Coolmay CX3G-24MT

Manwal tal-Istruzzjonijiet tal-Kontrollur PIL PLC Coolmay CX3G-24MT

Model: CX3G-24MT | Brand: Coolmay

1. Introduzzjoni

This manual provides detailed instructions for the installation, operation, programming, and maintenance of the Coolmay CX3G-24MT PID PLC Controller. The CX3G-24MT is a versatile programmable logic controller designed for industrial automation applications, featuring voltage support, high-speed pulse control, and motor drive capabilities. It integrates PID auto-tuning, linear arc interpolation, and supports various communication protocols.

Quddiem view of the Coolmay CX3G-24MT PLC controller

Figura 1: Quddiem view of the Coolmay CX3G-24MT PLC controller.

2. Prodott Aktarview

The Coolmay CX3G-24MT is a compact and powerful PLC controller offering 12 digital inputs (DI) and 12 digital outputs (DO). It supports multiple communication interfaces including RS232, RS485, and CAN, making it highly adaptable for various control systems. Key features include:

  • Highly integrated I/O, supporting up to 80 points in the CX3G series.
  • Supports up to 16 optional AD analog quantities.
  • 6-channel single-phase high-speed counting.
  • Standard 8-channel high-speed pulse output.
  • Advanced features like interrupt handling, linear arc interpolation, and PID auto-tuning.
  • 32K program capacity and 32K retentive registers.

Video 1: Product showcase highlighting the physical features and ports of the Coolmay CX3G PLC.

Labeled diagram of the CX3G PLC components and ports

Figure 2: Labeled diagram of the CX3G PLC components and ports. Key components include: 1. Mounting hole, 2. Terminal block for input signal of power supply, 3. Terminal block of digital output, 4. LED of Digital Input, 5. LED of Digital Output, 6. PWR: Power-up State (RUN: The light is On when the PLC is run), 7. RS485/RS232/CAN, 8. RS485, 9. RS485, 10. RUN/STOP PLC operational switch, 11. Analog output, 12. RS232, 13. DIN-Rail Slot (35mm), 14. Terminal block of digital input, 15. PLC USB programming port.

Diagram illustrating high-speed counting and pulse capabilities

Figure 3: Diagram illustrating the high-speed counting and high-speed pulse capabilities of the PLC.

3. Speċifikazzjonijiet

The following tables detail the specifications for the CX3G series, including the CX3G-24MT model.

3.1 Speċifikazzjonijiet Ġenerali

KaratteristikaDeskrizzjoni
Numru tal-MudellCX3G-24MT
Tip ta' MuturDC Motor, AC Motor
Kimika ta' tħassib kbirXejn
OriġiniIċ-Ċina kontinentali

3.2 CX3G Series Model Specifications

Table of specifications for various CX3G models

Figure 4: Detailed specifications for CX3G models including dimensions, I/O, and features.

MudellCX3G-16MCX3G-24MCX3G-32MCX3G-48MCX3G-34MCX3G-64MCX3G-80M
Dimensjoni85 * 90 * 36mm130 * 90 * 36mm200 * 90 * 36mm285 * 90 * 36mm
Daqs tal-qtugħ77 * 99mm122 * 99mm192 * 99mm277 * 99mm
InstallazzjoniFixed hole installation and DIN-Rail (35mm)
KaratteristiċiSupport interrupt, linear arc interpolation, PID auto-tuning. 32K program capacity, 32K retentive register
I/O levelInput: Passive NPN, public terminal isolated
Transistor output: NPN
Relay output: Normally open dry contact
I/O diġitali8DI/8DO12DI/12DO16DI/16DO24DI/24DO18DI/16DO32DI/32DO40DI/40DO
DO typeTransistor(MT) or mixed(2T6R)Relay(MR) or transistor(MT) or mixed(MRT)
(Relay output: max load 5A/ transistor output: max load 500mA)
High speed counting6 channel single-phase 60KHz or AB(Z) phase 2 channel 60KHz, 1 channel 10KHz
High speed pulse8 channels, Y0-Y3 is 100KHz, Y4-Y7 is 10KHz
High-speed counting + high-speed pulse < 480KHz
Analog I/O (optional)Null6AI/4AO2AI8AI/4AO12AI/8AO16AI/8AO4AI/4AO
AI type (optional)Type E/K/S/T/J thermocouple/ PT100/ PT1000/ NTC10K/ NTC50K/ NTC100K/
0~10V/ 0~5V/ 0-20mA/ 4-20mA
-5V~5V/ -10V~10V (except for CX3G-16M)
AO type (optional)0~10V/ 0-~5V/ 0~20mA/ 4~20mA
-5~5V/ -10~10V (2DA for 1 minus temperature)
Default COM port1 Mini type B USB port, 1 Rs232 (Interface terminal is mouse female port with 8 holes), 2 RS485 ports
FakultattivDefault 2 RS485 ports can be customized as:
1 RS485, 1 RS232,
or 1 RS485, 1 CAN (2.0A/B),
or 1 RS232, 1 CAN (2.0A/B)
CX3G-48M can add Ethernet port.
Default 2 RS485 ports can be customized as 1 RS485, 1 RS232,
CAN (2.0A/B) port is optional
SoftwareCompatible with WORKS 2

3.3 Analog Input Types and Ranges

Table detailing analog input types and their corresponding ranges

Figure 5: Detailed analog input types and their corresponding temperature/voltage/current ranges.

TipDeskrizzjonijiet
PTPT100 (Range: -200~500℃)
PT1000PT1000 (Range: -200~500℃)
EThermocouple type E (Range: 0~600℃)
E_Thermocouple type E, positive and negative temp. test (Range: -110~730℃)
KThermocouple type K, positive temperature test (Range: 0~1100℃)
K_Thermocouple type K, positive and negative temp. test (Range: -230~1370℃)
TThermocouple type T (Range: 0~400℃)
T_Thermocouple type T, positive and negative temp. test (Range: -230~400℃)
SThermocouple type S (Range: 0~1690℃)
S_Thermocouple type S, positive and negative temp. test (Range: -40~1690℃)
JThermocouple type J (Range: 0~800℃)
J_Thermocouple type J, positive and negative tempe. test (Range: -90~950℃)
NTC10KThermistor 10K (Range: -48~110℃)
NTC50KThermistor 50K (Range: -48~210℃)
NTC100KThermistor 100K (Range: -48~210℃)
V0 ~ 10V
V50 ~ 5V
V + customized voltage0~customized voltage (e.g., customized as 0~24V, the model is written as “V24”)
V_-10 ~ 10V
V5_-5 ~ 5V
A00 ~ 20mA
A44 ~ 20mA

4. Setup u Installazzjoni

The CX3G-24MT PLC controller can be installed using fixed holes or mounted on a 35mm DIN-Rail. Ensure proper ventilation and a stable environment for installation.

4.1 Dijagrammi tal-Wiring

Careful wiring is crucial for the correct and safe operation of the PLC. Refer to the diagrams below for connecting the PLC to other devices and for input/output configurations.

Wiring diagram for connecting CX3G PLC and HMI

Figure 6: Wiring diagram for connecting the CX3G PLC and HMI. This diagram illustrates connections for USB-232 serial port cable, PLC download cable, Mini type-B PLC download cable, HMI programming cable, and DC24V power supply.

Detailed input and output wiring diagrams

Figure 7: Detailed wiring diagrams including an input wiring diagram, relay output equivalent circuit diagram, and transistor output equivalent circuit diagram.

4.2 Protokolli ta' Komunikazzjoni

The CX3G-24MT supports a variety of communication protocols, enabling integration with different industrial devices.

Diagram showing PLC supporting multiple communication protocols

Figure 8: Diagram showing the PLC supporting multiple communication protocols, including Mitsubishi programming port, Mitsubishi BD board, Modbus RTU/ASCII/TCP, N:N communication, and EIP protocol, and connections to various devices like sensors, relays, thermocouples, soft starters, and frequency converters.

5. Istruzzjonijiet Operattivi

Once the PLC is properly installed and wired, ensure the power supply is stable (DC24V). The 'PWR' LED will illuminate when the PLC is powered on. The 'RUN' LED indicates that the PLC program is actively running. Use the RUN/STOP switch (labeled 10 in Figure 2) to control the PLC's operational state.

6. Programmazzjoni

The Coolmay CX3G-24MT PLC is compatible with WORKS 2 programming software. You can connect your computer to the PLC via the Mini type B USB port (labeled 15 in Figure 2) or the RS232 port (labeled 12 in Figure 2) for programming and debugging. Software and manuals are available on the Coolmay websit jew billi tikkuntattja l-appoġġ tal-klijent.

7. Manutenzjoni

To ensure the longevity and reliable operation of your Coolmay CX3G-24MT PLC controller, follow these maintenance guidelines:

  • Żomm l-unità nadifa u ħielsa minn trab u debris.
  • Iċċekkja regolarment il-konnessjonijiet tal-wajers kollha għal issikkar u sinjali ta' xedd.
  • Ensure adequate ventilation around the PLC to prevent overheating.
  • Avoid exposing the unit to excessive moisture, extreme temperatures, or corrosive environments.
  • Periodically back up your PLC programs.

8 Issolvi l-problemi

If you encounter issues with your CX3G-24MT PLC, consider the following common troubleshooting steps:

  • Ebda Qawwa/LEDs Mitfija: Check the DC24V power supply connection and ensure it is providing the correct voltage. Verify the power switch is in the 'ON' position.
  • PLC Not Running: Ensure the RUN/STOP switch is in the 'RUN' position. Check your program for errors using the WORKS 2 software.
  • Kwistjonijiet ta' Komunikazzjoni: Verify the correct cable is used (USB or RS232) and that the drivers are installed on your computer. Check communication settings (baud rate, parity, data bits, stop bits) in both the PLC and the programming software. For Modbus communication, ensure the protocol settings are correctly configured.
  • I/O Malfunction: Check wiring to input/output devices. Verify the status of input/output LEDs on the PLC. Test external devices independently to rule out external faults.

9. Għajnuniet għall-Utenti

  • Softwer tal-Programmazzjoni: The PLC is programmed using WORKS 2 software. Ensure you have the latest version for optimal compatibility and features.
  • Modbus Support: This PLC supports Modbus communication. Refer to the programming manual for detailed instructions on configuring Modbus RTU/ASCII/TCP protocols for integration with other devices.
  • Input Analog: When using optional analog inputs, ensure the correct sensor type (e.g., PT100, Thermocouple, Voltage, Current) is selected in your program to match your hardware.

10. Garanzija u Appoġġ

For technical support, software downloads, or further assistance, please contact Coolmay customer service. Software and manuals are provided free of charge and can be obtained from the official Coolmay website or by reaching out to the seller.

Dokumenti Relatati - CX3G-24MT

Preview Gwida għall-Utent tal-Pjattaforma tal-Cloud Coolmay: Reġistrazzjoni, Binding, u Konfigurazzjoni
Gwida komprensiva għall-użu tal-pjattaforma Coolmay Cloud għal tħaddim remot ta' PLC, li tkopri r-reġistrazzjoni tal-kont, l-irbit tat-tagħmir, il-konfigurazzjoni tal-varjabbli skjavi, u s-setup tal-parametri tan-netwerk. Dan id-dokument jagħti dettalji dwar il-passi għall-integrazzjoni tal-PLCs Coolmay mal-cloud għal monitoraġġ u kontroll imtejba.
Preview Manwal tal-Ipprogrammar tal-PLC Coolmay V20.81 - Istruzzjonijiet u Operazzjonijiet
Manwal komprensiv tal-ipprogrammar għall-kontrolluri tas-serje Coolmay PLC (V20.81), li jagħti dettalji dwar l-istruzzjonijiet, l-operazzjonijiet tal-apparat, u l-prinċipji tal-ipprogrammar. Kompatibbli mas-softwer Mitsubishi.
Preview Coolmay EX3S Series All-in-One PLC User Manual
User manual for Coolmay EX3S series all-in-one touch screen PLC, covering product features, specifications, wiring, installation, and programming guidance.
Preview Coolmay MX3G PLC User Manual: Features, Specifications, and Wiring
Comprehensive user manual for the Coolmay MX3G series Programmable Logic Controller (PLC). Details features, electrical and mechanical specifications, wiring diagrams, and installation guidelines for MX3G-16M and MX3G-32M models.
Preview Manwal tal-Ipprogrammar Coolmay QM3G Series HMI/PLC All-in-One: Karatteristiċi, Speċifikazzjonijiet, u Gwida għat-Tħaddim
This comprehensive programming manual details the Coolmay QM3G Series HMI/PLC All-in-one devices. It covers hardware specifications, programming precautions, PLC and HMI functionalities, communication protocols (Modbus, RS485, CAN, Ethernet), and software usage, providing essential information for engineers and technicians working with Coolmay's industrial automation solutions.
Preview Manwal tal-Ipprogrammar tal-PLC tas-Serje Coolmay L02: Karatteristiċi, Speċifikazzjonijiet, u Applikazzjonijiet
Esplora l-Manwal tal-Ipprogrammar tal-PLC tas-Serje Coolmay L02. Din il-gwida tagħti dettalji dwar il-karatteristiċi avvanzati tal-PLC L02, l-arkitettura tas-sistema, il-kompatibilità tal-moduli, il-protokolli ta' komunikazzjoni (Modbus, Ethernet/IP), u l-istruzzjonijiet tal-ipprogrammar. Ideali għal applikazzjonijiet ta' awtomazzjoni u kontroll industrijali.