Trane PSE-T19

Trane Furnace Flame Sensor PSE-T19 Instruction Manual

Model: PSE-T19 (Part Number: SEN01114_v4)

1. Introduzzjoni

This manual provides essential information for the proper installation, operation, maintenance, and troubleshooting of the Trane Furnace Flame Sensor, model PSE-T19. This component is a critical safety device designed to ensure the safe and efficient operation of your furnace. Please read this manual thoroughly before attempting any procedures.

2. Informazzjoni dwar is-Sigurtà

TWISSIJA: Installazzjoni, aġġustament, alterazzjoni, servizz jew manutenzjoni mhux xierqa jistgħu jikkawżaw ħsara lill-proprjetà, korriment, jew mewt. Aqra sew l-istruzzjonijiet dwar l-installazzjoni, it-tħaddim u l-manutenzjoni qabel tinstalla jew isservi dan it-tagħmir.

  • Always disconnect electrical power to the furnace before performing any service or maintenance.
  • Working with gas appliances can be hazardous. If you are not qualified to perform these procedures, contact a certified HVAC technician.
  • Ilbes tagħmir protettiv personali (PPE) xieraq, bħal ingwanti u protezzjoni għall-għajnejn.
  • Ensure all gas connections are properly sealed and tested for leaks after any work involving gas lines.
  • Taqbeż l-ebda apparat tas-sigurtà.

3. Prodott Aktarview

The flame sensor is a safety device in a gas furnace that detects the presence of a flame in the burner assembly. If the sensor does not detect a flame after the gas valve opens, it signals the furnace control board to shut off the gas supply, preventing unburnt gas from accumulating. This specific sensor is an upgraded replacement for Trane part number SEN01114.

Image of the Trane Furnace Flame Sensor PSE-T19

Figure 1: Trane Furnace Flame Sensor PSE-T19
This image displays the Trane Furnace Flame Sensor PSE-T19. It features a white ceramic insulator body, a metal mounting bracket with a screw hole, and a metal rod that extends into the flame path to detect the presence of a flame.

4. Setup u Installazzjoni

Installation of the flame sensor should only be performed by a qualified technician. The following steps are for informational purposes only.

  1. Skonnettja l-Enerġija: Turn off all electrical power to the furnace at the main service panel.
  2. Sib is-Sensor: Identify the existing flame sensor. It is typically a single metal rod positioned in the flame path of the burner assembly, often secured by one screw.
  3. Neħħi s-Sensor il-Qadim: Carefully disconnect the wire leading to the sensor. Remove the screw holding the sensor in place and gently pull the old sensor out.
  4. Installa Sensor Ġdid: Insert the new Trane PSE-T19 flame sensor into the same position. Ensure the metal rod is correctly positioned to be enveloped by the flame during operation. Secure it with the mounting screw.
  5. Qabbad il-Wiring: Reconnect the wire to the new flame sensor. Ensure the connection is secure.
  6. Irrestawra l-Enerġija: Ixgħel l-enerġija elettrika għall-forn.
  7. Operazzjoni tat-Test: Initiate a heating cycle and observe the furnace's ignition sequence. The main burners should ignite and remain lit.

5. Prinċipji Operattivi

When the furnace calls for heat, the igniter heats up, and the gas valve opens. As the gas ignites, the flame sensor, which is a small metal rod, becomes exposed to the flame. The flame rectifies a small alternating current (AC) into a direct current (DC) signal. This DC signal is sent to the furnace's control board, confirming the presence of a flame. If the control board does not receive this signal within a few seconds of ignition, it will shut off the gas supply as a safety measure, preventing unburnt gas from accumulating in the combustion chamber.

6. Manutenzjoni

Regular maintenance of the flame sensor is crucial for reliable furnace operation. A dirty flame sensor is a common cause of furnace malfunctions.

  • Tindif: Annually, or if experiencing ignition issues, carefully remove the flame sensor. Use fine-grit sandpaper or steel wool to gently clean off any carbon buildup or oxidation from the ceramic insulator and the metal rod. Do not use harsh chemicals or abrasive cleaners that could damage the sensor.
  • Spezzjoni: While cleaning, inspect the sensor for any signs of physical damage, such as cracks in the ceramic, corrosion, or a bent rod. Replace the sensor if any damage is observed.
  • Installazzjoni mill-ġdid: Reinstall the cleaned sensor, ensuring it is securely mounted and the wire connection is tight.

7 Issolvi l-problemi

If your furnace is experiencing issues related to ignition or short cycling, the flame sensor may be a contributing factor.

  • Furnace Ignites, then Shuts Off (Short Cycling): This is a classic symptom of a dirty or faulty flame sensor. The sensor detects the flame initially but then loses the signal, causing the furnace to shut down.
  • Furnace Fails to Ignite: While many factors can cause this, a completely failed flame sensor can prevent the furnace from even attempting to keep the gas valve open.

Passi għas-soluzzjoni tal-problemi:

  1. Clean the Flame Sensor: Follow the cleaning instructions in Section 6. This resolves most flame sensor-related issues.
  2. Iċċekkja l-Wiring: Ensure the wire connecting the flame sensor to the control board is secure and free from damage.
  3. Spezzjona għal Ħsara: Look for any visible damage to the sensor itself.
  4. Test for Continuity (Advanced): A qualified technician can use a multimeter to test the sensor's continuity and signal output.
  5. Ibdel is-Sensor: If cleaning and inspection do not resolve the issue, and the sensor is suspected to be faulty, replace it with a new Trane PSE-T19 or equivalent part.

8. Speċifikazzjonijiet

AttributValur
Numru tal-MudellPSE-T19 (SEN01114_v4)
ManifatturTrane
Dimensjonijiet tal-Prodott6 x 6 x 6 pulzieri
Piż tal-oġġett0.53 uqija
ASINB00ECEERIG

9. Informazzjoni dwar Garanzija

Warranty coverage for the Trane Furnace Flame Sensor PSE-T19 is typically provided by the seller or manufacturer at the time of purchase. Please refer to your purchase documentation or contact the original point of sale for specific warranty terms and conditions.

10. Appoġġ

For technical assistance, installation guidance, or troubleshooting beyond the scope of this manual, please contact the seller or a qualified HVAC professional. Ensure you have your product model number (PSE-T19 or SEN01114_v4) and purchase details available when seeking support.

Dokumenti Relatati - PSE-T19

Preview Forn Orizzontali li Jaħdem bil-Gass 'il Fuq/'l Isfel Trane XL 80: Speċifikazzjonijiet u Karatteristiċi
Gwida komprensiva għall-franijiet li jaħdmu bil-gass tas-serje Trane XL 80 (mudelli TUD2 u TDD2), li tiddeskrivi l-karatteristiċi, id-dejta tal-prestazzjoni, l-ispeċifikazzjonijiet elettriċi, u d-dimensjonijiet għal installazzjonijiet 'il fuq, 'l isfel, u orizzontali.
Preview Manwal tal-Installazzjoni, it-Tħaddim u l-Manutenzjoni tal-Forn tal-Gass tas-Serje S8 ta' Trane & American Standard
Gwida komprensiva għall-installazzjoni, it-tħaddim, u l-manutenzjoni ta' Trane u American Standard S8 Series Upflow/Downflow/Horizontal Gas-Fired 1-Stage u 2-StagFran b'Abbozz Indott b'Mutur ta' Effiċjenza Għolja. Jinkludi twissijiet ta' sigurtà, speċifikazzjonijiet, dijagrammi tal-wajers, u soluzzjoni ta' problemi.
Preview Forn tal-Gass b'Effiċjenza Għolja Trane XT95: Speċifikazzjonijiet u Karatteristiċi
Dejta dettaljata tal-prodott, karatteristiċi, benefiċċji, speċifikazzjonijiet, dejta dwar il-prestazzjoni, dijagrammi tal-wajers elettriċi, u dimensjonijiet għas-serje Trane XT95 ta' magni singoli b'effiċjenza għolja.tage, fran li jaħdmu bil-gass b'ventilazzjoni diretta, b'kondensazzjoni, assistiti minn fann.
Preview Bullettin tas-Servizz dwar il-Ħsarat tal-Bord tal-IFC ta' Trane & American Standard - Xogħol mill-Ġdid OBBLIGATORJU
Bullettin uffiċjali tas-servizz minn Trane u American Standard dwar ħsarat fil-bord tal-Kontroll Integrat tal-Forn (IFC) f'mudelli speċifiċi tal-forn. Dettalji dwar il-kodiċi tal-iżball 5, il-mudelli affettwati, u struzzjonijiet obbligatorji dwar ix-xogħol mill-ġdid.
Preview Trane S9V2 Series Gas Furnace: Installation, Operation, and Maintenance Manual
Comprehensive guide for installing, operating, and maintaining Trane and American Standard S9V2 series 2-stage condensing variable speed gas furnaces. Covers safety, installation procedures, specifications, and troubleshooting.
Preview Trane S9V2 Serje Tnejn StagDejta tal-Prodott tal-Forn li Jaħdem bil-Gass li Jikkondensa
Dejta dettaljata tal-prodott u speċifikazzjonijiet għat-Trane S9V2 Series Two StagForn li jaħdem bil-gass u li jikkondensa, li jkopri l-karatteristiċi, il-benefiċċji, il-varjazzjonijiet tal-mudell, l-ispeċifikazzjonijiet tekniċi, u t-tabelli tal-prestazzjoni tal-fluss tal-arja.