TOMZN TOMPD-8S

TOMZN TOMPD-8S AC/DC Over and Under Voltage Protettur

Manwal ta' Istruzzjoni

1. Introduzzjoni

The TOMZN TOMPD-8S is a versatile AC/DC adjustable over and under voltage protector designed for single-phase electrical systems. This device provides reliable voltage monitoring and protection, ensuring the safety and longevity of connected equipment. Featuring microprocessor technology, a built-in LCD, and a user-friendly keypad, it allows for precise digital setting and real-time voltage display. Its compact modular design makes it suitable for Din rail mounting in various electrical panels.

2. Karatteristiċi

  • Powered directly by the measuring circuit.
  • Compatible with both AC and DC power supplies.
  • Microprocessor technology for highly accurate and repeatable protection.
  • Integrated LCD and keypad for precise digital settings and display.
  • Compact modular 43mm housing for Din rail installation.
  • Adjustable overvoltage u undervoltage limiti.
  • Independent adjustable delay times for overvoltage u undervoltage tgerbib.
  • Adjustable reset modes: automatic reset or manual reset.
  • Equipped with 1 Changeover (CO) and 1 Normally Closed (NC) contacts.
  • Failure recording function stores the last 3 fault events.
  • Flame retardant PC shell for enhanced safety.

3. Speċifikazzjonijiet

Tabella tal-Informazzjoni dwar il-Prodott

Figure 3.1: Product Information and Technical Specifications

Tabella 3.1: Speċifikazzjonijiet Tekniċi
ParametruValur
Numru tal-MudellTOMPD-8S
Provvista Rated VoltageAC/DC 110V~240V (50-60Hz)
Medda OperattivaAC/DC 40-310V
Voltage Medda ta' l-issettjarAC/DC 50.0 ~ 300V
Voltage Isteresi1.0-90.0V
Over- and Undervoltage Tripping Time0.1 ~ 999s
Ħin Awtomatiku Irrisettja0.1 ~ 999s
Kundizzjonijiet tax-Xogħol-25°C~65°C, ≤85%RH (non-condensing)
Żball tal-Kejl≤1% with adjustable voltagfirxa e
Failure RecordingLast 3 faults
Tip ta' Output1CO & 1NC
Kuntatt Kapaċità6A, 250VAC/30VDC (resistive load)
Grad ta' ProtezzjoniIP 20
Durabilità Mekkanika1,000,000 ċiklu
Qawwa Dielettrika> 2KVAC 1min
ĊertifikazzjoniCE
Karatteristika ta' ProtezzjoniIssiġillat
LCD Indication Table

Figure 3.2: LCD Indication Descriptions

Table 3.2: LCD Indication
Indikazzjoni LCDDeskrizzjoni
U>Overvoltage fault indication or overvoltage setting indication
U<Undervoltage fault indication or undervoltage setting indication
SETParameter setting indication

4. Installazzjoni u Wiring

The TOMPD-8S is designed for easy installation on a standard Din rail. Ensure all power is disconnected before attempting installation or wiring.

4.1 Installazzjoni Fiżika

  1. Mount the device securely onto a 35mm Din rail in your electrical panel.
  2. Kun żgur li jkun hemm ventilazzjoni adegwata madwar l-apparat biex tevita li jisħon iżżejjed.

4.2 Dijagramma tal-Wiring

Connect the device according to the wiring diagram below. Ensure correct polarity for DC circuits and proper phase/neutral connections for AC circuits. It is recommended to install appropriate fuses for protection.

Wiring Diagram for TOMZN TOMPD-8S

Figure 4.1: Standard Wiring Diagram for TOMPD-8S

Deskrizzjonijiet tat-Terminal:

  • A1+, A2-: Power supply input terminals.
  • 18(14): Common contact for the relay output.
  • 15(11): Normally Open (NO) contact for the relay output.
  • 26(22): Normally Closed (NC) contact for the relay output.
  • 25(21): Another Normally Open (NO) contact for the relay output.

The diagram shows the input from the top side, connecting Line (L+) and Neutral (N-) through fuses to the device's A1+ and A2- terminals. The relay output contacts (18, 15, 26, 25) are used to control a contactor (KM) which in turn controls the LOAD. The 'Power-off position' indicates the state when the load is disconnected.

5. Istruzzjonijiet Operattivi

The TOMPD-8S features an LCD display and a keypad for easy operation and parameter setting.

5.1 Wiri u Buttuni

TOMZN TOMPD-8S Buttons and Display

Figure 5.1: Front Panel with LCD and Control Buttons

Il-pannell ta 'quddiem jinkludi:

  • LCD: Displays current voltage and setting parameters.
  • RST (Red Button): Used for Reset/Test functions.
  • + (Black Button): Used for increasing setting values.
  • - (Grey Button): Used for decreasing setting values.
  • MOD (Green Button): Used for setting parameters and navigating menus.

5.2 Metodu ta 'Setting tal-Parametri

To configure the protection parameters, use the MOD button to enter the setting mode and navigate through options, and the + / - buttons to adjust values. The RST button can be used to exit or confirm in some cases.

Parameter Setting Method Table

Figure 5.2: Parameter Setting Method and Ranges

Tabella 5.1: Settings tal-Parametri
Indikazzjoni LCDParametruFirxa tal-issettjarDefault
U> SETOvervoltaglimitu minimuAD220: 50.0-300V-OFFAD220: 253V
tU> S SETOvervoltage ħin ta' dewmien0.1-999s5s
U< SETUndervoltaglimitu minimuAD220: 50.0-300V-OFFAD220: 187V
tU< S SETUndervoltage ħin ta' dewmien0.1-999s5s
U>U< SETVoltage isteresiAD220: 1.0-90.0VAD220: 10.0V
oRU SETIrrisettja l-modAU/HA/SA*2AU
t 3.0 S SETIrrisettja l-ħin0.1-999s3S
F50 SETVoltage frekwenza50/60Hz50Hz
r 3.0Item versionVer3.0---
End SETExit*4------

The device can display four monitoring data points in turn, including overvoltage protection (OV) and undervoltage protection (UV) settings, as shown in Figure 5.3.

Four Monitoring Data Displayed in Turn

Figura 5.3: Eżample of Monitoring Data Display

6. Manutenzjoni

The TOMPD-8S is designed for minimal maintenance. Regular checks can help ensure optimal performance:

  • Tindif: Keep the device clean and free from dust. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
  • Konnessjonijiet: Periodically check all wiring connections to ensure they are tight and secure. Loose connections can lead to intermittent operation or damage.
  • Ambjent: Ensure the operating environment remains within the specified temperature and humidity ranges (-25°C~65°C, ≤85%RH, non-condensing).

7 Issolvi l-problemi

If you encounter issues with your TOMPD-8S, refer to the following common problems and solutions:

  • Apparat mhux mixgħul: Check the input voltage at terminals A1+ and A2- to ensure it is within the rated supply voltage (AC/DC 110V~240V). Verify that fuses are intact.
  • Device trips unexpectedly: Riview your overvoltage u undervoltage threshold settings (U> SET, U< SET) and delay times (tU> S SET, tU< S SET). Ensure they are appropriate for your application and that the actual voltage is not exceeding these limits.
  • Device does not reset after a trip: Check the 'Reset mode' setting (oRU SET). If set to 'HA' (manual reset), you will need to manually reset the device after a fault. If set to 'AU' (automatic reset), verify the 'Reset time' (t 3.0 S SET) is configured correctly.
  • Vol mhux korretttage reading on LCD: Ensure the device is correctly wired and the input voltage is stable. If the error persists, the measurement error is typically ≤1%, but significant discrepancies may indicate a fault or incorrect wiring.

8. Għajnuniet għall-Utenti

  • Solar Inverter Protection: This device can be considered for protecting solar inverters from under/over voltage conditions. However, always verify compatibility with the specific DC output characteristics of your solar panel system and inverter. Ensure the operating range of the protector matches the inverter's voltage.
  • Setting Precision: When setting overvoltage jew undervoltage thresholds, consider a small buffer (hysteresis) to prevent frequent tripping due to minor voltage fluctuations. The adjustable voltage hysteresis (U>U< SET) can help manage this.
  • Storja tal-Ħtija: Utilize the failure recording feature to check the last 3 faults. This can provide valuable diagnostic information for recurring issues.

9. Garanzija u Appoġġ

For warranty information, technical support, or service inquiries, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase. Ensure to provide the model number (TOMPD-8S) and a detailed description of the issue when seeking support.

Dokumenti Relatati - TOMPD-8S

Preview TOMZN TOMPD-8S Three-phase VoltagManwal tal-Utent tar-Relay tal-Monitoraġġ elettroniku
User manual for the TOMZN TOMPD-8S Three-phase Voltage Monitoring Relay, detailing its features, technical specifications, installation, and operation for electrical protection.
Preview TOMZN DDS238-VAP Multifunctional Voltage and Current Protector User Manual
User manual for the TOMZN DDS238-VAP multifunctional protective device, detailing its features, specifications, operation, and installation for overvoltage, undervoltage, and overcurrent protection, along with energy metering capabilities.
Preview TOMZN DDS238-VAP Voltage Manwal għall-Utent tal-Protector
User manual for the TOMZN DDS238-VAP voltage protector, detailing safety information, installation instructions, precautions, applicable regulations, and function overview.
Preview TOMZN TOQ7e Dual Power Switch User Manual
User manual for the TOMZN TOQ7e Dual Power Automatic Transfer Switch, detailing safety information, installation instructions, precautions, and applicable regulations.
Preview TOMZN TOVA-63T WiFi Smart Circuit Breaker User Manual
User manual for the TOMZN TOVA-63T WiFi smart circuit breaker. Learn about its features including remote control via Tuya APP, real-time energy monitoring, and protection against voltage, current, and leakage faults. Includes installation guidance and safety information.
Preview Tomzn Isolation Type Automatic Transfer Switch Operating Instructions
Operating manual for the Tomzn Isolation Type Automatic Transfer Switch, detailing installation, operation, technical specifications, and wiring for reliable dual power source management.