Notifier FST-951

Manwal tal-Utent tas-Sensor Termali tat-Temperatura Fissa Notifier FST-951

Model: FST-951

1. Prodott Aktarview

The Notifier FST-951 is a fixed temperature thermal sensor designed for integration into fire alarm systems. This device detects heat exceeding a predetermined threshold, triggering an alarm condition. It utilizes FlashScan Technology for efficient communication within compatible Notifier systems. The sensor is housed in a white casing, suitable for various indoor environments.

Quddiem view of the Notifier FST-951 Fixed Temperature Thermal Sensor

Figura 1: Quddiem view of the Notifier FST-951 Fixed Temperature Thermal Sensor. This image shows the white, circular sensor head with a central, slightly recessed element.

2. Installazzjoni u Setup

Installation of the Notifier FST-951 thermal sensor should only be performed by qualified personnel in accordance with all local and national electrical codes and standards, including NFPA 72. Proper placement is crucial for effective fire detection.

2.1 Immuntar

  1. Ensure the mounting location is clean, dry, and free from obstructions that could impede heat detection.
  2. Attach the compatible sensor base (not included) securely to the ceiling or wall using appropriate fasteners.
  3. Connect the system wiring to the terminals on the sensor base as per the wiring diagram provided with the base and control panel documentation.
  4. Align the FST-951 sensor head with the mounting base and rotate clockwise until it clicks into place, ensuring a secure electrical connection.
Lura view of the Notifier FST-951 Thermal Sensor showing mounting points and electrical contacts

Figura 2: Wara view of the Notifier FST-951 sensor head. This image displays the electrical contacts and mounting alignment features on the back of the sensor, which connect to a separate base.

2.2 Qawwa Inizjali

Once installed, apply power to the fire alarm control panel. The sensor will perform a self-diagnostic check. Refer to the control panel manual for specific power-up sequences and indicator lights.

3. Operazzjoni

The Notifier FST-951 is a fixed temperature thermal sensor, meaning it activates when the ambient temperature at the sensor location reaches a specific, predetermined threshold. It does not detect smoke or rapid temperature changes (rate-of-rise) unless specified by the model variant.

  • Operazzjoni normali: Under normal conditions, the sensor continuously monitors the ambient temperature. There are typically no visible indicators (like flashing LEDs) during normal operation for this specific model, as it is a thermal sensor head. Communication with the control panel occurs via FlashScan Technology.
  • Kundizzjoni ta' allarm: If the temperature at the sensor reaches its fixed activation point (e.g., 135°F or 155°F, depending on the specific model variant), the sensor will enter an alarm state. This alarm condition is communicated to the fire alarm control panel, which will then initiate its programmed alarm sequence (e.g., activating audible/visual alarms, notifying monitoring stations).
  • Issettjar mill-ġdid ta' Allarm: After an alarm condition, the sensor will remain in alarm until the temperature drops below the alarm threshold and the fire alarm control panel is reset. Refer to your control panel's manual for proper alarm reset procedures.

4. Manutenzjoni

Regular maintenance ensures the continued reliability and proper functioning of your thermal sensor. Always follow NFPA 72 guidelines for inspection, testing, and maintenance of fire alarm systems.

4.1 Tindif

  • Frekwenza: Inspect the sensor head annually for dust, dirt, or obstructions. More frequent cleaning may be required in dusty environments.
  • Proċedura:
    1. Notify relevant personnel that the fire alarm system will be temporarily taken out of service to prevent false alarms.
    2. Carefully remove the sensor head from its base by rotating counter-clockwise.
    3. Uża artab, damp cloth to wipe the exterior of the sensor. Do not use harsh chemicals or abrasive cleaners.
    4. Kun żgur li ma tidħol l-ebda umdità fil-komponenti interni.
    5. Reattach the sensor head to its base, ensuring it is securely seated.
    6. Restore the fire alarm system to normal operation and verify proper communication with the control panel.
Notifier FST-951 sensor with an orange protective cap and instruction manual

Figure 3: Notifier FST-951 sensor shown with its protective orange cap and a small instruction manual. The cap is typically removed before operation but can be used during maintenance or storage.

4.2 Ittestjar

Functional testing of thermal sensors should be conducted periodically by trained professionals. This typically involves applying a controlled heat source to the sensor to verify its activation at the specified temperature. Consult NFPA 72 and local codes for testing frequency and methods.

5 Issolvi l-problemi

This section provides general guidance for common issues. For complex problems, always contact a qualified fire alarm technician.

ProblemaKawża PossibbliSoluzzjoni
Sensor not reporting to control panelLoose connection, incorrect wiring, sensor fault, control panel issue.
  • Verify sensor is securely seated on its base.
  • Check wiring connections at the base and control panel.
  • Consult control panel diagnostics for specific error codes.
  • Contact a qualified technician for further diagnosis.
Sensor in alarm without apparent heat sourceActual high temperature, sensor fault, environmental factors.
  • Investigate the area for any actual heat sources.
  • Ensure ambient temperature is below the sensor's activation point.
  • If no heat source is present, the sensor may be faulty.
  • Contact a qualified technician for inspection and replacement if necessary.

6. Speċifikazzjonijiet

KaratteristikaDettall
BrandNotifikatur
Numru tal-MudellFST-951
Tip tas-SensorFixed Temperature Thermal Sensor
KulurAbjad
Piż tal-oġġett4.7 uqija (madwar 133 gramma)
Sors tal-EnerġijaSystem Powered (via fire alarm control panel)
Tip ta 'allarmAudible (via connected fire alarm system)
TeknoloġijaFlashScan Technology
UPC734038305089
Numru tal-PartiNFST951
Dimensjonijiet tal-Pakkett4.53 x 4.29 x 1.93 pulzieri

7. Garanzija u Appoġġ

For detailed warranty information, please refer to the official documentation provided by Notifier at the time of purchase or visit the Notifier website. For technical support, installation assistance, or service, please contact your authorized Notifier dealer or a qualified fire alarm system professional.

Manifattur: NOTIFIKAR

Websit: www.notifier.com (Eżampil-link, il-link attwali jista' jvarja)

Dokumenti Relatati - FST-951

Preview Istruzzjonijiet ta' Installazzjoni u Manutenzjoni tas-Sensors tat-Temperatura Programmabbli Intelliġenti tas-Serje Notifier FST-951
Gwida għall-installazzjoni u l-manutenzjoni għal Notifier FST-951, FST-951-IV, FST-951R, FST-951R-IV, FST-951H, u FST-951H-IV Sensuri tat-Temperatura Programmabbli Intelliġenti. Tkopri l-ispeċifikazzjonijiet, id-deskrizzjoni ġenerali, il-wajers, l-ittestjar, it-tindif, u d-dikjarazzjoni tal-FCC.
Preview Notifier FST-951-SELFT Intelligent Programmable Temperature Self-Test Sensor Installation Guide
Comprehensive installation and maintenance guide for the Notifier FST-951-SELFT Intelligent Programmable Temperature Self-Test Sensor. Details specifications, wiring procedures, self-test and manual testing methods, cleaning instructions, and compliance information for this UL 521 listed fire alarm device.
Preview Notifier FSP-951 and FSP-951-IV Intelligent Photoelectric Smoke Sensors Installation and Maintenance
This document provides installation and maintenance instructions for Notifier FSP-951 and FSP-951-IV intelligent photoelectric smoke sensors. It details product specifications, wiring guidelines, testing procedures, cleaning methods, and compliance information for fire detection systems.
Preview Manwal tal-Wajers tan-Notifier SLC: Gwida għall-Installazzjoni tal-Panel tal-Kontroll Intelliġenti
Manwal komprensiv tal-wajers għal apparati Notifier Intelligent Control Panel SLC. Ikopri l-installazzjoni, ir-rekwiżiti tal-wajers, l-ispeċifikazzjonijiet tal-apparat, u l-prekawzjonijiet ta' sigurtà għal sistemi ta' allarm tan-nar, li jappoġġjaw diversi Notifier FACPs.
Preview NOTIFIER N16 Pannell tal-Kontroll tal-Allarm tan-Nar - Sistema ta' Sigurtà tal-Ħajja Skalabbli u Konnessa
Esplora l-Pannell tal-Kontroll tal-Allarm tan-Nar (FACP) NOTIFIER N16 minn Honeywell, li għandu touchscreen ta' 10", kapaċità skalabbli għal apparati indirizzabbli intelliġenti, u integrazzjoni ma' Connected Life Safety Services (CLSS). Tgħallem dwar il-karatteristiċi, l-ispeċifikazzjonijiet, u l-komponenti kompatibbli tiegħu għal skoperta u evakwazzjoni avvanzati tan-nar.
Preview Skeda Teknika tas-Sistema ta' Allarm tan-Nar Indirizzabbli Intelliġenti Notifier NFS-320
Skeda tad-dejta komprensiva għas-Sistema ta' Allarm tan-Nar Indirizzabbli Intelliġenti Notifier NFS-320, li tiddeskrivi l-karatteristiċi tagħha, il-kapaċitajiet ta' sensing intelliġenti, il-protokoll FlashScan, l-ispeċifikazzjonijiet tas-sistema, l-apparati kompatibbli, u l-approvazzjonijiet tal-aġenzija.