1. Introduzzjoni u Fuqview
This manual provides essential instructions for the safe and effective installation, operation, and maintenance of the Zurn RV 150 PSI CA# FWL-2 Water Equipment. This device is designed to prevent over-pressure in storage tanks, ensuring system integrity and safety. Please read this manual thoroughly before installation or use.

Figura 1: Zurn RV 150 PSI CA# FWL-2 Water Equipment. This image shows the brass pressure relief valve with a male NPT inlet and a female NPT outlet, along with the pressure setting mechanism on top.
2. Informazzjoni dwar is-Sigurtà
TWISSIJA: Improper installation or use of this device can lead to property damage, serious injury, or death. All installation and maintenance should be performed by a qualified professional in accordance with local codes and regulations.
- Always depressurize the system before attempting any installation, maintenance, or inspection.
- Ilbes tagħmir protettiv personali (PPE) xieraq waqt l-installazzjoni u l-manutenzjoni.
- Ensure the valve's pressure setting matches the system requirements and is not exceeded.
- M'għandekx tamper with the factory-set pressure relief mechanism.
- This device is designed for water equipment and storage tanks. Consult a professional for specific application suitability.
3. Karatteristiċi tal-prodott
- Prevents over-pressure of storage tanks.
- Available with various PSI settings, including 30, 75, 100, 125, and 150 PSI.
- Features a 3/4" male NPT inlet and a 3/4" female NPT outlet for standard connections.
- CSA Compliance to ANSI Z21.22/CSA 4.4.
- Certified to ASME Section IV by National Board.
4. X'hemm fil-Kaxxa
Il-pakkett tal-prodott tipikament jinkludi:
- One (1) Zurn RV 150 PSI CA# FWL-2 Relief Valve.
Please inspect the contents upon receipt to ensure all components are present and undamaged.
5. Setup u Installazzjoni
Installation should only be performed by a qualified plumber or technician. Adhere to all local plumbing codes and regulations.
- Depressurizzazzjoni tas-Sistema: Before beginning installation, ensure the water system is completely shut off and depressurized. Drain any residual water from the system.
- Għażla tal-Post: Install the relief valve in an accessible location on the storage tank or water equipment, typically at the highest point or as specified by the tank manufacturer.
- Thread Preparation: Apply appropriate thread sealant (e.g., PTFE tape or pipe dope) to the 3/4" male NPT inlet threads of the relief valve.
- Konnessjoni: Carefully thread the valve into the designated port on the storage tank. Tighten securely using a wrench, but do not overtighten, which can damage the valve or tank.
- Pajpijiet ta' Skariku: Connect appropriate discharge piping to the 3/4" female NPT outlet. The discharge pipe must be sized correctly, sloped for drainage, and terminate in a safe location where discharged water will not cause damage or injury. Do not cap or restrict the discharge pipe.
- System Repressurization: Slowly repressurize the system and check for leaks at all connections.
- Kontroll tal-Funzjonalità: Verify that the valve is not leaking and that the system pressure is within acceptable limits for the valve's setting.
6. Operazzjoni
The Zurn RV 150 PSI CA# FWL-2 Water Equipment is an automatic pressure relief valve. It is designed to open and discharge water when the system pressure exceeds its factory-set limit (e.g., 150 PSI for this model). This action prevents excessive pressure buildup within the storage tank, protecting the tank and connected components from potential damage.
Under normal operating conditions, the valve remains closed. If the valve discharges water, it indicates an over-pressure condition in the system. Investigate the cause of the over-pressure immediately.
7. Manutenzjoni
Regular inspection and maintenance are crucial for the continued safe operation of the relief valve. It is recommended to have the valve inspected annually by a qualified professional.
- Spezzjoni Viżwali: Check the valve and discharge piping for any signs of corrosion, leaks, or damage.
- Test manwali: Periodically, and with caution, manually operate the relief valve by lifting the test lever (if present) to ensure it opens and closes freely. Allow a small amount of water to discharge, then release the lever. If the valve does not discharge or does not close completely, it may need replacement.
- Sostituzzjoni: Relief valves have a service life and may require replacement after several years of service, especially if signs of wear, leakage, or malfunction are observed. Consult a professional for replacement recommendations.
8 Issolvi l-problemi
| Problema | Kawża Possibbli | Soluzzjoni |
|---|---|---|
| Valve continuously drips or leaks. |
|
|
| Valve does not discharge during over-pressure. |
|
|
| Water discharges frequently. |
|
|
For persistent issues or if you are unsure about any troubleshooting steps, contact a qualified plumbing professional.
9. Speċifikazzjonijiet
| Attribut | Dettall |
|---|---|
| Brand | Zurn |
| Numru tal-Mudell | P1000AXL-150C |
| Deskrizzjoni tal-Prodott | RV 150 PSI CA# FWL-2 Lead Free Water Equipment |
| Daqs | 3/4 pulzier |
| Konnessjoni tad-Dħul | 3/4" Male NPT |
| Konnessjoni tal-Ħut | 3/4" NPT femminili |
| Materjal | Ram |
| Kulur | Ram |
| Finish ta 'barra | Ram |
| Tip ta' Thread | NPT |
| Piż tal-oġġett | 0.5 Liri (madwar 8 uqija) |
| Dimensjonijiet tal-Prodott (L x W x H) | 1.25 x 1.25 x 3.44 pulzieri |
| Ċertifikazzjonijiet | CSA Compliance to ANSI Z21.22/CSA 4.4, Certified to ASME Section IV by National Board |
10. Garanzija u Appoġġ
For information regarding product warranty, technical support, or replacement parts, please contact Zurn customer service directly. You can find contact information and additional resources on the official Zurn webis-sit jew billi żżur il- Zurn Store on Amazon.