Wattive GYAR9-AC-G

Wattive GYAR9-AC-G 2P 40A Automatic Reclosing RCCB Circuit Breaker User Manual

Model: GYAR9-AC-G

Brand: Wattive

1. Prodott Aktarview

The Wattive GYAR9-AC-G is an intelligent 2-pole, 40A Residual Current Circuit Breaker (RCCB) with an automatic reclosing function. Designed for AC230V systems, it features a digital display and a 300mA leakage protection value. This device automatically recloses the circuit after an accidental trip, reducing manual intervention and improving system efficiency. It supports both automatic and manual operating modes.

Wattive GYAR9-AC-G Automatic Reclosing RCCB Circuit Breaker

Stampa 1.1: Quddiem view of the Wattive GYAR9-AC-G Automatic Reclosing RCCB Circuit Breaker, showing its compact design, digital display, and control switches.

2. Informazzjoni dwar is-Sigurtà

TWISSIJA: Installation and maintenance of this device must be performed by qualified electricians only. Failure to follow these instructions can result in electric shock, fire, or serious injury.

  • Always disconnect power before installing, wiring, or servicing the circuit breaker.
  • Aċċerta ruħek li jkun hemm ertjar xieraq skont il-kodiċijiet elettriċi lokali.
  • Tħaddimx l-apparat jekk jidher li hu bil-ħsara.
  • Iċċekkja li l-konnessjonijiet kollha huma siguri u korretti qabel ma terġa' ġġib l-enerġija.
  • The device is designed for indoor use in environments within specified temperature and humidity ranges.

3. Karatteristiċi tal-prodott

The GYAR9-AC-G circuit breaker incorporates several advanced features for enhanced safety and operational efficiency:

  • Intelligent Automatic Reclosing: Automatically restores power after an accidental trip, minimizing downtime.
  • Automatic/Manual Switching: Allows selection between automatic reclosing and manual restoration modes.
  • Self-Locking Mode: Engages after multiple consecutive faults to ensure circuit safety before manual reset.
  • Display LED diġitali: Provides real-time status, fault codes, reclosing counts, and countdown timers.
  • Kostruzzjoni ta' Kwalità Għolja: Made from PC material with an IP20 protection grade.
  • Installazzjoni tal-Ferrovija DIN: Compatible with standard 35mm DIN rails.
Key Features of Wattive GYAR9-AC-G Circuit Breaker

Stampa 3.1: Visual representation of the key features, including PC material, IP20 protection, DIN rail installation, digital display, two switching modes, and LED indicator.

4. Speċifikazzjonijiet

ParametruValur
MaterjalPolikarbonat (PC)
Provvista VoltageAC 230V
Kurrent Rated40 A
Frekwenza Operattiva50/60 Hz
Leakage Protection Value300 mA
Sinjal ta 'KontrollAutomatic Reclosing + Dry Contact Control
Wiri Diġitali3-digit interruption code, reclosing count, countdown
Effective Control Signal Duration> 400 ms
Ħin tal-Għeluq< 1 s
Ħin tal-Ftuħ< 0.5 s
Control Cable Length≤ 1500 m
Konsum tal-Enerġija≤ 1.5 VA (static), ≤ 25 VA (dynamic)
Insulazzjoni Rated Voltage400 V
Rated Impuls jiflaħ Voltage (Uimp)4 kV (4.9 kV at sea level)
Ħajja Elettrika10,000 cycles, 3 cycles/min
Ħajja Mekkanika10,000 ċiklu
Klassi ta' ProtezzjoniIP20
Temperatura Ambjentali-25 sa +70 °C
Temperatura tal-Ħażna-40 sa +70 °C
Wiring Capacity (Power/Control Terminals)28-12 AWG (2.5 mm²)
Wiring Capacity (Auxiliary Signal Terminals)28-14 AWG (1.5 mm²)
ImmuntarDIN Rail EN 60715 (35 mm)
Dimensjonijiet (madwar)12 x 11.5 x 9 ċm
Piż (madwar)351 gramma
Product Size Information and Key Parameters

Stampa 4.1: Detailed diagram showing the physical dimensions of the circuit breaker and a summary table of its key operational parameters.

5. Installazzjoni u Wiring

The GYAR9-AC-G circuit breaker is designed for DIN rail mounting. Ensure all wiring is performed by a qualified professional in accordance with national and local electrical codes.

5.1. Immuntar

  1. Ensure the power supply to the distribution box is completely disconnected.
  2. Attach the circuit breaker securely onto a standard 35mm DIN rail.

5.2. Dijagramma tal-Wajers

Refer to the wiring diagram below for correct connection of the circuit breaker to the main power supply and loads. The diagram illustrates connections for the Line (L) and Neutral (N) inputs, as well as connections to multiple load circuits.

Dijagramma tal-Wiring tal-Prodott

Stampa 5.1: Detailed wiring diagram showing the connection points for the main power supply (L, N), the circuit breaker, and multiple downstream loads. It also indicates optional external opening and closing buttons.

  • Connect the main Line (L) and Neutral (N) wires to the designated terminals on the circuit breaker.
  • Connect the load circuits to the output terminals.
  • For manual control, an external normally open reset button can be connected to the auxiliary signal terminals (28-14 AWG, 1.5 mm²). The product does not require an external button for automatic reclosing.
  • Kun żgur li l-konnessjonijiet kollha huma ssikkati u iżolati sew.

6. Istruzzjonijiet Operattivi

The GYAR9-AC-G offers both automatic and manual operating modes, selectable via a switch on the device.

6.1. Automatic/Manual Switching Modes

The device features an AUTO/MANU selector switch. The 'LOCK' mechanism prevents accidental operation when engaged.

  • Modalità AUTO: In this mode, the circuit breaker will automatically attempt to reclose after a fault trip. The digital display will show a red flashing light when the gate is open and a green flashing light when the gate is closing.
  • MANU Mode: In this mode, the circuit breaker requires manual restoration after a fault trip. The yellow light on the display will remain on for manual opening and closing.
  • LOCK Function: When the 'LOCK' switch is engaged (pulled out), the circuit breaker cannot be closed, ensuring electrical safety during maintenance or inspection and preventing accidental contact.
Automatic and Manual Switching Modes with Digital Display Indicators

Stampa 6.1: Close-up view of the circuit breaker's controls, highlighting the leakage switch, safety lock, broken code display, LED digital display, working mode selection (AUTO/MANU), and operating handle. A table explains the automatic/manual switching and corresponding LED digital display behaviors.

6.2. Self-Locking Mode

To prevent continuous reclosing into a persistent fault, the device enters a self-locking mode after multiple consecutive trips:

  1. First Fault: The circuit breaker automatically recloses after 9 seconds.
  2. Second Fault: The circuit breaker automatically recloses after 59 seconds.
  3. Third Fault: The circuit breaker automatically recloses after 299 seconds.
  4. Fourth Fault: After the fourth consecutive fault, the recloser enters self-locking mode. Manual intervention is required. The circuit must be checked for safety, and then the gate must be manually reopened.

After 40 seconds of self-locking, the device will automatically recover and be ready for manual or automatic operation again, provided the fault has been cleared.

Self-Locking Mode Explanation

Stampa 6.2: Illustration of the self-locking mode, showing the digital display countdowns for the first three reclosing attempts and the final self-locking state after the fourth fault.

6.3. Digital Display Information

The 3-digit digital display provides critical operational feedback:

  • Interruption Code: Displays a code indicating the type of interruption.
  • Reclosing Count: Shows the number of times the circuit has been opened and reclosed.
  • Timer tal-Countdown: Indicates the remaining time until the next automatic reclosing attempt or recovery from self-locking mode.
  • Indikatur LED: Green for normal operation, red for MCB overcurrent error.

7. Manutenzjoni

Manutenzjoni regolari tiżgura l-lonġevità u t-tħaddim affidabbli tas-circuit breaker tiegħek.

  • Spezzjoni Viżwali: Periodically inspect the device for any signs of physical damage, discoloration, or loose connections.
  • Tindif: Żomm l-apparat nadif u ħieles mit-trab u l-fdalijiet. Uża drapp niexef u artab għat-tindif. Tużax prodotti tat-tindif likwidi.
  • Buttuna tat-test: Press the 'Test Monthly' button (if available) regularly to verify the leakage protection function. Follow the instructions on the device for testing.
  • Kontroll Professjonali: Have a qualified electrician inspect the device and electrical system annually.

8 Issolvi l-problemi

If the circuit breaker is not functioning as expected, consider the following:

  • Device in Self-Locking Mode: If the device has tripped multiple times and is not reclosing, it may be in self-locking mode. Check the circuit for faults and manually reset the breaker.
  • Ebda Qawwa: Verify the main power supply to the distribution box.
  • Incorrect Mode: Ensure the AUTO/MANU switch is in the desired position. If in MANU mode, manual reset is required.
  • Ħsara Persistenti: If the breaker trips immediately after reclosing, there is a persistent fault in the circuit. Disconnect power and have a qualified electrician inspect the wiring and connected loads.
  • Żball fil-Wiri Diġitali: Note any error codes displayed and consult a qualified electrician.

9. Oqsma ta' Applikazzjoni

The Wattive GYAR9-AC-G intelligent circuit breaker is suitable for a wide range of applications requiring reliable electrical protection and automatic fault recovery:

  • Photovoltaic grid-connected AC distribution boxes
  • Unmanned mobile phone base stations
  • Elevaturi
  • Smart homes
  • Fabbriki intelliġenti
  • New energy vehicle charging stations
Applikazzjoni tal-Prodott Eżamples

Stampa 9.1: Collage of images depicting various application environments for the circuit breaker, including mobile phone base stations, solar power installations, electric vehicle charging points, and smart factory settings.

10. Garanzija u Appoġġ

Specific warranty information is not provided in this manual. Please refer to the product packaging or contact your retailer or the manufacturer, Wattive, for details regarding warranty coverage and technical support.

For technical assistance or inquiries, please visit the official Wattive websit jew ikkuntattja lid-dipartiment tas-servizz tal-konsumatur tagħhom.

© 2025 Wattive. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.