and Air Conditioning) duct systems, providing an early warning of potential fire conditions. Adherence to these instructions is crucial for the detector's optimal performance and your safety.
2. Informazzjoni Importanti dwar is-Sigurtà
- Skonnettja l-Enerġija: Always disconnect all power to the HVAC system and the smoke detector before performing any installation, maintenance, or servicing. Failure to do so may result in electrical shock or damage to the unit.
- Persunal kwalifikat: Installation and servicing of this device should only be performed by qualified and authorized personnel in accordance with all local and national electrical codes and standards.
- Propożizzjoni 65 ta' Kalifornja Twissija: This product can expose you to DINP, which is known to the State of California to cause cancer. For more information, please visit www.P65Warnings.ca.gov.
- Użu Intenzjonat: This detector is intended for use as a conventional duct smoke detector. Do not use for purposes other than its specified design.
3. Prodott Aktarview u Komponenti
The APC SL-2000-P is a photoelectric duct smoke detector designed for reliable smoke detection within air ducts. It features a clear cover allowing visual inspection of internal components and indicators.

Figura 3.1: Fuq view of the SL-2000-P detector. Visible components include the photoelectric sensor head, a red alarm LED, and a test port.
The detector unit includes provisions for air sampling tubes, which extend into the ductwork to draw air samples for analysis. These tubes are essential for the detector's proper function.

Figura 3.2: Ġenb view of the SL-2000-P detector with air sampling tube ports. The accessory bag contains the necessary sampling tubes and additional maintenance instructions.
The product packaging provides critical information regarding specifications, certifications, and manufacturer contact details.

Figure 3.3: Product box label detailing specifications, manufacturer information, and certifications.
4. Speċifikazzjonijiet
| Parametru | Valur |
|---|---|
| Numru tal-Mudell | SL-2000-P |
| Vol Operattivtage (230VAC) | 8mA (Standby), 18mA (Alarm) |
| Vol Operattivtage (120VAC) | 14mA (Standby), 32mA (Alarm) |
| Vol Operattivtage (24VDC) | 14mA (Standby), 68mA (Alarm) |
| Vol Operattivtage (24VAC) | 55mA (Standby), 190mA (Alarm) |
| Veloċità tal-Ajru | 100 sa 4000 pied/min. |
| Indikazzjoni ta' Allarm | LED on Sensor Head |
| Test Capabilities | Test Port Valve and Magnet Test Capability |
| Dimensjonijiet (HxWxD) | 13.5" (34.2cm) x 4.5" (11.4cm) x 2.25" (5.7cm) |
| Ċertifikazzjonijiet | CSFM LISTED, MEA ACCEPTED, UL LISTED |
| UPC | 0814498020033 |
5. Gwida għall-Installazzjoni
Proper installation is critical for the reliable operation of the SL-2000-P detector. It is recommended that installation be performed by a certified HVAC or electrical technician.
- Għażla tal-Post: Choose a suitable location on the HVAC ductwork where airflow is consistent and representative of the air within the system. Avoid locations near bends, dampers, or other obstructions that may cause turbulence.
- Immuntar: Securely mount the detector housing to the ductwork using appropriate fasteners. Ensure the unit is level and stable.
- Ajru S.ampling Tube Installation: Install the provided air sampling tubes into the designated ports on the detector. The tubes must extend into the duct to capture air samples effectively. Ensure the tubes are cut to the correct length for the duct size and that the intake and exhaust holes are properly oriented.
- Wiring: Connect the detector to the appropriate power supply and alarm control panel according to the wiring diagrams provided by the manufacturer (refer to the specific wiring instructions included with your unit). Ensure all connections are secure and comply with local electrical codes. Verify the correct operating voltage (230VAC, 120VAC, 24VDC, or 24VAC) is supplied.
- Power Up: Once all connections are verified, restore power to the HVAC system and the detector. Observe the detector for initial power-up sequence and status indicators.
6. Operazzjoni
The SL-2000-P detector continuously monitors the air within the duct for the presence of smoke particles. When smoke is detected above a predetermined threshold, the unit will activate its alarm.
- Operazzjoni normali: During normal operation, the detector's status indicator (if present) will show a steady state, indicating it is functioning correctly.
- Indikazzjoni ta' Allarm: Upon smoke detection, the red LED on the sensor head will illuminate, and the detector will send an alarm signal to the connected fire alarm control panel.
- Ittestjar: The detector can be tested using two methods:
- Test Port Valve: Introduce approved test smoke into the test port valve to simulate smoke conditions.
- Magnet Test Capability: Use a magnet near the designated area on the detector to initiate a functional test.
7. Manutenzjoni
Regular maintenance is essential to ensure the long-term reliability and effectiveness of your duct smoke detector. Refer to the specific
Dokumenti Relatati - SL-2000-P
![]() |
Manwal tal-Utent tat-Tastiera tal-Kontroll tal-Aċċess APC-KP1-C Manwal tal-utent għat-tastiera tal-kontroll tal-aċċess APC-KP1-C minn APC Automation Systems. Jipprovdi informazzjoni dettaljata dwar l-installazzjoni, l-ispeċifikazzjonijiet tekniċi, l-operazzjonijiet tal-amministratur, is-settings tal-utent, l-indikazzjonijiet tal-ħoss u tad-dawl, u l-ispeċifikazzjonijiet tas-sistema għal kontroll tal-aċċess sigur. |
![]() |
Manwal tal-Installazzjoni tal-Attwatur tal-Awtomazzjoni tal-Bieb STARK6 STARK12 tas-Serje APC Proteous Manwal tal-installazzjoni għall-attwaturi tal-awtomazzjoni tal-bibien tas-Serje APC Proteous STARK6 u STARK12. Jipprovdi speċifikazzjonijiet, struzzjonijiet ta' sigurtà, gwidi tal-installazzjoni pass pass, dijagrammi tal-wajers, u informazzjoni dwar il-garanzija għas-sistemi tal-awtomazzjoni tal-bibien. |
![]() |
Speċifikazzjonijiet Tekniċi tal-APC Smart-UPS SRT 10000VA 208V Speċifikazzjonijiet tekniċi dettaljati għall-APC Smart-UPS SRT 10000VA 208V, inklużi dettalji dwar l-output, l-input, il-batterija, il-komunikazzjoni, id-dettalji fiżiċi, ambjentali u ta' konformità. Mudell SRT10KXLT. |
![]() |
Manwal tal-Prodott tal-Impjant tal-Enerġija DC APC MX28B600 Dan il-manwal tal-prodott jipprovdi informazzjoni dettaljata dwar l-APC MX28B600 DC Power Plant, li jkopri l-installazzjoni, is-setup, it-tħaddim, l-ispeċifikazzjonijiet tekniċi, u l-garanzija. Tgħallem dwar il-karatteristiċi, il-komponenti, u l-manutenzjoni tiegħu mingħand l-APC. |
![]() |
Manuale di Funzionamento APC Smart-UPS C: Guida Completa Manwal tal-funzjonament dettagliato għal APC Smart-UPS C (1000/1500/2000/3000 VA, 120/230 Vac, Montaggio a Rack 2U). Inkludi istruzioni di sicurezza, installazione, funzionamento, specifiche tecniche, risoluzione problemi e. |
![]() |
Guida all'installazione APC Smart-UPS X SMX 2000/2200/3000 XL: Montaggio Rack e Torretta Guida completa all'installazione per i modelli APC Smart-UPS X SMX 2000, 2200 e 3000 XL. Copre il montaggio su rack e torretta, la rimozione della batteria, la configurazione e le caratteristiche del pannello posteriore. Include descrizioni dettagliate dei diagrammi e istruzioni. |