Elitech DMG-4B

Manwal tal-Utent tal-Gauge tal-Manifold Diġitali Intelliġenti Elitech DMG-4B

Model: DMG-4B

Marka: Elitech

1. Prodott Aktarview

The Elitech Smart Digital Manifold Gauge DMG-4B is designed to provide precise measurements for HVAC/R systems. It offers advanced features such as remote firmware upgrades, a comprehensive refrigerant database, and smart app control via Bluetooth. This device aims to simplify complex refrigeration tasks with its digital accuracy and robust design.

Elitech Smart Digital Manifold Gauge DMG-4B

Image: Elitech Smart Digital Manifold Gauge DMG-4B, front view.

Il-karatteristiċi ewlenin jinkludu:

  • Remote firmware upgrade (OTA) for up-to-date functionality.
  • Supports over 140 types of refrigerants with instant updates via the Elitech Tools APP.
  • Bluetooth connectivity for real-time data monitoring and analysis.
  • Digital sensors for enhanced measurement accuracy.
  • Compact, portable, and durable design with up to 200 hours of battery life.

2. X'hemm fil-Kaxxa

The Elitech Smart Digital Manifold Gauge DMG-4B package includes the following items:

  • 1 x Digital Manifold Gauge (DMG-4B)
  • 1 x Bag tal-Ġarr
  • 1 x Manwal għall-Utent
  • 1 x Kaxxa tal-Ippakkjar
Elitech DMG-4B Packing List

Image: Contents of the Elitech DMG-4B package, including the manifold, bag, and manual.

3. Istruzzjonijiet ta' Setup

Follow these steps to set up your Elitech Smart Digital Manifold Gauge DMG-4B for initial use.

3.1. Initial Calibration and Refrigerant Selection

Before each measurement, it is crucial to calibrate the pressure sensor and select the correct refrigerant type.

  1. Ensure there is no connection between the gauge and any pressure source. The gauge should be at atmospheric pressure.
  2. Long press the 'Zero' button to calibrate the pressure sensor. The calibration range is 1-100psi.
  3. To switch the refrigerant type, long press 'Zero' and the 'Down Arrow' button together. Then, short press 'Up Arrow' or 'Down Arrow' to cycle through available refrigerant types.

Video: This video demonstrates how to use the Elitech DMG-4B, including initial setup, calibration, and refrigerant selection.

3.2. App Connection and Firmware Upgrade (OTA)

The Elitech Tools app enhances the functionality of your manifold gauge. It also allows for remote firmware upgrades to keep your device up-to-date.

  1. Download and open the 'Elitech Tools' app on your smartphone.
  2. Click the menu icon in the upper left corner of the homepage and log in or register an account.
  3. On the manifold gauge, click the Bluetooth button. The Bluetooth icon on the display will flash.
  4. In the app, click 'Search nearby device' and connect to your DMG-4B.
  5. If a newer firmware version is available, the device will prompt you to upgrade. Confirm to start the OTA upgrade process. Alternatively, you can manually initiate a firmware update from the app's settings.

Video: This video demonstrates connecting the manifold gauge to the Elitech Tools app and performing a firmware upgrade.

4. Istruzzjonijiet Operattivi

The Elitech DMG-4B offers various functions for comprehensive HVAC/R system analysis. Some advanced functions require in-app purchase.

4.1. DIY Refrigerant List

Customize your refrigerant list by selecting from over 140 available types in the app.

  1. In the Elitech Tools app, click on the refrigerant icon in the upper right corner of the dashboard.
  2. Select the refrigerant types you wish to add or remove from your 'Favorite' list by touching the star icon.
  3. Click the update icon in the upper right corner to save your settings and synchronize with the device.

4.2. Pressure Holding Test (Requires In-App Purchase)

This function allows you to test the pressure integrity of your system.

  1. Connect the high-pressure refrigerant hose to the testing system and close the high-pressure valve.
  2. In the app, navigate to 'Settings' and then 'Hold Pressure Setting'.
  3. Set the charging warning value, decay ratio, enable/disable temperature compensation, and set the pressure-holding time.
  4. On the device, press and hold the 'MODE' and 'Down Arrow' keys simultaneously to enter the pressure-holding test.
  5. Inject gas into the system until the pressure reaches the charging warning value. The device will flash and emit a sound.
  6. Click the 'Down Arrow' button on the device to begin the leak test. The timer will start counting down.
  7. If the pressure remains within the acceptable leak value (calculated based on decay ratio), the test is successful. Otherwise, it indicates a leak.

4.3. Vacuum Measurement (Requires In-App Purchase)

Measure the vacuum level of your system.

  1. Connect the system to the high-pressure side of the manifold and open the high-pressure valve.
  2. Simultaneously press the 'MODE' and 'Down Arrow' buttons twice on the device to enter the vacuum mode.
  3. Connect one end of the refrigerant pipe to the vacuum pump.
  4. Start the vacuum pump and extract pressure from the system. The device will display the vacuum degree and elapsed time.

4.4. Offline Data Logging (Requires In-App Purchase)

Record measurement data directly on the device for later analysis.

  1. In the app, navigate to 'Settings' and then 'Record Function'.
  2. Select the desired recording interval (e.g., 1s, 10s, 1min).
  3. Click 'Start Offline Recording'. The recording icon on the device will light up and flash.
  4. To stop recording, click 'Stop Offline Recording'. The recording icon will turn off.
  5. Biex view or export historical data, click 'Read Device History Data' in the app. Data can be exported in PDF or Excel format.
  6. To clear historical data from the device, click 'Clear Historical Data' in the app.

Video: This video provides an introduction to the Elitech DMG-4B APP's value-added functions, including refrigerant list customization, pressure holding test, vacuum measurement, and offline data logging.

5. Manutenzjoni

Proper maintenance ensures the longevity and accuracy of your Elitech DMG-4B.

  • Tindif: Regularly wipe the device with a soft, damp drapp. Evita li tuża prodotti tat-tindif jew solventi li joborxu li jistgħu jagħmlu ħsara lis-casing jew skrin.
  • Ħażna: Store the manifold gauge in its provided carrying bag in a dry, cool place when not in use.
  • Sostituzzjoni tal-batterija: The device uses replaceable AAA batteries. Replace them promptly when the low battery indicator appears to ensure continuous operation.
  • Kura tas-Sensor: Ensure the pressure ports are free from debris and moisture. Always cap the ports when not connected to a system.

6 Issolvi l-problemi

This section addresses common issues you might encounter with your Elitech DMG-4B.

ĦruġKawża PossibbliSoluzzjoni
Pressure Holding Test Failure
  • System leakage.
  • Refrigerant pipe connection not tightened.
  • Too small leak decay alarm value settings.
  • Check the system for leaks and repair as necessary.
  • Kun żgur li l-konnessjonijiet kollha jkunu ssikkati sew.
  • Adjust the leak decay alarm value in the app settings if appropriate for your system.
Screen goes blank or dims immediatelyLow battery or display settings.Replace batteries. Check app settings for display brightness or auto-off timers.
Kwistjonijiet ta 'konnettività BluetoothOut of range, interference, or app/device not paired correctly.Ensure device and phone are within Bluetooth range. Restart both the device and the app. Re-pair the device through the app.
Qari mhux eżattSensor not calibrated, dirty ports, or incorrect refrigerant selected.Perform pressure sensor calibration. Clean pressure ports. Verify the correct refrigerant type is selected in the device and app.

7. Speċifikazzjonijiet

Detailed technical specifications for the Elitech Smart Digital Manifold Gauge DMG-4B.

SpeċifikazzjoniValur
MudellDMG-4B
Piż tal-oġġett1.5 liri (madwar 680g)
Dimensjonijiet tal-Prodott4.33 x 2.95 x 5.31 pulzieri (madwar 11 x 7.4 x 13.5 ċm)
Medda tal-Pressjoni-14 sa 800 psi
Eżattezza± 1% FS
Riżoluzzjoni1 psi
Unitajiet ta' Pressjonipsi, kg/cm2, kPa, MPa, bar, inHg
Unitajiet tat-Temperatura° C / ° F
Batteriji2 batteriji AAA (inklużi)
Ħajja tal-batterijaSa 200 sigħat
Elitech DMG-4B Dimensions and Specifications

Image: Visual representation of Elitech DMG-4B dimensions and key specifications.

8. Garanzija u Appoġġ

Elitech provides comprehensive support for its products.

  • Garanzija: The Elitech DMG-4B typically comes with a 1-year warranty from the date of purchase. Please refer to the official Elitech webis-sit jew id-dokumentazzjoni tax-xiri tiegħek għal termini u kundizzjonijiet speċifiċi tal-garanzija.
  • Manwal tal-Utent (PDF): For a detailed PDF version of the user manual, please refer to the official product page or Elitech's support resources. Niżżel il-Manwal tal-Utent (PDF)
  • Appoġġ onlajn: For further assistance, technical support, or inquiries, visit the official Elitech websit jew ikkuntattja lis-servizz tal-konsumatur tagħhom.

Dokumenti Relatati - DMG-4B

Preview Manwal tal-Utent tal-Gauge tal-Manifold Diġitali Intelliġenti Elitech MS-100 PLUS
Manwal komprensiv għall-utent għall-Elitech MS-100 PLUS Smart Digital Manifold Gauge, li jkopri l-introduzzjoni tal-prodott, l-istruzzjonijiet tas-sigurtà, aktar minnview, funzjonijiet tal-buttuni, parametri tekniċi, u gwidi ta' tħaddim rapidu għal sistemi ta' refriġerazzjoni u HVAC.
Preview Elitech MS-100 Manwal għall-Utent tal-Gauge tal-Manifold Diġitali
Manwal tal-utent għall-Elitech MS-100 Digital Manifold Gauge, li jiddeskrivi l-karatteristiċi, l-operat, l-ispeċifikazzjonijiet u l-manutenzjoni tiegħu.
Preview Manwal tal-Utent u Speċifikazzjonijiet tal-Gauge tal-Manifold Diġitali tas-Serje Elitech MS-800
Manwal komprensiv għall-utent għall-istrument diġitali tal-manifold tas-Serje Elitech MS-800, li jkopri l-introduzzjoni tal-prodott, linji gwida dwar is-sigurtà, protezzjoni ambjentali, speċifikazzjonijiet dettaljati, u gwidi ta' tħaddim rapidu għall-kejl tal-pressjoni u t-temperatura, testijiet tal-pressjoni ta' żamma, u ċċarġjar tar-refriġerant għal sistemi HVAC u ta' refriġerazzjoni.
Preview Gauge tal-Manifold Diġitali Elitech MS-100: Karatteristiċi, Tħaddim, u Speċifikazzjonijiet
Gwida komprensiva għall-Elitech MS-100 Digital Manifold Gauge, li tkopri l-karatteristiċi tiegħu, it-tħaddim rapidu, l-ispeċifikazzjonijiet tekniċi, il-prekawzjonijiet, u d-dettalji tal-prodott għas-sistemi tal-HVAC u tar-refriġerazzjoni.
Preview Manwal tal-Utent tal-Gauge tal-Manifold Diġitali tas-Serje MS ta' Elitech
Manwal tal-utent għall-gauge diġitali tal-manifold tas-Serje MS ta' Elitech, li jkopri d-deskrizzjoni tal-prodott, dettalji ġeneraliview, funzjonijiet tal-buttuni, speċifikazzjonijiet, gwida ta' bidu rapidu, passi ta' operazzjoni, applikazzjonijiet intelliġenti, u manutenzjoni.
Preview Manifold Diġitali Elitech MS-100: Manwal tal-Utent u Speċifikazzjonijiet
Gwida komprensiva għall-manifold diġitali Elitech MS-100, li tkopri l-karatteristiċi tiegħu, l-ispeċifikazzjonijiet tekniċi, it-tħaddim, l-istruzzjonijiet tas-sigurtà, u s-soluzzjoni tal-problemi. Tgħallem kif tuża l-apparat għal kejl tal-pressjoni u t-temperatura, testijiet tat-tnixxija, proċessi tal-vakwu, u r-reġistrazzjoni tad-dejta bl-app Elitech Tools.