Introduzzjoni
This manual provides essential information for the proper installation, operation, and maintenance of the Simplex 4099-9006 Addressable Manual IDNET Pull Station. Please read this manual thoroughly before attempting any procedures to ensure safe and correct usage.
The Simplex 4099-9006 is designed for use in fire alarm systems to manually initiate an alarm. It is an addressable device, meaning it communicates its status and location to a compatible fire alarm control panel.
Informazzjoni dwar is-Sigurtà
Istruzzjonijiet Importanti dwar is-Sigurtà:
- L-installazzjoni u s-servizz għandhom isiru minn persunal kwalifikat biss.
- Skonnettja l-enerġija kollha qabel isservi.
- Refer to all local and national electrical codes and fire safety regulations.
- Tħaddimx l-apparat jekk jidher li hu bil-ħsara.
- Żgura ertjar xieraq biex tevita xokk elettriku.
Prodott Overview

Figura 1: Quddiem view of the Simplex 4099-9006 Addressable Manual IDNET Pull Station. The device is red with "FIRE ALARM" text at the top, a keyhole for resetting, and a black "PUSH" bar above a white "PULL DOWN" handle with a downward arrow. The Simplex logo is at the bottom.
The Simplex 4099-9006 is a single-action manual pull station designed for flush or surface mounting. It features a durable red housing and clear instructions for activation. The device includes a key-operated reset mechanism.
Setup u Installazzjoni
Proper installation is crucial for the reliable operation of the pull station. Follow these steps carefully:
- Post tal-Immuntar: Select a visible and accessible location, typically near exits, in accordance with local fire codes (e.g., NFPA 72). The handle should be between 42 and 48 inches (107-122 cm) above the finished floor.
- Wiring:
- Ensure power to the fire alarm control panel is disconnected.
- Connect the IDNET communication wiring to the designated terminals on the pull station. Refer to the wiring diagram provided with the device or the control panel manual for specific terminal assignments.
- Maintain proper polarity.
- Immuntar:
- Attach the pull station to a standard single-gang electrical box or a compatible surface mount box using the provided screws.
- Ensure the device is securely fastened and level.
- Indirizzar: The 4099-9006 is an addressable device. Set the address using the rotary switches or dip switches on the back of the unit, as per the fire alarm control panel's programming requirements. Consult the control panel's manual for address range and assignment procedures.
- Assemblea Finali: Secure the front cover of the pull station.
- Ixgħel u Ittestja: Restore power to the fire alarm control panel and perform a functional test of the pull station as described in the "Operating" section.
Istruzzjonijiet Operattivi
The Simplex 4099-9006 is designed for straightforward operation during a fire emergency.
To Activate the Alarm:
- Locate the manual pull station.
- IMBOTTA the black bar at the top of the activation mechanism.
- Immediately after pushing, IĠBED L-ISFEL the white handle firmly until it latches in the activated position.
- This action will send an alarm signal to the fire alarm control panel, initiating the building's alarm sequence.
To Reset the Pull Station:
After an alarm has been activated and the situation is resolved, the pull station must be reset. This requires a special key.
- Insert the Simplex reset key into the keyhole located at the top center of the pull station.
- Turn the key clockwise until the handle returns to its normal, non-activated position.
- Neħħi ċ-ċavetta.
- The fire alarm control panel must also be reset after the pull station has been restored. Refer to the control panel's manual for its specific reset procedure.
Manutenzjoni
Regular maintenance ensures the continued reliability of your Simplex 4099-9006 pull station.
- Spezzjoni Viżwali (Kull Xahar): Check for any physical damage, obstructions, or signs of tampering. Ensure the device is clean and visible.
- Functional Test (Annually or as per local codes):
- Notify building occupants and the monitoring station before testing.
- Activate the pull station as described in the "Operating Instructions" section.
- Verify that the alarm signal is received at the fire alarm control panel and that associated alarm functions (e.g., sirens, strobes) activate correctly.
- Reset the pull station and the fire alarm control panel.
- Document all tests, including date, time, and results.
- Tindif: Uża drapp artab u niexef biex tnaddaf il-barra. Tużax prodotti tat-tindif jew solventi li joborxu.
Issolvi l-problemi
This section addresses common issues you might encounter with the Simplex 4099-9006 pull station.
| Problema | Kawża Possibbli | Soluzzjoni |
|---|---|---|
| L-istazzjon tal-ġbid ma jattivax l-allarm. |
|
|
| L-istazzjon tal-ġbid ma jistax jiġi rrisettjat. |
|
|
| Control panel shows a trouble signal for the pull station. |
|
|
For issues not listed here, or if solutions do not resolve the problem, contact qualified fire alarm service personnel.
Speċifikazzjonijiet
| Karatteristika | Dettall |
|---|---|
| Numru tal-Mudell | 4099-9006 |
| Tip | Stazzjon tal-Iġbed Manwali Indirizzabbli |
| Metodu ta' Attivazzjoni | Push/Pull Down |
| Irrisettja l-Metodu | Irrisettjar taċ-Ċavetta |
| Kulur | Aħmar |
| Dimensjonijiet (Approx.) | 5.39 x 4.45 x 4.09 pulzieri (Dimensjonijiet tal-Pakkett) |
| Piż (Approx.) | 12.8 uqija (0.8 lbs) |
| Sors tal-Enerġija | System Powered (Manual Activation) |
| Kompatibilità | Simplex IDNET Fire Alarm Control Panels |
Informazzjoni dwar Garanzija
Specific warranty terms for the Simplex 4099-9006 are typically provided at the point of purchase or can be obtained directly from Simplex or an authorized distributor. Generally, Simplex products come with a limited warranty covering defects in materials and workmanship under normal use and service.
For detailed warranty information, please refer to the documentation included with your purchase or visit the official Simplex websit. Żomm il-prova tax-xiri tiegħek għal talbiet ta' garanzija.
Appoġġ u Kuntatt
If you require technical assistance, have questions regarding installation, operation, or maintenance, or need to report a malfunction, please contact your authorized Simplex distributor or service provider.
For general inquiries, you may visit the official Simplex website or refer to the contact information provided in your system's overall documentation.
Nota: Do not attempt to repair the device yourself. Servicing should only be performed by qualified and authorized personnel.