1. Matulview
The SMARTGEN HAT600N series ATS controller is an intelligent dual-supply module designed for automatic transfer switch (ATS) applications. It features programmable functions, automatic measurement capabilities, an LCD display, and digital communication. This controller integrates digital intelligence and networking to minimize operational errors, making it an ideal solution for ATS systems.
At its core, the HAT600N series ATS controller utilizes a microprocessor to accurately detect 2-way-3-phase voltage. It can make precise judgments and output passive control switch commands in response to abnormal voltage conditions, including over/under voltage, phase loss, and over/under frequency. The controller is designed with comprehensive consideration for various ATS applications, allowing direct use with Intelligent ATS, Contactor ATS, and Circuit Breaker ATS systems. Its compact structure, advanced circuitry, simple wiring, and high reliability make it suitable for a wide range of applications in electric power, telecommunications, petroleum, coal, metallurgy, railways, municipal administration, intelligent buildings, electrical devices, automatic control, and testing systems.

Figura 1: Quddiem view of the SMARTGEN HAT600N ATS Controller. This image displays the controller's user interface, including the LCD screen, alarm indicator, setting buttons, and operational mode buttons (Manual, Auto, Open, Close, Test).
2. Prestazzjoni u Karatteristiċi
- System type can be set for: Mains (1#) & Mains (2#), Mains (1#) & Generator (2#), Generator (1#) & Mains (2#), Generator (1#) & Generator (2#).
- Backlit 128x64 LCD, optional Chinese and English display, push-button operation.
- Kejjel u wiri 2-way 3 phase Voltage u Frekwenza:
- 1 #: Line-Line voltage (Uab, Ubc, Uca), Line-Nature voltage (Ua, Ub, Uc), Frequency (F1)
- 2 #: Line-Line voltage (Uab, Ubc, Uca), Line-Nature voltage (Ua, Ub, Uc), Frequency (F2)
- Measure and display active power, apparent power, power factor and 3 phase current.
- Over current alarm.
- Vol over / undertage, telf ta 'fażi, sekwenza ta' fażi inversa, protezzjoni tal-frekwenza fuq / taħt.
- Automatic/Manual mode. In manual mode, can force switch to close or open.
- All parameters can be set on site. With two different passwords which ensures authorized staff operation only.
- During genset testing ATS controller can be set either On-load or Off-load mode.
- Il-Kontrollur ATS għandu funzjoni ta 'għeluq mill-ġdid awtomatiku.
- Is-sinjal tal-ħruġ tal-għeluq jista 'jiġi ssettjat bħala fuq intervalli jew bħala output kontinwu.
- Applikabbli għal ATS ta' pożizzjoni newtrali waħda, żewġ pożizzjonijiet newtrali u bidla.
- Applikabbli għal 2 linja newtrali iżolati għal Ġeneratur u Mains.
- Arloġġ f'ħin reali (RTC).
- Il-ġurnal tal-avvenimenti jista 'jirreġistra 99 oġġett b'mod ċirkolari.
- L-iskeda f'waqtha tista 'tiġi stabbilita fuq bażi ta' kull xahar jew kull ġimgħa u l-prova tista 'tiġi ssettjata bħal fuq tagħbija jew off-load.
- Can control two generators to work in a cycle, even the genset running time and crank rest time can be set.
- Firxa wiesgħa ta 'provvista ta' enerġija DC (8V sa 35V). Max.80V DC input jista 'jiġi mġarrab fi instant, jew jiġi fornut permezz ta' modulu HWS560 (input AC 85V ~ 560V, output DC 12V).
- Spazju wiesa 'bejn terminali ta' konnessjoni ta 'input AC. Max.625V input voltage.
- With standard isolated RS485 communication interface. With "remote controlling, remote measuring, remote communication" function by the ModBus communication protocol.
- Tista 'tiċċekkja l-istatus attwali tal-kontrollur (inkluż swiċċ diġitali input, fuq Voltage, u taħt Voltage eċċ.).
- Adattat għal diversi sistemi AC (3 fażi 4-wajers, 3-fażi 3-wajers, fażi waħda 2-wajers, u 2-fażi 3-wajers).
- Disinn modulari, qoxra tal-plastik ABS reżistenti għall-fjammi, terminali plug-in u installazzjoni inkorporata. Struttura kompatta b'installazzjoni faċli.
3. Setup u Installazzjoni
Proper installation is crucial for the safe and reliable operation of the HAT600N ATS Controller. This section provides general guidance; always refer to the detailed wiring diagrams and local electrical codes.
3.1 Dijagrammi tal-Wiring
The HAT600N controller supports various ATS configurations. Below are illustrative wiring diagrams for common setups. Ensure you select the correct diagram for your specific ATS type (ATS3, SGQ-N/T, SGQ-M, VITZRO).

Figure 2: Comprehensive wiring diagrams for different ATS control module types compatible with the HAT600N. Each diagram illustrates connections for 1# Voltage Input, 2# Voltage Input, 3-Phase Current Input, and RS485 communication, along with load and generator connections.
3.2 Immuntar
The HAT600N features a modular design for embedded installation. Ensure adequate space for ventilation and access to terminals. The panel cutout dimensions are 186mm x 141mm.
3.3 Provvista tal-Enerġija
The controller operates on a wide DC power supply range of 8V to 35V. It can withstand a maximum 80V DC input momentarily. Alternatively, it can be supplied via an HWS560 module (AC 85V~560V input, DC 12V output).
3.4 AC VoltagInput
The controller supports various AC systems (3-phase 4-wire, 3-phase 3-wire, single-phase 2-wire, and 2-phase 3-wire). Ensure correct wiring for voltage inputs (L-L and L-N) as per the specific model variant (HAT600N/HAT600NI or HAT600NB/HAT600NBI).
4. Istruzzjonijiet Operattivi
The HAT600N ATS Controller offers both automatic and manual operating modes, controlled via its push-button interface and LCD display.
4.1 Għażla tal-Modalità
- Modalità Awtomatika: The controller continuously monitors the primary and secondary power sources. Upon detection of an abnormality in the primary source, it automatically initiates the transfer sequence to the secondary source. Once the primary source recovers, the system automatically transfers back.
- Modalità Manwali: Allows for manual control of the transfer switch. In this mode, operators can force the switch to close or open using the dedicated buttons on the controller's front panel. This mode is typically used for testing or maintenance.
4.2 Settings tal-Parametru
All operational parameters can be configured directly on site using the controller's push-buttons and LCD display. Access to these settings is protected by two different password levels to ensure only authorized personnel can make adjustments. Parameters include system type, voltage/frequency thresholds, transfer delays, and scheduling for genset trials.
4.3 Monitoraġġ
The LCD display provides real-time monitoring of 2-way 3-phase voltage, frequency, active power, apparent power, power factor, and 3-phase current for both power sources. The controller also logs up to 99 events circularly, providing a history of operations and alarms.
5. Speċifikazzjonijiet
The following table details the technical specifications of the SMARTGEN HAT600N ATS Controller:
| Oġġett | Kontenut |
|---|---|
| Provvista ta 'enerġija DC | 8.0V-35.0V continuous power supply; HTS220/HWS560 power supply (without DC input). |
| Vol Operattivtage | AC 160V-280V (HAT600N/HAT600NI) during AC power L1N1/L2N2 supply. |
| Konsum tal-Enerġija | <2W (modalità Standby: <2W) |
| AC VoltagInput |
|
| Frekwenza Rated | 50/60Hz |
| Close / Open Trip Relay Output | 16A AC250V Free Voltage output relay |
| Output Relay programmabbli | 16A/7A AC250V Free Voltage output relay |
| Input Diġitali | Konnessjoni ma 'GND |
| Komunikazzjoni | Interfaċċja iżolata RS485, Protokoll MODBUS |
| Dimensjonijiet | 209mm x 153mm x 55mm |
| Qtugħ tal-Panew | 186mm x 141mm |
| Temp operattiv. Firxa | Temperature: (-25~+70)°C; Humidity: (20~93)%RH |
| Kundizzjoni tal-Ħażna | Temperatura: (-25 ~ + 70) °C |
| Protezzjoni Rank | Siegla IP55 |
| Qawwa tal-Insulazzjoni | Applika AC2.2kV voltage bejn vol għolitage terminali u vol baxxtage terminal; Il-kurrent tat-tnixxija mhuwiex aktar minn 3mA fi żmien 1min. |
| Piż | 0.8kg (HAT600N, HAT600NI) / 1.0kg (HAT600NB/HAT600NBI) |
| Dimensjonijiet tal-Prodott | 8.23 x 6.02 x 2.17 pulzieri |
| Piż tal-oġġett | 1.7 liri |
6. Manutenzjoni
To ensure the longevity and optimal performance of your SMARTGEN HAT600N ATS Controller, regular maintenance is recommended. While the controller is designed for high reliability, periodic checks can prevent potential issues.
- Spezzjoni Viżwali: Spezzjona l-kontrollur perjodikament għal kwalunkwe sinjal ta’ ħsara fiżika, konnessjonijiet maħlula, jew akkumulazzjoni ta’ trab.
- Tindif: Keep the controller's exterior and display clean using a soft, dry cloth. Avoid using abrasive cleaners or solvents.
- Verifiki tat-Terminal: Ensure all wiring terminals are securely fastened. Loose connections can lead to intermittent operation or damage.
- Kundizzjonijiet Ambjentali: Verify that the operating environment remains within the specified temperature and humidity ranges to prevent premature component failure.
- Aġġornamenti tal-Firmware: Iċċekkja l-manifattur webis-sit għal kwalunkwe aġġornamenti tal-firmware disponibbli li jistgħu jtejbu l-prestazzjoni jew jindirizzaw kwistjonijiet magħrufa.
For any complex maintenance or repairs, it is recommended to contact qualified service personnel or SMARTGEN technical support.
7 Issolvi l-problemi
This section provides general guidance for common issues you might encounter with the HAT600N ATS Controller. For detailed diagnostics, refer to the full product manual or contact technical support.
- Il-Kontrollur Mhux Qed Jixgħel:
- Iċċekkja l-konnessjonijiet tal-provvista tal-enerġija DC u kun żgur li l-volumtage huwa fil-medda 8V-35V.
- If using an HWS560 module, verify its AC input and DC output.
- Inspect fuses if present in the power supply line.
- Trasferiment Awtomatiku Mhux Qed Iseħħ:
- Ensure the controller is in "Automatic Mode".
- Iċċekkja voltage and frequency readings on the LCD for both sources to confirm abnormalities are detected.
- Verify that protection parameters (over/under voltage, frequency, phase loss) are correctly set and not preventing transfer.
- Inspect control wiring to the ATS mechanism.
- Qari Żbaljat fuq l-LCD:
- Ivverifika l-volum tal-ACtage and current input wiring according to the appropriate diagram (Figure 2).
- Ensure the system type (3-phase 4-wire, etc.) is correctly configured in the controller settings.
- Kwistjonijiet ta' Komunikazzjoni (RS485):
- Check RS485 wiring for correct polarity and secure connections.
- Verify ModBus communication parameters (baud rate, address) are correctly set on both the controller and the connected device.
If the issue persists after performing these checks, contact SMARTGEN technical support for further assistance.
8. Garanzija u Appoġġ
For information regarding the product warranty, please refer to the warranty card included with your purchase or visit the official SMARTGEN website. Warranty terms typically cover manufacturing defects under normal operating conditions.
For technical support, troubleshooting assistance, or inquiries about spare parts, please contact SMARTGEN customer service. You can find contact information on the SMARTGEN-America webis-sit jew permezz tad-distributur lokali tiegħek.
When contacting support, please have your product model (HAT600N) and any relevant purchase details ready to facilitate a quicker resolution.