Allen-Bradley 1746-P2

Allen-Bradley 1746-P2 SLC 500 Power Supply Instruction Manual

1. Introduzzjoni

This manual provides essential information for the safe and effective installation, operation, and maintenance of the Allen-Bradley 1746-P2 SLC 500 Power Supply. The 1746-P2 is designed to provide reliable power to the SLC 500 programmable controller system, ensuring stable performance for industrial automation applications.

Please read this manual thoroughly before attempting to install or operate the unit. Retain this document for future reference.

2. Informazzjoni dwar is-Sigurtà

TWISSIJA: Electrical shock hazard. Always disconnect power before installing, removing, or wiring modules in the racks. Never operate any module selector switch while the circuit is energized. Failure to follow these instructions may result in serious injury or death.

Observe all local and national electrical codes. Installation and maintenance should only be performed by qualified personnel.

Fuq view of Allen-Bradley 1746-P2 Power Supply with warning label

Figura 2.1: Fuq view of the 1746-P2 Power Supply, showing the Allen-Bradley branding and a critical safety warning label regarding live circuits.

  • Aċċerta ruħek li s-sistema hija ertjata sew.
  • Use only specified fuse types and ratings for replacement.
  • Use copper wire rated for 75°C or higher for all connections.

3. Prodott Aktarview

The Allen-Bradley 1746-P2 is a power supply module designed for use with the SLC 500 chassis. It converts incoming AC line voltage into the necessary DC voltages required to power the SLC 500 processor and I/O modules within the rack. This module is part of Series C, indicating its revision level.

Allen-Bradley 1746-P2 Power Supply mounted in an SLC 500 rack

Figure 3.1: The Allen-Bradley 1746-P2 Power Supply shown connected to an SLC 500 chassis, illustrating its typical installation configuration.

Detailed product label of Allen-Bradley 1746-P2 Power Supply

Figura 3.2: Close-up view of the product label on the 1746-P2 Power Supply, displaying model number, serial number, and electrical specifications.

4. Installazzjoni

The 1746-P2 power supply is designed for direct mounting into any slot of an SLC 500 chassis. Ensure the chassis is securely mounted in its intended location before installing the power supply.

4.1 Proċedura ta 'Immuntar

  1. Ensure all power to the SLC 500 chassis is disconnected and locked out.
  2. Align the 1746-P2 module with an available slot in the SLC 500 chassis.
  3. Slide the module firmly into the slot until it is fully seated and the locking mechanism engages.
  4. Verify that the module is securely fastened to the chassis.
Qiegħ view of Allen-Bradley 1746-P2 Power Supply and rack with interconnect cable

Figura 4.1: Qiegħ view of the 1746-P2 Power Supply and an SLC 500 rack, showing the interconnect cable (1746-C7) which links the power supply to the backplane.

Close-up of Allen-Bradley 1746-C7 Rack Interconnect cable

Figura 4.2: Dettaljata view of the 1746-C7 Rack Interconnect cable, essential for connecting the power supply to the SLC 500 backplane.

5. Il-wajers

Proper wiring is critical for the safe and reliable operation of the 1746-P2 power supply. Refer to the product label for specific terminal designations and voltage rekwiżiti.

5.1 Konnessjoni tal-Enerġija tad-Dħul

  • The 1746-P2 accepts two ranges of AC input voltage: 85-132 VAC or 170-265 VAC.
  • The operating frequency is 50/60 Hz.
  • Connect the incoming AC power lines to the designated input terminals on the power supply. Ensure correct phase and neutral connections as per local electrical codes.
  • Always use 75°C rated copper wire for all power connections.

5.2 Qawwa tal-Ħruġ

The power supply provides the following DC outputs to the SLC 500 backplane:

  • 5 VDC f'5 Amperes
  • 24 VDC f'0.96 Amperes
  • User 24 VDC at 0.2 Amperes
Close-up of Allen-Bradley 1746-P2 Power Supply label showing voltage and output specifications

Figura 5.1: Dettaljat view of the power supply label, highlighting the input line voltage requirements and the various DC output specifications.

6. Operazzjoni

Once the 1746-P2 power supply is correctly installed and wired, apply the specified AC input voltage. The power supply will automatically convert and distribute the necessary DC voltages to the SLC 500 backplane, powering the processor and I/O modules. There are no user-adjustable controls on the power supply module itself for normal operation.

Refer to the SLC 500 processor and I/O module manuals for specific operational details of the overall system.

7. Manutenzjoni

Routine maintenance helps ensure the longevity and reliability of the 1746-P2 power supply.

7.1 Spezzjoni

  • Periodically inspect the power supply and its connections for any signs of damage, loose wiring, or excessive dust accumulation.
  • Kun żgur li l-fetħiet tal-ventilazzjoni jkunu ħielsa minn ostakli biex tevita li s-sħana tisħon iżżejjed.
Close-up of the ventilation grille on the Allen-Bradley 1746-P2 Power Supply

Figura 7.1: Close-up view of the ventilation grille on the 1746-P2 Power Supply, emphasizing the importance of keeping these areas clear for proper cooling.

7.2 Tindif

If cleaning is necessary, disconnect all power to the unit. Use a soft, dry cloth or a low-pressure air duster to remove dust and debris. Do not use liquid cleaners or solvents.

7.3 Sostituzzjoni tal-Fjus

If a fuse requires replacement, ensure power is disconnected. The specified fuse replacement is a 250V 3A FUSE (SANO SOC SD4 or BUSSMANN AGC 3). Always replace with a fuse of the identical type and rating.

8 Issolvi l-problemi

This section provides basic troubleshooting steps for common issues. For complex problems, contact qualified technical support.

8.1 No Power to SLC 500 System

  • Iċċekkja l-Qawwa tad-Dħul: Verify that the correct AC line voltage (85-132 VAC or 170-265 VAC, 50/60 Hz) is supplied to the power supply terminals.
  • Iċċekkja l-Fjusijiet: Inspect the internal fuses of the power supply. If a fuse is blown, replace it with the specified type (250V 3A FUSE, SANO SOC SD4 or BUSSMANN AGC 3).
  • Module Seating: Ensure the 1746-P2 module is fully seated in the SLC 500 chassis slot.
  • Kejbil ta' Interkonnessjoni: Verify the 1746-C7 interconnect cable is properly connected between the power supply and the backplane.

8.2 System Instability or Errors

  • VoltagE Produzzjoni: While not user-adjustable, ensure the power supply is providing stable output voltages (5VDC, 24VDC). This may require specialized test equipment.
  • Tagħbija żejda: Check if the total current draw from the SLC 500 modules exceeds the power supply's capacity.
  • Fatturi Ambjentali: Ensure the operating temperature is within the specified range and there is adequate ventilation.

9. Speċifikazzjonijiet

ParametruSpeċifikazzjoni
Numru tal-Mudell1746-P2
SerjeC
Input Voltage Firxa85-132 VAC jew 170-265 VAC
Frekwenza tad-dħul50/60 Hz
Output 1 (5 VDC)5 Amperes
Output 2 (24 VDC)0.96 Amperes
Output 3 (User 24 VDC)0.2 Amperes
Sostituzzjoni tal-Fjus250V 3A FUSE (SANO SOC SD4 or BUSSMANN AGC 3)
Tip ta' Wajer Rakkomandat75°C Copper Wire
Dimensjonijiet tal-Prodott (L x W x H)6 x 6 x 3.5 pulzieri
Piż1.35 Liri
Operating Temperature CodeT3C
Hazardous Location RatingClass 1, Groups A, B, C and D, Div 2

10. Garanzija u Appoġġ

Warranty information for the Allen-Bradley 1746-P2 Power Supply is typically provided at the point of purchase or through official Allen-Bradley (Rockwell Automation) channels. Please refer to your purchase documentation or contact your supplier for specific warranty terms and conditions.

For technical support, service, or additional product information, please contact Allen-Bradley (Rockwell Automation) directly or an authorized distributor. Their official website often provides comprehensive resources, including updated manuals, software, and contact information for support services.

Dokumenti Relatati - 1746-P2

Preview Allen-Bradley PanelView Operator Terminals User Manual
This user manual provides comprehensive information on Allen-Bradley PanelView Operator Terminals, covering their intended uses, types, features, configuration, applications, installation, and troubleshooting. It details various models including PanelView 550, 600, 900, 1000, and 1400.
Preview SLC 500 Hardware Migration Guide: Upgrade to CompactLogix
This guide provides comprehensive instructions for migrating from SLC 500 hardware to newer Allen-Bradley CompactLogix and Compact 5000 I/O systems. It covers controller and I/O module replacements, including wiring diagrams and software requirements for a smooth transition.
Preview SLC to CompactLogix Programming Migration Guide - Rockwell Automation
A comprehensive guide for migrating SLC programs and I/O to CompactLogix systems, detailing the process, requirements, and considerations for a smooth transition. This document provides insights into leveraging existing infrastructure while minimizing costs and risks.
Preview MicroLogix 1200 16-point DC Input Module Installation Instructions
Comprehensive installation guide for the Allen-Bradley MicroLogix 1200 16-point DC Input Module (1762-IQ16), covering mounting, wiring, specifications, and safety precautions for industrial environments.
Preview Allen-Bradley MicroLogix 1762-OB32T Solid State 24V DC Source Output Module Installation Instructions
Detailed installation instructions for the Allen-Bradley MicroLogix 1762-OB32T Solid State 24V DC Source Output Module. Covers safety information, environmental considerations, mounting procedures, wiring diagrams, I/O addressing, specifications, and Rockwell Automation support resources.
Preview 1746 SLC I/O to Compact 5000 I/O Conversion System Selection Guide
This guide provides information on selecting and installing the 1746 SLC I/O to Compact 5000 I/O Conversion System from Allen-Bradley. It details conversion modules, chassis, and wiring diagrams.