1. Introduzzjoni
This manual provides essential information for the proper installation, operation, and maintenance of the Simplex 4090-9116 Addressable IDNet Isolator. This device is designed to enhance the reliability of fire alarm systems by isolating faults on the Signaling Line Circuit (SLC).
2. Prodott Aktarview
The Simplex 4090-9116 is an addressable IDNet isolator module. Its primary function is to protect the integrity of the IDNet communication loop by automatically isolating sections of the circuit that develop a short circuit fault. This ensures that other parts of the fire alarm system continue to operate normally, maintaining critical communication and detection capabilities.
When a short circuit is detected, the isolator opens the circuit on both sides of the fault, effectively removing the faulty section from the loop. Once the fault is cleared, the isolator automatically restores the circuit to normal operation. This self-healing capability significantly improves system resilience and reduces downtime during fault conditions.

Figura 2.1: Quddiem view of the Simplex 4090-9116 Addressable IDNet Isolator, showing terminal blocks for wiring connections.
3. Informazzjoni dwar is-Sigurtà
TWISSIJA:
- Installation and servicing must be performed by qualified personnel only, in accordance with all local and national electrical codes, and the National Fire Alarm and Signaling Code (NFPA 72).
- Disconnect all power before installing or servicing this device to prevent electrical shock and/or equipment damage.
- Ensure proper grounding and wiring to prevent system malfunctions.
- Do not operate the device outside its specified environmental limits.
4. Setup u Installazzjoni
The 4090-9116 isolator is designed for easy integration into Simplex IDNet fire alarm systems. It typically mounts in a standard 4-inch square electrical box or compatible enclosure.

Figure 4.1: The 4090-9116 isolator module shown with its original packaging and accompanying instruction manual.
4.1 Immuntar
- Select a suitable location for mounting, ensuring it complies with local fire codes and accessibility requirements.
- Mount the isolator module securely within a compatible electrical box or enclosure using appropriate fasteners.
4.2 Wajers
Connect the IDNet Signaling Line Circuit (SLC) wiring to the designated terminals on the isolator module. Ensure correct polarity and secure connections. Refer to the specific wiring diagrams provided with your Simplex fire alarm control panel and the isolator's included documentation for detailed instructions.
- Input/Output terminals are clearly marked.
- Use appropriate wire gauge as specified by system requirements.
- Verify all connections before applying power.

Figure 4.2: The 4090-9116 isolator module securely placed within its protective cardboard packaging, ready for installation.
4.3 Indirizzar
The 4090-9116 is an addressable device. Set the unique address for the isolator using the rotary switches or DIP switches on the module, as per your system's addressing scheme. Consult the fire alarm control panel's manual for address assignment procedures.
5. Prinċipji Operattivi
The Simplex 4090-9116 operates passively within the IDNet SLC. It continuously monitors the circuit for short circuit conditions. In the event of a short circuit:
- The isolator detects the fault and automatically opens the circuit on both sides of the shorted section.
- This action prevents the short circuit from affecting the entire SLC loop, allowing other devices on the unaffected sections to continue communicating with the fire alarm control panel.
- Once the short circuit is resolved, the isolator automatically closes the circuit, restoring full loop communication.
The isolator does not require external power; it draws power directly from the IDNet SLC.
6. Manutenzjoni
The Simplex 4090-9116 isolator is designed for reliable, long-term operation with minimal maintenance. However, regular system checks are recommended as part of a comprehensive fire alarm system maintenance program.
- Spezzjoni Viżwali: Periodically inspect the isolator and its wiring for any signs of physical damage, corrosion, or loose connections.
- Ittestjar tas-Sistema: Ensure the isolator's functionality is verified during routine fire alarm system testing, as required by NFPA 72 and local codes. This typically involves simulating a fault to confirm proper isolation.
- Tindif: If necessary, gently clean the exterior of the device with a soft, dry cloth. Do not use abrasive cleaners or solvents.
Any maintenance or repair beyond visual inspection and cleaning should be performed by a qualified fire alarm technician.
7 Issolvi l-problemi
If a fault is indicated on the fire alarm control panel related to an IDNet SLC, and an isolator is suspected, consider the following:
- System Fault Indication: If the control panel indicates an SLC fault, identify the specific section of the loop that is isolated. This points to the location of the short circuit.
- Verifika tal-Wajers: Verify all wiring connections to the isolator and connected devices for shorts, opens, or ground faults.
- Ħsara fl-apparat: While rare, an isolator itself could malfunction. If all other devices and wiring in the isolated section are confirmed to be fault-free, the isolator may need to be replaced by a qualified technician.
- Kwistjonijiet ta' Enerġija: Ensure the fire alarm control panel is providing stable power to the SLC.
Always consult the fire alarm control panel's troubleshooting guide for specific fault codes and resolutions.
8. Speċifikazzjonijiet
| Attribut | Valur |
|---|---|
| Brand | Simplex |
| Numru tal-Mudell | 4090 9116 |
| Numru tal-Parti | 4090-9116 |
| Piż tal-oġġett | 16 uqija (1 libbra) |
| Dimensjonijiet tal-Prodott | 23 x 16 x 18 pulzieri (dimensjonijiet tal-ippakkjar) |
| Sors tal-Enerġija | IDNet SLC |
| Batteriji Inklużi? | Nru |
| Batteriji Meħtieġa? | Nru |
| Manifattur | Simplex |
| UPC | 643485654193 |
| Data L-Ewwel Disponibbli | 5 ta’ Awwissu, 2015 |
Note: Product dimensions listed may refer to shipping package dimensions rather than the device itself.
9. Garanzija u Appoġġ
For warranty information and technical support regarding your Simplex 4090-9116 Addressable IDNet Isolator, please contact Simplex customer service or your authorized Simplex distributor. Ensure you have your product model number and any relevant system details available when seeking support.
For general inquiries, you may refer to the official Simplex website or contact their support channels. Always rely on qualified professionals for installation, maintenance, and troubleshooting of fire alarm system components.





