Sure-Lites LPX7

Sure-Lites LPX7 Universal Emergency Exit Light User Manual

Model: LPX7 | Brand: Sure-Lites

Introduzzjoni

The Sure-Lites LPX7 Series LED Exit Light is a universal emergency exit sign designed for general purpose applications. This unit features a durable polycarbonate housing and is equipped with LED lamps, offering energy efficiency and reliability. It supports dual voltage input (120/277 VAC) and includes a nickel cadmium battery for emergency operation, providing a minimum run time of 90 minutes during power loss.

The LPX7 series is engineered for ease of installation and maintenance, making it a suitable replacement for previous models like the CCX Series. It ships with components to configure either red or green exit legends, providing flexibility for various installation requirements.

Sure-Lites LPX7 Universal Emergency Exit Light

Figure 1: Sure-Lites LPX7 Universal Emergency Exit Light with red legend illuminated.

Informazzjoni dwar is-Sigurtà

Please read and understand all instructions before installing or operating this product. Failure to follow these instructions may result in electric shock, fire, or other hazards that could cause property damage or personal injury.

Kontenut tal-Pakkett

Ivverifika li l-komponenti kollha huma preżenti u mhux imħassra qabel tibda l-installazzjoni:

Setup u Installazzjoni

The LPX7 exit sign is designed for universal mounting, allowing for ceiling, wall, or end mount installations. Follow these steps for proper setup:

1. L-Għażla tas-Sit

Choose a mounting location that is visible and meets local building codes for emergency exit signage. Ensure the mounting surface is structurally sound to support the unit's weight.

2. Skonnettjar tal-Enerġija

Before starting any electrical work, turn off power to the circuit at the main breaker panel to prevent electric shock.

3. Preparazzjoni tal-Immuntar

Determine the desired mounting method (ceiling, wall, or end mount). The unit is designed for semi-flush mount installation. Refer to the dimensions diagram for precise measurements.

Dimensions of Sure-Lites LPX7 Emergency Exit Light

Figure 2: Dimensional drawing of the LPX7 exit light, showing overall width of 13 inches (330mm), overall height of 7 1/2 inches (190mm), and overall depth of 2 1/8 inches (54mm).

4. Konnessjoni Elettrika

Connect the unit to a 120 VAC or 277 VAC, 60 Hz power source. The LPX7 features dual voltage input. Ensure proper wiring according to the provided wiring diagram (typically found inside the unit or on a separate sheet). All connections must be secure and insulated.

5. Konnessjoni tal-batterija

Connect the internal Nickel Cadmium (NiCAD) battery. The battery is typically pre-installed but may require connecting a small plug to the circuit board. Ensure the connection is firm.

6. Legend Configuration

Insert the desired red or green legend panels into the unit. The LPX7 ships with both options, allowing for field configuration.

7. Assemblea Finali

Secure the unit to the mounting surface using the provided hardware. Ensure the housing is properly closed and secured.

8. Power Restoration & Testing

Restore power to the circuit. The exit sign should illuminate. Press the "TEST" button (usually a small push-button on the side or bottom of the unit) to verify emergency operation. The unit should switch to battery power and remain illuminated for at least 30 seconds. Release the button, and the unit should return to AC power.

Operazzjoni

The Sure-Lites LPX7 Emergency Exit Light operates automatically. When connected to a continuous AC power source, the LED lamps will remain illuminated, indicating the exit path. The internal Nickel Cadmium battery continuously charges while AC power is present.

Modalità ta 'Emerġenza

Fil-każ ta' qawwa outage or interruption to the AC supply, the unit will automatically switch to emergency mode, drawing power from its internal battery. The LED lamps will remain illuminated for a minimum of 90 minutes, providing essential egress lighting.

Buttuna tat-test

A test button is provided on the unit for routine maintenance checks. Pressing and holding this button simulates a power failure, allowing you to verify that the battery and lamps are functioning correctly in emergency mode. Release the button to return to normal AC operation.

Emergency exit light installed in a waiting area

Figura 3: Eżample installation of an emergency exit light in a commercial waiting area, demonstrating its function in a public space.

Emergency exit light installed in an auditorium

Figura 4: Eżample installation of an emergency exit light in an auditorium, highlighting its visibility in a large gathering space.

Manutenzjoni

Regular maintenance ensures the continued reliable operation of your emergency exit light. Always disconnect power before performing any maintenance.

Ittestjar ta 'kull xahar

Perform a monthly 30-second test by pressing the test button. The unit should operate on battery power for the duration of the test. If the lamps do not illuminate or dim significantly, the battery may need replacement or further charging.

Ittestjar Annwali

Conduct an annual 90-minute discharge test. Disconnect AC power to the unit and allow it to operate on battery power for 90 minutes. The lamps should remain illuminated for the entire duration. If the unit fails to operate for 90 minutes, the battery requires replacement.

Tindif

Clean the exterior of the unit periodically with a soft, damp cloth. Do not use abrasive cleaners or solvents, as these can damage the polycarbonate housing.

Sostituzzjoni tal-batterija

The Nickel Cadmium battery has a typical lifespan of 5-7 years. If the unit fails to meet the required emergency run time during testing, replace the battery with an approved Sure-Lites replacement battery. Ensure proper polarity when connecting the new battery.

Issolvi l-problemi

If your Sure-Lites LPX7 Emergency Exit Light is not functioning as expected, refer to the following common issues and solutions:

ProblemaKawża PossibbliSoluzzjoni
Unit does not illuminate when AC power is on.No AC power to the unit; Loose wiring connection; Faulty LED lamps.Check circuit breaker and power supply. Verify all wiring connections are secure. Contact qualified service personnel if lamps are faulty.
Unit does not illuminate in emergency mode (during test or power outagu).Battery not connected; Battery not charged; Battery has reached end of life; Faulty circuit board.Ensure battery is properly connected. Allow 24 hours for initial battery charge. Replace battery if it fails annual test. Contact qualified service personnel.
Lamps are dim in emergency mode.Batterija mhux iċċarġjata għalkollox; Il-batterija waslet biex tispiċċa.Allow unit to charge for 24 hours. If problem persists, replace battery.

If the problem persists after attempting these solutions, contact Sure-Lites customer support or a qualified electrician.

Speċifikazzjonijiet

KaratteristikaDettall
Numru tal-MudellLPX7
Input Voltage120/277 VAC, 60 Hz
Sors tad-DawlLED (2 Lamps)
Temperatura tal-Kulur5000K
Legend ColorConfigurable Red or Green
Legend Height6 pulzieri
Tip ta 'ImmuntarUniversal (Ceiling, Wall, End Mount)
Materjal tad-DjarPolikarbonat
Kulur tad-DjarAbjad
Tip ta 'batterijaNickel Cadmium (NiCAD)
Ħin ta 'EmerġenzaMinimu ta '90 minuta
Għoli Ġenerali7.5 pulzieri (190mm)
Wisa 'Ġenerali13 pulzieri (330mm)
Fond Ġenerali2.125 pulzieri (54mm)
Piż tal-oġġett2.88 liri

Garanzija u Appoġġ

Informazzjoni dwar Garanzija

The Sure-Lites LPX7 Emergency Exit Light comes with a garanzija ta 'sena from the date of purchase. This warranty covers defects in materials and workmanship under normal use and service. The warranty does not cover damage resulting from improper installation, misuse, abuse, or acts of nature.

Appoġġ għall-Klijent

For technical assistance, warranty claims, or replacement parts, please contact Sure-Lites customer support. Refer to the Sure-Lites official webis-sit jew l-imballaġġ tal-prodott għall-aktar informazzjoni ta' kuntatt aġġornata.

Nota: Always provide your product model number (LPX7) and date of purchase when contacting support to expedite assistance.

Dokumenti Relatati - LPX7

Preview Speċifikazzjonijiet u Dejta tal-Prodott tas-Sewwieq tal-LED ta' Emerġenza Sure-Lites EBPLEDL6SF
Speċifikazzjonijiet dettaljati, karatteristiċi, u dejta dwar l-installazzjoni għas-Sewwieq LED ta' Emerġenza Sure-Lites EBPLEDL6SF minn Cooper Lighting Solutions. Jinkludi l-prodott fuqview, dejta teknika, ċertifikazzjonijiet, u tpinġijiet dimensjonali.
Preview Manwal tal-Installazzjoni tal-Ballast ta' Emerġenza Sure-Lites EBP1400NCX/NCF
Gwida komprensiva għall-installazzjoni, it-tħaddim u l-manutenzjoni għall-ballasts ta' emerġenza Sure-Lites EBP1400NCX u EBP1400NCF, li tiddettalja l-prekawzjonijiet ta' sigurtà, id-dijagrammi tal-wajers u l-karatteristiċi.amp kompatibilità.
Preview Sure-Lites FirstLink Connected Emergency Lighting System | Cooper Lighting Solutions
Explore the Sure-Lites FirstLink connected emergency lighting system from Cooper Lighting Solutions. This brochure details system features, hardware, app control, and service plans designed for building safety and code compliance.
Preview Sure-Lites ELX Series LED Exit Sign - Technical Specifications
Detailed technical specifications for the Sure-Lites ELX Series self-powered LED exit signs, including features, construction, code compliance, energy data, and mounting options.
Preview Sure-Lites APEL Series Emergency Lighting Fixture
Explore the Sure-Lites APEL Series emergency light, featuring UL 924 listing, 90-minute runtime, adjustable LED heads, and a durable nickel cadmium battery. Ideal for reliable emergency egress with remote capacity options.
Preview Sure-Lites All-Pro APX RG Series LED Exit Sign - Technical Specifications
Detailed specifications for the Sure-Lites All-Pro APX RG Series LED Exit Sign, featuring thermoplastic housing, selectable red or green faces, AC-only or battery backup options, and compliance with UL924 and California Title 20.