Tyenaza ETCR2100A+

Tyenaza ETCR2100A+ Digital Clamp Resistance Tester User Manual

Model: ETCR2100A+

1. Introduzzjoni

This manual provides essential instructions for the safe and effective operation of the Tyenaza ETCR2100A+ Digital Clamp Resistance Tester. This device is designed for accurate measurement of grounding resistance and circuit resistance, featuring a dustproof and shockproof structure for reliable performance in various industrial and departmental settings.

Please read this manual thoroughly before using the instrument to ensure proper handling and to prevent damage or injury.

Tyenaza ETCR2100A+ Digital Clamp Testjar tar-Reżistenza

Image 1.1: The Tyenaza ETCR2100A+ Digital Clamp Resistance Tester, showing its overall design with the clamp jaw and control panel.

2. Informazzjoni dwar is-Sigurtà

Always observe the following safety precautions to avoid electric shock, injury, or damage to the instrument:

  • Tużax l-istrument jekk jidher li għandu ħsara jew qed jaħdem b'mod mhux normali.
  • Kun żgur li l-kompartiment tal-batterija jkun magħluq sew qabel l-operazzjoni.
  • Do not attempt to measure live circuits beyond the specified voltage limits (CAT III 150V).
  • Avoid using the instrument in wet environments or during thunderstorms.
  • Refer to qualified personnel for any repairs or servicing.
  • Keep the instrument away from strong magnetic fields and electric fields exceeding specified limits.

3. Kontenut tal-Pakkett

Ivverifika li l-oġġetti kollha huma preżenti fil-pakkett:

  • 1 x ETCR2100A+ Digital Clamp Testjar tar-Reżistenza
  • 1 x Accessory (likely a test ring or similar calibration aid)
  • 1 x Manwal tal-Utent (dan id-dokument)
  • 1 x Kaxxa tal-Ħażna

Note: 1.5V AA batteries (x4) are required and are not included in the package.

ETCR2100A+ Digital Clamp Resistance Tester with included accessory

Image 3.1: The ETCR2100A+ tester shown with a standard test ring, which is typically included as an accessory for calibration or verification.

4. Karatteristiċi tal-prodott

The ETCR2100A+ Digital Clamp Resistance Tester offers the following key features:

  • Display Multifunzjonali: Resistance and current values are displayed simultaneously on a new black luxury screen.
  • Preċiżjoni Għolja: Microprocessor-controlled for precise grounding resistance detection, utilizing fast filtering technology to minimize interference.
  • Ġestjoni tad-Data: Features real-time clock, data storage for up to 99 sets, and data retrieval capabilities.
  • Allarm Awdibbli u Viżwali: "Beep beep beep" alarm sound with adjustable threshold settings for resistance (1-199 Ω) and current (1-499mA).
  • Funzjonijiet Awtomatiċi: Automatic shutdown and fully automatic gear shifting for ease of use.
  • Disinn robust: Shockproof and dustproof structure, suitable for demanding industrial environments.
  • Applikazzjoni wiesgħa: Ideal for telecommunications, power, meteorology, computer rooms, oil fields, power distribution lines, tower transmission lines, gas stations, factory grounding grids, and lightning rod systems.
Close-up view tal-clamp jaws of the ETCR2100A+ tester

Immaġni 4.1: Close-up view tas-cl robustaamp jaws, highlighting the double insulation and structural features designed for durability and safety.

5. Setup

5.1 Installazzjoni tal-batterija

The ETCR2100A+ requires four (4) 1.5V AA batteries (not included).

  1. Sib l-għatu tal-kompartiment tal-batterija fuq wara tal-istrument.
  2. Use a suitable tool (if necessary) to open the battery compartment.
  3. Insert four 1.5V AA batteries, ensuring correct polarity (+/-) as indicated inside the compartment.
  4. Agħlaq l-għatu tal-kompartiment tal-batterija sew.

5.2 Qawwa Inizjali

Wara l-installazzjoni tal-batterija, agħfas il-buttuna ON/OFF button to power on the device. The LCD display will illuminate, indicating the device is ready for use.

6. Istruzzjonijiet Operattivi

6.1 Kejl Bażiku

To perform a grounding resistance test:

  1. Kun żgur li l-istrument ikun mixgħul.
  2. Iftaħ il-clamp xedaq billi tagħfas il-grillu.
  3. Poġġi l-clamp around the grounding conductor or circuit to be measured. Ensure the jaws are fully closed around the conductor.
  4. The resistance value will be displayed on the LCD screen. The device features fully automatic shifting.
  5. The single measurement time is approximately 0.5 seconds.
ETCR2100A+ tester clamping an insulated ground wire

Image 6.1: The ETCR2100A+ tester shown clamping an insulated ground wire, demonstrating its capability to accurately test even insulated conductors.

6.2 Single Point Grounding System, Auxiliary Measurement

For single point grounding systems where direct clamp measurement of the lead wire is not feasible, auxiliary methods can be used. The two-point method is illustrated below:

Diagram illustrating the two-point auxiliary measurement method for single point grounding systems

Image 6.2: Diagram showing the two-point method for auxiliary grounding resistance measurement. It depicts a grounding rod (RA) connected to a single point, with a wire extending to a natural grounding point (e.g., water pipe, buried metal) for measurement.

Biex tuża dan il-metodu:

  • Identify a natural grounding point with a low resistance value near the grounding point to be measured. Examples include a water pipe, fire hydrant, or other deeply buried metal structure.
  • Connect a wire from the point to be measured to this auxiliary grounding point.
  • Clamp the ETCR2100A+ around the connecting wire to perform the measurement.
ETCR2100A+ Digital Clamp Resistance Tester in an industrial substation environment

Image 6.3: The ETCR2100A+ tester positioned in an industrial substation, illustrating a typical application environment for grounding resistance measurement.

6.3 Data Storage and Retrieval

The instrument can store up to 99 sets of measurement data.

  • To store data: After a measurement, press the MEM button to save the current reading.
  • To retrieve data: Press the MEM button repeatedly to cycle through stored data.

6.4 Funzjoni ta 'allarm

The ETCR2100A+ features an audible and visual alarm for out-of-range measurements.

  • To activate/deactivate the alarm: Press the AL buttuna.
  • To set alarm thresholds: Refer to the device's on-screen menu or specific instructions for setting resistance (1-199 Ω) and current (1-499mA) alarm limits.
Hand holding the ETCR2100A+ Digital Clamp Testjar tar-Reżistenza

Image 6.4: A hand holding the ETCR2100A+ tester, demonstrating its ergonomic design and ease of handling during operation.

7. Manutenzjoni

7.1 Tindif

Imsaħ il-barra tal-istrument b'ċarruta ratba u damp cloth. Do not use abrasive cleaners or solvents. Ensure the device is powered off before cleaning.

7.2 Ħażna

When not in use for extended periods, remove the batteries to prevent leakage. Store the instrument in its provided storage box in a cool, dry place, away from direct sunlight and extreme temperatures.

7.3 Kalibrazzjoni

Regular calibration by qualified personnel is recommended to maintain measurement accuracy, especially after prolonged use or if accuracy is suspected to be compromised.

8 Issolvi l-problemi

ProblemaKawża PossibbliSoluzzjoni
L-apparat ma jixgħelx.Batteriji mejta jew installati ħażin.Ibdel il-batteriji b'batteriji AA ġodda ta' 1.5V, filwaqt li tiżgura l-polarità korretta.
Qari mhux preċiż.Jaws not fully closed; interference from external fields; dirty jaws; need for calibration.Ensure jaws are fully closed. Move away from strong magnetic/electric fields. Clean jaws. Consider professional calibration.
L-allarm ħsejjes kontinwament.Measurement exceeds set alarm threshold.Check the measured value against the set alarm limits. Press the AL button to silence or deactivate the alarm.
Id-displej huwa vojt jew jitteptep.Low battery power; environmental conditions (extreme temperature/humidity).Replace batteries. Operate within specified temperature and humidity ranges (-20 ℃ to 55 ℃; 10% RH to 90% RH).

9. Speċifikazzjonijiet

MudellETCR2100A+
FunzjoniGrounding resistance test, circuit resistance test, leakage current test
Firxa tar-reżistenza0.01 Ω sa 200 Ω
Riżoluzzjoni tar-reżistenza0.001 Ω
Medda KurrentiNone (for leakage current test, the range is 1-499mA for alarm setting)
Ħażna tad-Data99 sett
Alarm Threshold Setting Range (Resistance)1-199 Ω
Alarm Threshold Setting Range (Current)1-499mA
Temperatura tax-Xogħol u Umdità-20 ℃ to 55 ℃; 10% RH to 90% RH
Display LCD4 digit LCD digital display
Daqs tal-WiriApprox. 47 x 28.5mm / 1.85 x 1.12in (L x W)
Jaw Size (Round)Approx. 32mm / 1.26in diameter
Jaw Opening Size (Long)Approx. 32mm / 1.26in
Clamp Size (Long Jaw)Madwar 260 x 90 x 56mm / 10.24 x 3.54 x 2.2 pulzieri
Livell ta' ProtezzjoniInsulazzjoni doppja
Karatteristiċi StrutturaliClamp shaped CT
Gear ShiftingFully automatic shifting
Qasam Manjetiku Estern<40A / m
Qasam Elettriku Estern<1V/m
Ħin ta' Kejl Uniku0.5 sekonda
Frekwenza tal-Kejl tar-ReżistenzaGreater than 1KHz
Frekwenza Kurrenti Ttestjata50/60Hz awtomatiku
Provvista tal-Enerġija4 x 1.5V batteriji AA (mhux inklużi)
MaterjalABS
Piż tal-oġġett2.13 Kilogrammi / 4.69 liri

10. Garanzija u Appoġġ

Għal informazzjoni dwar il-garanzija, appoġġ tekniku, jew mistoqsijiet dwar is-servizz, jekk jogħġbok ikkuntattja lill-bejjiegħ tiegħek jew lill-manifattur direttament. Żomm l-irċevuta tax-xiri tiegħek bħala prova tax-xiri.

Manufacturer: Tyenaza

© 2023 Tyenaza. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.